13-834R-013SEQUENCE OF OPERATION: VAV AHU WITH HYDRONIC COOLING: BUILDING AUTOMATION SYSTEM INTERFACE: THE BUILDING AUTOMATION SYSTEM ( BAS) WILL SEND THE CONTROLLER OCCUPIED COMMANDS. THE BAS WILL ALSO SEND A DISCHARGE AIR TERMPERATURE SETPOINT AND A DUCT STATIC PRESSURE SETPOINT. IF COMMUNICATION IS LOST WITH THE BAS, THE CONTROLLER WILL OPERATE IN THE OCCUPIED MODE USING ITS DEFAULT SETPOINTS, OCCUPIED: DURING OCCUPIED PERIODS. THE SUPPLY FAN WILL RUN CONTINUOUSLY AND THE OUTSIDE AIR DAMPER WILL OPEN TO MAINTAIN MINIMUM VENTILATION REQUIREMENTS, THE CHILLED WATER VALVE WILL MODULATE TO MAINTAIN THE DISCHARGE AIR TEMPERATURE COOLING SETPOINT (55F ADJ.). IF THE DISCHARGE AIR TEMPERATURE SENSOR FAILS DURING NORMAL OPERATION, THE CHILLED WATER VALVE WILL CLOSE AND AN ALARM WILL BE ANNUNCIATED. VAV SUPPLY FAN: WHEN THE CONTROLLER IS IN THE OCCUPIED MODE, THE SUPPLY FAN WILL OPERATE CONTINUOUSLY AND ITS SPEED WILL BE MODULATED TO MAINTAIN THE DUCT STATIC PRESSURE SEiPOINT. THE DUCT STATIC PRESSURE SETPOINT IS SENT BY THE BAS AND IS RESET BETWEEN THE MINIMUM AND MAXIMUM STATIC PRESSURE LIMITS TO MAINTAIN THE "CRITICAL ZONE' IF THE SUPPLY FAN FAILS TO PROVE STATUS FOR 30 SECONDS (ADJ.), THE FAN WILL BE COMMANDED OFF, THE OUTSIDE AIR DAMPER AND CHILLED WATER VALVE WILL CLOSE AND AN ALARM WILL BE ANNUNCIATED- A MANUAL RESET IS REQUIRED TO RESTART THE FAN. A HARDWIRED, HIGH STATIC PRESSURE CUT -OFF SWITCH IS ELECTRICALLY INTERLOCKED WITH THE VARIABLE SPEED DRIVE. IF THE HIGH STATIC PRESSURE CUT -OFF SWITCH IS TRIPPED, THE FAN WILL STOP, THE OUTSIDE AIR DAMPER AND CHILLED WATER VALVE WILL CLOSE AND AN ALARM WILL BE ANNUNCIATED. A MANUAL RESET OF THE HIGH STA11C PRESSURE CUT -OFF SWITCH WILL BE REQUIRED TO RESTART THE FAN. OUTSIDE AIR CONTROL: OUTSIDE AIR FLOW SHALL BE MEASURED BY AFS -1 TO ENSURE MINIMUM OUTSIDE AIR PROVIDED TO THE SPACE RETURN DAMPER D -RET SHALL MODULATE TO CONTROL OUTSIDE AIR QUANTITY. A HARDWIRED, LOW LIMIT TEMPERATURE SWITCH IS ELECTRICALLY INTERLOCED WITH THE VARIABLE SPEED DRIVE IF THE LOW LIMIT TEMPERATURE SWITCH IS TRIPPED (38T ADJ.). THE OUTSIDE AIR DAMPER WILL CLOSE. THE CHILLED WATER VALVE WILL OPEN TO 100% (ADJUST PER CLIMATE) AND AN ALARM WILL BE ANNUNCIATED. A MANUAL RESET OF THE LOW LIMIT SWITCH WILL BE REQUIRED TO RESTART THE FAN. FILTER STATUS: A DIFFERENTIAL PRESSURE SWITCH WALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE FILTER WHEN THE FAN IS RUNNING. IF THE SWITCH CLOSES DURING NORMAL OPERATION, A DIRTY FILTER ALARM WILL BE ANNUNCIATED. FIRE ALARM: UPON ACTIVA11ON OF FIRE ALARM, RTU SHALL SHUT DOWN ALONG MATH ASSOCIATED EXHAUST FAN. EXHAUST FAN: THE AUTO POSITION OF THE STARTER SWITCH SHALL BE CONTROLLED BY THE CONTROL SYSTEM. FAN SHALL SHUT DOWN FROM A SIGNAL FROM THE FIRE ALARM PANEL. THE CONTROL SYSTEM SHALL ALARM IF THE FAN FAILS TO START. FAN SHALL BE MATCHED TO THE ASSOCIATED AIR HANDLING UNIT WHICH SERVES THE SAME AREA AS THE EXHAUST FAN. THE CONTROL SYSTEM SHALL START THE FAN WHENEVER THE AHU IS ENERGIZED AND SHALL DEENERGIZE THE FAN WHENEVER THE AHU IS DEENERGIZED. UNOCCUPIED MODE: THERE IS NO UNOCCUPIED MODE ASSOCIATED WITH THIS SCOPE OF WORK. BASIS OF DESIGN: SIEMENS CONTROLS, COORDINATE AND CONNECT TO EXISTING BUILDING BMS. DISCHARGE AIR TEMPERATURE SENSOR.. ELECTRIC COIL RELAY SUPPLY AIR ILu o I I I CONTROL CONTROL DAMPER 24 VOLT WIRING FROM CONTROL PANEL PANEL NOTE: A TRANSFORMER SHALL BE PROVIDED AS REQUIRED. NETWORK INTERFACE TT -1 WITH THE VAV CONTROLLER. AI SPACE SETPOINT THE DEADBAND SHALL NOT EXCEED + /- 0.5-F. THE FOLLOWING POINTS SHALL BE MAPPED TO BE TRENDED FROM THE OPERATORS WORKSTATION, A VAV BOX SUMMARY SHALL BE PROGRAMMED TO ALLOW THE OPERATOR TO VIEW THE FOLLOWING POINTS IN TABULAR FORM: - SPACE TEMPERATURE SETPOINT - CURRENT SPACE TEMPERATURE - CFM SETTING - CURRENT CFM - DAMPER POSITION - COIL STATUS - VAV DISCHARGE AIR TEMP TYPICAL VARIABLE VOLUME BOX WITH ELECTRIC COIL 04SC„LE: N.s A-4 AHU-131A3 CONTROL DIAGRAM V I SCALE: NTS CONTROLS SHALL MATCH EXISTING BUILDING CONTROL SYSTEM (TYPICAL): SIEMENS CONTROLS. 01M Ethernet Connect to Hospitals EXISTING Remote Apogee Server To Existing Network Control Panels Existitng Control Panel NETWORK RISER 0 . NTs EMERGENCY OFF SHALL STOP FAN UNDER ALL CONDITIONS VFD TERMINAL BLOCK VERIFY WITH VFD MANUFACTURER ACTUAL TERMINALS TO PERFORM THE FUNCTION INDICATED. TS -FZ FREEZESTAT SD -SA SMOKE DETECTOR ESO -D -SAS S.DMPR END SWITCH = SPS -SHI STATIC PRESS, HIGH LIMIT = SPS -SLO STATIC PRESS. LOW LIMIT -,- FIRE ALARM RELAY AHU SUPPLY FAN SAFETY WIRING HARDWIRED SAFETIES IN ADDITION TO NETWORK INTERFACE BETWEEN VFD AND DDC CONTROL SYSTEM. 120VAC FROM CONTROL XFMR OHAND-T- OOFF .AUTO--1 DDC SYSTEM RELAY FA COIL OL'S FAN STARTER FIRE ALARM RELAY TO SHUTDOWN FAN PER ASSOCIATED AHU SEQUENCE. EXHAUST 'ACE MPERATURE ANSMITTER AI FREEZESTAT TS -FZ FZ -OR FRZ OVERRIDE FANS SHALL BE MATCHED TO THE ASSOCIATED AIR HANDLING UNIT WHICH SERVES THE SAME AREA AS THE EXHAUST FAN. THE DDC CONTROL SYSTEM SHALL START THE FAN WHENEVER THE AHU IS ENERGIZED AND SHALL DEENERGIZE X THE EXHAUST FAN WHENEVER THE AHU IS DDEENERGIZED. AHU -B1A3 CONNECT EXISTING FAN CONTROLS TO NEW RTU. 'XCM Controller BUILDING MANAGEMENT SYSTEM SHALL START AND STOP FAN AND CHECK STATUS. CONTROLS SHALL CONNECT TO EXISTING BUILDING CONTROL SYSTEM: SIEMENS CONTROLS. EXISTING EF-EX CONTROL 02SCALE:NTS E 7 U c _ O O d U a 0 r1 Cn Ol M- p ('� �G �O � v� N M I ri r0 II as u- �,o 1,a 5 8 I Q Ln u-) o c o o + O C O M M W U-) C� O -E N Q) O ,� O x a g N U) U a � > x O C O d W c 4� CP ro EQ � a REVISIONS MARK: REMARKS: J Q CL W VJ O W Awm =U 6 a(L W ''O^ Q V, ei• w t,� �p�° 'PII�C, GIN ER.; �d��a -. e MECHANICAL CONTROLS Job No: 412474.00 Date: File: Sheet Title: Sheet No: M9,02