13-781R-044E i i I D C E. :i= U) I M 0 rV JI Z W UI a a I I 2 U W QI ,u V) rn C a� E 0 U 0 0 U) U) U t In L 'i 111 fa u_ U) Q C G a It In O� oA d' rl 0 fV U) L 0 ..0 Q ISOLATION ROOM EXHAUST FAN The Isolation Room Exhaust Fan runs at all times. When running, the speed of the VFD will be controlled to maintain a constant volume of air measured by the fan peizometer ring via transducer. The Isolation Room Exhaust Fan shall not be shut down by Fire Alarm. If the Isolation Room Exhaust Fan fails (as measured by the Differential Pressure Switch), all interlocked constant volume terminal unit dampers serving the Isolation Room will be overridden to closed. Once the fan returns to its normal state (running), all terminal unit dampers will return to normal control. A differential pressure switch shall be installed across the final filter. An alarm will be generated when the filter is dirty. Dirty setpoint 1.50 ". An alarm will also be generated if the fan loses status. 1410518 DPS- 2 1.5 IN WG E01FSS 1410574 DPS- 1 SETPTN WG rn,ci AM AND TRANSDUCER cR ^Y� TYPICAL ISOLATION ROOM EXHAUST FAN CONTROL DIAGRAM - ISOLATION ROOM EXHAUST FAN n 00 HTE -1 50 %RH AFF CONTROL DIAGRAM - CRAC UNIT EA INSTALLATION NOTES: O TEC-1 TO BE MOUNTED IN MANUFACTURER SUPPLIED CONTROLLER ENCLOSURE O LOCATE AS SHOWN ON FLOOR PLANS /CONTRACT DOCUMENTS O3 CRAC UNIT SHALL BE TIED INTO EXISTING BMS SYSTEM FOR MONITORING FOR STOP,START, STATUS. ALARM SHALL OCCUR BY 8, AT EXISTING BMS 1� SYSTEM IN ROOM EXCEEDS 78F, 60 %RH. TO CLOSEST PANEL TTE -1 HT E -1 SET POINT: XXXX F o SET POINT: 30 -60 %RH 24 VAC 48" AFF 48" AFF CONDENSATE OVERFLOW SWITCH 12 SENSORS LOCATED IN DATA ROOM SWITCH PROVIDED BY 4 OTHERS DATA ROOM POINTS ONE CONDESATE SWITCH PER TELECOM /DATA ROOMS CRAC UNIT A TEMPERATURE AND HUMIDITY SENSOR WILL MONITOR ROOM TEMP AND HUMIDITY. IF THE HUMIDITY RISES ABOVE A SETPOINT (60 %), OR DROPS BELOW A SETPOINT (30 %) (HI /LOW), AN ALARM WILL BE GENERATED. THE CONDENSATE OVERFLOW SWITCH WILL BE MONITORED FOR EACH LIEBERT. THE POINT WILL ALARM IF THE OVERFLOW SWITCH CHANGES STATE SIGNIFYING an overflow issue. CONTROL DIAGRAM - CRAC UNIT TO UNIT SAFETY CIRCUIT TO CLOSEST PANEL DROVRF DETAIL MC 2 FRONT BACK 5 TRIATEK MODEL FMS1630 QNormal a Alarm QSilen e DPM -1 EXTERNAL, ALARM DIFFERENTIAL PRESSURE MONITOR LOCATION: ISOLATION ROOMS ISOLATION ROOM MONITORING The Differential Pressure Monitor (DPM) monitors the differential pressure of a critical environment relative to an anteroom and the differential pressure of the anteroom to an adjacent space and compares the readings to the pressure set points. LAN TRUNK FOR ao 24 VAC TRUNK Two Remote Pressure Transmitters (RPTs) measure the pressure differential between the room and the anteroom and between the anteroom and its adjacent space and transmit those values to the DPM. The DPM displays the critical environment space's pressurization mode (Neutral, Positive or Negative), measured differential pressure and all alarms. It also displays the differential pressure of the anteroom. Each alarm (pressure too low or high) is annunciated by a hom. A built in alarm delay (adjustable) protects from nuisance alarms (i.e. doors opening, air flow changes, movement near sensor, etc.) EF Sequence of operations: (Typical of 2) C WALL AIRFLOW / TUBE OUTSIDE INSIDE COVER COVER PLATE PLATE FLOOR BACK OF PLATE 547 003 RPT- 1 REMOTE PRESSURE TRANSMITTER 6-18 IN —►I 0 0 0 6 -18 IN DOOR WALL FLOOR REMOTE PRESSURE TRANSMITTER ISOLATION ROOM SEQUENCE OF OPERATION 24 VAC TRUNK 1. PROVIDE TRIATEK 1630 PRESSURE MONITOR ON ISOLATION ROOMS FLOORS 4 -7. 2. ROOM PRESSURE MONITOR SHALL BE CONTROLED BY THE BMS. MINIMAL OVERRIDE SHALL BE ALLOWED BY THE FLOOR NURSE. 3. IN THE EVENT THE ROOM PRESSURE IS NOT SUSTAINED, AN ALARM ADVISOTY SHALL OCCUR AND STATE: "ROOM PRESSURE ISOLATION #XXXX IS OUT OF RANGE, CALL FLOOR NURSE." 4. PROVIDE STATUS ON FLOOR PLAN GRAPHICAL DISPLAY. 5. SET ALARM DELAY FOR 45 SECONDS, MINIMUM SET POINT 0.01" WG NEGATIVE PRESSURE. 6. ALARM SHALL BE CONSTANT ON FLOOR AND BMS IF DOOR IS LEFT OPEN. NOTE: PROVIDE TRIATEK FMS 1630 PRESSURE DIFFERENTIAL MONITOR. CONTROL DIAGRAM - DIFFERENTIAL PRESSURE MONITOR Run Conditions - Interlocked: The EF shall be interlocked with associated AHU to run when the AHU is energized and shutdown when the AHU shuts down. Fan Status: The controller shall monitor the fan status. Alarms shall be provided as follows: Fan Failure: Commanded on, but the status is off. 4 Fan in Hand: Commanded off, but the status is on. Fire /Smoke Damper: All fire /smoke dmapers in the associated exhaust system shall be interlocked with the exhaust fan. Failure of the fan to start or disconnecting of power to the exhaust fan shall close associated fire /smoke dampers. Fan shall not start until end switch on damper is closed. 5 E GENERAL EXHAUST FANS ALL INTERLOCKING SHALL BE THRU HARD WIRING. EA 211:611114 EF -1,2 are exisitng and shall be controlled as primary/standby. Revise control sequence shall operate in this condition. Fans shall be alternated on a weekly basis. VFD's shall be installed to balance fan throughout construction. CONTROL DIAGRAM - GENERAL EXHAUST o. 5360 , ATE F 'ir� QNA 1 3 -A R R AY - - a r c h i t o c t s . , -- --- - -- - -- -- --- -- - - - - - -" --------------------------------------------------- ARRAY- ARCHITECTS.COM 6800 Broken Sound Pkwy NW, Ste 125 Boca Raton, FL. 33487 o: 561 - 995 -1700 f: 561- 995 -1701 ------------------------------------------------------------------------------ SEAL: firm license # AA26000880 Mark D. Taudien AR0011821 CONSULTANTS: � Smith Beckman Reid, Inc. 600 West Hillsboro Blvd., Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 wWW.ssr- inc.com Frank Rivera PE - 54525 Jorge Rivera PE - 45360 SSR's JOB #1132077.0 OWNER: BAPTIST HEALTH SOUTH FLORIDA HOSPITAL: SOUTH MIAMI HOSPITAL PROJECT: PAVILION RENOVATIONS FLOOR, 4 -7 6200 Southwest 73rd Street South Miami, FL 33143 6 Bulletin B1 -03 02 -07 -14 5 1 1 08 -16 -12 4 0410143 04119101 Doll 041 A 1K Q WE Vey IN IN • 1 i� 07 -15 -12 3 F o 0 0 F 1 ................ �K ]I5f�7L7t1130]iCifiril�iLilNiL: il iii iii —� ■■■■■■■■■■■■ =�� %= =�i - 04 -10 -12 n 00 HTE -1 50 %RH AFF CONTROL DIAGRAM - CRAC UNIT EA INSTALLATION NOTES: O TEC-1 TO BE MOUNTED IN MANUFACTURER SUPPLIED CONTROLLER ENCLOSURE O LOCATE AS SHOWN ON FLOOR PLANS /CONTRACT DOCUMENTS O3 CRAC UNIT SHALL BE TIED INTO EXISTING BMS SYSTEM FOR MONITORING FOR STOP,START, STATUS. ALARM SHALL OCCUR BY 8, AT EXISTING BMS 1� SYSTEM IN ROOM EXCEEDS 78F, 60 %RH. TO CLOSEST PANEL TTE -1 HT E -1 SET POINT: XXXX F o SET POINT: 30 -60 %RH 24 VAC 48" AFF 48" AFF CONDENSATE OVERFLOW SWITCH 12 SENSORS LOCATED IN DATA ROOM SWITCH PROVIDED BY 4 OTHERS DATA ROOM POINTS ONE CONDESATE SWITCH PER TELECOM /DATA ROOMS CRAC UNIT A TEMPERATURE AND HUMIDITY SENSOR WILL MONITOR ROOM TEMP AND HUMIDITY. IF THE HUMIDITY RISES ABOVE A SETPOINT (60 %), OR DROPS BELOW A SETPOINT (30 %) (HI /LOW), AN ALARM WILL BE GENERATED. THE CONDENSATE OVERFLOW SWITCH WILL BE MONITORED FOR EACH LIEBERT. THE POINT WILL ALARM IF THE OVERFLOW SWITCH CHANGES STATE SIGNIFYING an overflow issue. CONTROL DIAGRAM - CRAC UNIT TO UNIT SAFETY CIRCUIT TO CLOSEST PANEL DROVRF DETAIL MC 2 FRONT BACK 5 TRIATEK MODEL FMS1630 QNormal a Alarm QSilen e DPM -1 EXTERNAL, ALARM DIFFERENTIAL PRESSURE MONITOR LOCATION: ISOLATION ROOMS ISOLATION ROOM MONITORING The Differential Pressure Monitor (DPM) monitors the differential pressure of a critical environment relative to an anteroom and the differential pressure of the anteroom to an adjacent space and compares the readings to the pressure set points. LAN TRUNK FOR ao 24 VAC TRUNK Two Remote Pressure Transmitters (RPTs) measure the pressure differential between the room and the anteroom and between the anteroom and its adjacent space and transmit those values to the DPM. The DPM displays the critical environment space's pressurization mode (Neutral, Positive or Negative), measured differential pressure and all alarms. It also displays the differential pressure of the anteroom. Each alarm (pressure too low or high) is annunciated by a hom. A built in alarm delay (adjustable) protects from nuisance alarms (i.e. doors opening, air flow changes, movement near sensor, etc.) EF Sequence of operations: (Typical of 2) C WALL AIRFLOW / TUBE OUTSIDE INSIDE COVER COVER PLATE PLATE FLOOR BACK OF PLATE 547 003 RPT- 1 REMOTE PRESSURE TRANSMITTER 6-18 IN —►I 0 0 0 6 -18 IN DOOR WALL FLOOR REMOTE PRESSURE TRANSMITTER ISOLATION ROOM SEQUENCE OF OPERATION 24 VAC TRUNK 1. PROVIDE TRIATEK 1630 PRESSURE MONITOR ON ISOLATION ROOMS FLOORS 4 -7. 2. ROOM PRESSURE MONITOR SHALL BE CONTROLED BY THE BMS. MINIMAL OVERRIDE SHALL BE ALLOWED BY THE FLOOR NURSE. 3. IN THE EVENT THE ROOM PRESSURE IS NOT SUSTAINED, AN ALARM ADVISOTY SHALL OCCUR AND STATE: "ROOM PRESSURE ISOLATION #XXXX IS OUT OF RANGE, CALL FLOOR NURSE." 4. PROVIDE STATUS ON FLOOR PLAN GRAPHICAL DISPLAY. 5. SET ALARM DELAY FOR 45 SECONDS, MINIMUM SET POINT 0.01" WG NEGATIVE PRESSURE. 6. ALARM SHALL BE CONSTANT ON FLOOR AND BMS IF DOOR IS LEFT OPEN. NOTE: PROVIDE TRIATEK FMS 1630 PRESSURE DIFFERENTIAL MONITOR. CONTROL DIAGRAM - DIFFERENTIAL PRESSURE MONITOR Run Conditions - Interlocked: The EF shall be interlocked with associated AHU to run when the AHU is energized and shutdown when the AHU shuts down. Fan Status: The controller shall monitor the fan status. Alarms shall be provided as follows: Fan Failure: Commanded on, but the status is off. 4 Fan in Hand: Commanded off, but the status is on. Fire /Smoke Damper: All fire /smoke dmapers in the associated exhaust system shall be interlocked with the exhaust fan. Failure of the fan to start or disconnecting of power to the exhaust fan shall close associated fire /smoke dampers. Fan shall not start until end switch on damper is closed. 5 E GENERAL EXHAUST FANS ALL INTERLOCKING SHALL BE THRU HARD WIRING. EA 211:611114 EF -1,2 are exisitng and shall be controlled as primary/standby. Revise control sequence shall operate in this condition. Fans shall be alternated on a weekly basis. VFD's shall be installed to balance fan throughout construction. CONTROL DIAGRAM - GENERAL EXHAUST o. 5360 , ATE F 'ir� QNA 1 3 -A R R AY - - a r c h i t o c t s . , -- --- - -- - -- -- --- -- - - - - - -" --------------------------------------------------- ARRAY- ARCHITECTS.COM 6800 Broken Sound Pkwy NW, Ste 125 Boca Raton, FL. 33487 o: 561 - 995 -1700 f: 561- 995 -1701 ------------------------------------------------------------------------------ SEAL: firm license # AA26000880 Mark D. Taudien AR0011821 CONSULTANTS: � Smith Beckman Reid, Inc. 600 West Hillsboro Blvd., Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 wWW.ssr- inc.com Frank Rivera PE - 54525 Jorge Rivera PE - 45360 SSR's JOB #1132077.0 OWNER: BAPTIST HEALTH SOUTH FLORIDA HOSPITAL: SOUTH MIAMI HOSPITAL PROJECT: PAVILION RENOVATIONS FLOOR, 4 -7 6200 Southwest 73rd Street South Miami, FL 33143 6 Bulletin B1 -03 02 -07 -14 5 ADDENDUM #5 08 -16 -12 4 ADDENDUM #3 07 -15 -12 3 PRICING SET 04 -10 -12 2 50% CONSTRUCTION SET 03 -11 -1? 1 AHCA STAGE II 10 -17 -12 NO. DESCRIPTION DATE REVISIONS /ISSUES ------------------------------------------------------------------------------ SHEET TITLE: MECHANICAL CONTROLS DRAWN: Author CHECKEDChecker CON /REF NCAHCA 23/100154 -191 -1 PROJECT No3593 DATE:05 -03 -13 SCALE: As indicated SHEET NO. M.602 This document is a copyright protected instrument of service, prope of Array Architects and licensed for use in the title project only. Reproduction or use of this document without written permission of Array Architects is illegal and will be prosecuted under the law. ©COPYRIGHT - 2013 ARRAY - ARCHITECTS, INC.