13-781R-026L
C
y
FASTEN RUNNER TO
FLOOR /ROOF DECK ABOVE AS
REQUIRED BY SPECIFICATIONS
CARRY WALLBOARD TO 2"
ABOVE FINISHED CEILING.
METAL RUNNER INSTALLED
z BETWEEN STUDS
FINISHED CEILING
2 1/4"
5/8" MOLD /MOISTURE RESISTANT TYPE
X GYPSUM WALLBOARD
I
1 /- — 15/8" METAL STUDS @ 16" O.C. MAX.
UNFINISHED FLOOR SLAB
I
TYPE 1
I
TYPE 1A METIAL STUDS 1 EXCEPT 21/2"
SAME AS TYPE 1 EXCEPT IGH
TYPE 1 B IMPACT GWB W/ STUDS @ 12" O.C.
2
rno i uv Ruiv ism i v rwVt%1Kvur
DECK ABOVE AS REQUIRED BY
SPECIFICATIONS
GYPSUM WALLBOARD AT 2A ONLY
CARRY WALLBOARD TO 2"
ABOVE FINISHED CEILING
FINISHED CEILING
41/4" 7SOUND ATTENUATION
1� �� FIRE BLANKET
(SEE NOTE #3 FOR WHERE
SOUND ATTENUATION
BLANKET IS REQUIRED)
5/8" MOLD /MOISTURE RESISTANT TYPE
X GYPSUM WALLBOARD
21/2" METAL STUDS @ 16" O.C. MAX.
21/2" METAL TRACK
- � UNFINISHED FLOOR SLAB
TYPE 2
TYPE 2A
SAME AS TYPE 2 EXCEPT CARY GYPSUM
WALLBOARD TO FLOOR/ OOFDECK ABOVE
TYPE 2 B
SAME AS
STUDS @ 16'PO.CEXCEPT 6" METAL .
CONT 22 GA 3" DEEP
SPRAY APPLIED FIRESTOP
FIRE STOPPING
-< P .-
MATERIAL EACH SIDE -MIN
FASTEN RUNNERTO FLOOR /ROOF
_
- ° •6" °a a . -
112" OVERLAP AT GYP BD
SEALANT
..' a '
• °
AND SLAB
DECK ABOVE AS REQUIRED BY
1
- . .
FASTEN RUNNER TO
DO NOT ATTACH GYP BD
DESCRIPTION
SPECIFICATIONS
REVISIONS /ISSUES
CARRY WALLBOARD TO
FLOOR /ROOF DECK ABOVE AS
OR STUDS TO DEFLECTION
FIRE STOPPING SEALANT
a
�-
REQUIRED BY SPECIFICATIONS
TRACK IN THIS AREA
SYSTEM ABOVE AND SEAL TIGHT
_
CARRY WALLBOARD TO
FILL GAP BETWEEN
FILL GAP BETWEEN SLAB
CARRY WALLBOARD TO
I 1
UNDERSIDE OF STRUCTURAL
WALLTYPE "166" ONLY
UNDERSIDE OF STRUCTURAL
:• . I
WALL WITH MINERAL
SYSTEM ABOVE AND SEAL
- 1
SYSTEM ABOVE AND SEAL TIGHT
22 GA MTL STRAP - ATTACH
TIGHT
SOUND ATTENUATION
INSULATION
GYP BD TO STRAP AT 8" OC
(SEE NOTE #3 FOR WHERE
FINISHED CEILING
MAX
FINISHED CEILING
IS REQUIRED)
REFER TO UL LISTING FOR
SOUND ATTENUATION
-
SOUND ATTENUATION
6 1/8' ,
FIRE BLANKET
(SEE NOTE #3 FOR WHERE
4 5/8"
FIRE BLANKET
(SEE NOTE #3 FOR WHERE
GYPSUM WALLBOARD
SOUND ATTENUATION
TO STRAP AT 8" OC MAX
ATTENUATION
REFER TO UL LISTING FOR
CONCRETE FLOOR OR ROOF SLAB
BLANKET IS REQUIRED)
FIRE RATED SMOKE BARRIER UL -HW -D-
BLANKET IS
4" C -H SHAFTWALL STUDS
COMPLETE ASSEMBLY
5/8" TYPE X GYPSUM WALLBOARD
REQUIREMENTS
@ 24" O.C. MAXIMUM
DOUBLE LAYER OF 5/8"
CONCRETE FLOOR OR ROOF SLAB
TWO HOUR FIRE RATED AND TWO
HOUR FIRE RATED SMOKE BARRIER UL-
J- RUNNER
HW -D -0108
TYPE'X' GYPSUM
UNFINISHED FLOOR SLAB
TYPE
17
2 FIRE RATED
1" GYPSUM SHAFTWALL LINER
<
3 5/8" METAL STUDS
@ 16" O.C.
;
4" C -H SHAFTWALL STUDS
3 5/8" METAL RUNNER
@ 24" O.C. MAXIMUM
FIRE STOPPING SEALANT
?r,
J- RUNNER
UNFINISHED FLOOR SLAB
UNFINISHED FLOOR SLAB
TYPE
14
2 HOUR FIRE
TYPE
16
1 HOUR FIRE RATED
RATED WALL UL DES U411 /U419
SHAFT WALL UL. DES. U417
TYPE
14A
2 HOUR RATED STC 56
TYPE
16A
EXCEPT
SMOKE BARRIER UL DES U411/U419
6T CH STUD
UL. DES. U417
STC 56
TYPE
16 B
SAME AS TYPE 16
EXCEPT 2112' CH STUD UL. DES. U417
CONT 22 GA 3" DEEP
SPRAY APPLIED FIRESTOP
LEG DEFLECTION
-< P .-
MATERIAL EACH SIDE -MIN
TRACK ATTACH TO
_
- ° •6" °a a . -
112" OVERLAP AT GYP BD
SLAB AT 12" OC MAX
..' a '
• °
AND SLAB
10 -17 -12
,°
- . .
FIRESTOPPING SEALANT
DO NOT ATTACH GYP BD
DESCRIPTION
DATE
REVISIONS /ISSUES
CARRY WALLBOARD TO
OR STUDS TO DEFLECTION
DO NOT ATTACH GYP BD OR
a
�-
TRACK IN THIS AREA
SYSTEM ABOVE AND SEAL TIGHT
_
r-
FILL GAP BETWEEN
FILL GAP BETWEEN SLAB
I 1
SLAB AND TOP OF
WALLTYPE "166" ONLY
AND TOP OF WALL WITH
CONT 2" WIDE X
WALL WITH MINERAL
FINISHED CEILING
- 1
MINERAL WOOL
22 GA MTL STRAP - ATTACH
SOUND ATTENUATION
INSULATION
GYP BD TO STRAP AT 8" OC
(SEE NOTE #3 FOR WHERE
MAX
IS REQUIRED)
REFER TO UL LISTING FOR
CONT 2" WIDE X
-
2- LAYERS 5/8" TYPE X
NOTE:
GYPSUM WALLBOARD
REQUIREMENTS
TO STRAP AT 8" OC MAX
REFER TO UL LISTING FOR
CONCRETE FLOOR OR ROOF SLAB
ONE HOUR FIRE RATED AND ONE HOUR
FIRE RATED SMOKE BARRIER UL -HW -D-
0108
4" C -H SHAFTWALL STUDS
COMPLETE ASSEMBLY
REQUIREMENTS
@ 24" O.C. MAXIMUM
CONCRETE FLOOR OR ROOF SLAB
TWO HOUR FIRE RATED AND TWO
HOUR FIRE RATED SMOKE BARRIER UL-
J- RUNNER
HW -D -0108
RATED PARTITION INTERSECTION
11/2" =1' -0"
HIGHER PRIORITY
LOWER PRIORITY
F
FASTEN RUNNER TO
FLOOR /ROOF DECK ABOVE AS
REQUIRED BY SPECIFIATIONS
CARRY WALLBOARD TO
UNDERSIDE OF
STRUCTURAL SYSTEM
ABOVE, AND SEAL TIGHT
FINISHED CEILING
4 7/8" SOUND ATTENUATION
� 1� FIRE BLANKET
(SEE NOTE #3 FOR WHERE SOUND
ATTENUATION BLANKET IS
REQUIRED)
I
MOLD /MOISTURE RESISTANT TYPE
X GYPSUM WALLBOARD
2112 METAL STUDS @ 16 O.C. MAX.
21/2" METAL TRACK
SLABNISHED FLOOR
TYPE 5
TYPE 6
FASTEN RUNNER TO
FLOOR /ROOF DECK ABOVE AS
REQUIRED BY SPECIFICATIONS
CARRY WALLBOARD TO
UNDERSIDE OF STRUCTURAL
SYSTEM ABOVE AND SEAL TIGHT
FINISHED CEILING
SOUND ATTENUATION
FIRE BLANKET
(SEE NOTE #3 FOR WHERE SOUND
ATTENUATION BLANKET IS
REQUIRED)
MOLD /MOISTURE RESISTANT TYPE
X GYPSUM WALLBOARD
—6" METAL STUDS @ 16" O.C. MAX.
—6" METAL TRACK
— UNFINISHED
FI OOR RI AR
STC 49 STC 49
CONT. FIRE RETARDANT WOOD
NAILER SECURE TO DECK W/
APPROPRIATE FASTENERS @ 24" O.C.
6 MIL. FIRE RETARDANT
POLYETHYLENE, SEAL ALL
JOINTS, PENETRATIONS &
PERIMETER W/ DUCT TAPE
CLOSE ALL OPEN DUCTS
W/ 6 MIL. POLY. & SEAL W/
DUCT TAPE.
CONT. FIRE RETARDANT WOOD
NAILER.
FINISHED CEILING
COMPRESSIBLE INSULATION
3 5/8" METAL STUDS @ 16" O.C.
PLASTER TAPE ALL JOINTS. SEAL
AROUND ALL PIPE /DUCT PENETRATIONS
4 7/8" IN PARTITION AND POLY BARRIER W/
I`- DUCT TAPE. SECURE TAPE W/ RAM -RACI
►� HIGH TACK SPRAY OR EQUAL.
5/8" TYPE 'WGYPSUM WALLBOARD
11 SOUND ATTENUATION BATTS
' 3 5/8" METAL TRACK
COMPRESSIBLE INSULATION
SEAL PERIMETER OF WALL W /DUCT
TAPE, TYP. SECURE ALL W/ RAM -TACK
HIGH TACK SPRAY OR EQUAL.
TYPE TF TEMPORARY PARTITION
SAME AS TYPE 17 EXCEPT 1 112 " =1' 0"
TYPE 17A 6" CH STUD UL. DES. U417
TYPE 17B
SAME AS 17
EXCEPT 21 /2 "ECHSTUD
UL. DES. U417
CONT 22 GA 3" DEEP LEG
SPRAY APPLIED FIRESTOP
DEFLECTION TRACK
a
DECK ABOVE AS REQUIRED BY
MATERIAL EACH SIDE -
ATTACH TO DECK AT 12"
50% CONSTRUCTION SET
°< ;a , ' ;
SPECIFICATIONS
OC MAX
10 -17 -12
° ° :
BD AND SLAB
FIRESTOPPING SEALANT
NO.
DESCRIPTION
DATE
REVISIONS /ISSUES
CARRY WALLBOARD TO
DO NOT ATTACH GYP BD OR
UNDERSIDE OF STRUCTURAL
SYSTEM ABOVE AND SEAL TIGHT
_
r-
FILL GAP BETWEEN
5/8" WALLBOARD @
I 1
SLAB AND TOP OF
WALLTYPE "166" ONLY
WALL WITH MINERAL
FINISHED CEILING
- 1
WOOL INSULATION
GYP BD TO STRAP AT 8" OC MAX
SOUND ATTENUATION
FIRE BLANKET
(SEE NOTE #3 FOR WHERE
SOUND ATTENUATION BLANKET
IS REQUIRED)
REFER TO UL LISTING FOR
CONT 2" WIDE X
-
2- LAYERS 5/8" TYPE X
22 GA MTL STRAP - ATTACH GYP BD
GYPSUM WALLBOARD
REQUIREMENTS
TO STRAP AT 8" OC MAX
1" GYPSUM SHAFTWALL LINER
CONCRETE FLOOR OR ROOF SLAB
ONE HOUR FIRE RATED AND ONE HOUR
FIRE RATED SMOKE BARRIER UL -HW -D-
0108
4" C -H SHAFTWALL STUDS
@ 24" O.C. MAXIMUM
J- RUNNER
UNFINISHED FLOOR SLAB
TYPE
17
2 FIRE RATED
SHAG T WALL
UL. DES. U417
CONT. FIRE RETARDANT WOOD
NAILER SECURE TO DECK W/
APPROPRIATE FASTENERS @ 24" O.C.
6 MIL. FIRE RETARDANT
POLYETHYLENE, SEAL ALL
JOINTS, PENETRATIONS &
PERIMETER W/ DUCT TAPE
CLOSE ALL OPEN DUCTS
W/ 6 MIL. POLY. & SEAL W/
DUCT TAPE.
CONT. FIRE RETARDANT WOOD
NAILER.
FINISHED CEILING
COMPRESSIBLE INSULATION
3 5/8" METAL STUDS @ 16" O.C.
PLASTER TAPE ALL JOINTS. SEAL
AROUND ALL PIPE /DUCT PENETRATIONS
4 7/8" IN PARTITION AND POLY BARRIER W/
I`- DUCT TAPE. SECURE TAPE W/ RAM -RACI
►� HIGH TACK SPRAY OR EQUAL.
5/8" TYPE 'WGYPSUM WALLBOARD
11 SOUND ATTENUATION BATTS
' 3 5/8" METAL TRACK
COMPRESSIBLE INSULATION
SEAL PERIMETER OF WALL W /DUCT
TAPE, TYP. SECURE ALL W/ RAM -TACK
HIGH TACK SPRAY OR EQUAL.
TYPE TF TEMPORARY PARTITION
SAME AS TYPE 17 EXCEPT 1 112 " =1' 0"
TYPE 17A 6" CH STUD UL. DES. U417
TYPE 17B
SAME AS 17
EXCEPT 21 /2 "ECHSTUD
UL. DES. U417
CONT 22 GA 3" DEEP LEG
SPRAY APPLIED FIRESTOP
DEFLECTION TRACK
a
_
a°
MATERIAL EACH SIDE -
ATTACH TO DECK AT 12"
50% CONSTRUCTION SET
°< ;a , ' ;
MIN 112" OVERLAP AT GYP
OC MAX
10 -17 -12
° ° :
BD AND SLAB
NO.
DESCRIPTION
DATE
REVISIONS /ISSUES
DO NOT ATTACH GYP BD OR
STUDS TO DEFLECTION
_
r-
FILL GAP BETWEEN
TRACK IN THIS AREA
I 1
SLAB AND TOP OF
CONT 2" WIDE X
WALL WITH MINERAL
22 GA MTL STRAP - ATTACH
- 1
WOOL INSULATION
GYP BD TO STRAP AT 8" OC MAX
I
NOTE:
I
REFER TO UL LISTING FOR
CONT 2" WIDE X
COMPLETE ASSEMBLY
22 GA MTL STRAP - ATTACH GYP BD
REQUIREMENTS
TO STRAP AT 8" OC MAX
CONCRETE FLOOR OR ROOF SLAB
ONE HOUR FIRE RATED AND ONE HOUR
FIRE RATED SMOKE BARRIER UL -HW -D-
0108
LOWER PRIORITY
HIGHER PRIORITY
a' .. g CONT 22 GA 3" DEEP
°' 4 = = LEG DEFLECTION
SEALANT :- TRACK ATTACH TO
DO NOT ATTACH GYP — DECK AT 12" OC MAX
BD OR STUDS TO
DEFLECTION TRACK IN CONT 7" WIDE X
THIS AREA 1 22 GA MTL STRAP FOR
I TOP ATTACHMENT OF
GYP BD
CONCRETE FLOOR OR ROOF
NON -RATED OR SMOKE RESISTANT
HIGHER PRIORITY
LOWER PRIORITY
LOWER PRIORITY
HIGHER PRIORITY
5
SEALANT
1
FASTEN RUNNER TO
FLOOR /ROOF DECK ABOVE AS
REQUIRED BY SPECIFICATIONS
CARRY WALLBOARD TO
UNDERSIDE OF STRUCTURAL
SYSTEM ABOVE, AND SEAL
TIGHT
C
FINISHED CEILING
SOUND ATTENUATION
FIRE BLANKET
(SEE NOTE #3 FOR WHERE
SOUND ATTENUATION
BLANKET IS REQUIRED)
X5 /8" MOLD /MOISTURE RESISTANT TYPE
X GYPSUM WALLBOARD
X21/2" METAL STUDS @ 16" O.C. MAX.
X21/2" METAL TRACK
UNFINISHED FLOOR SLAB
SMOKE PARTITION
L 4 7/8" U
TYPE 8
STC 49
TYPE 8A SAME AS TYPE 9 EXCEPT 6" STUDS
AS NECESSARY TO \
ACCOMMODATE EXISTING CONDITIONS
STC 49
is
nn� � � yr nivv o�r�uvv
1 FASTEN RUNNER TO
FLOOR /ROOF DECK ABOVE AS
REQUIRED BY SPECIFICATIONS
1 CARRY WALLBOARD TO
UNDERSIDE OF STRUCTURAL
SYSTEM ABOVE, AND SEAL TIGHT
FINISHED CEILING
-U 4 7/8" T
SOUND ATTENUATION
FIRE BLANKET
(SEE NOTE #3 FOR WHERE
SOUND ATTENUATION
BLANKET IS REQUIRED)
5/8" MOLD /MOISTURE RESISTANT
X GYPSUM WALLBOARD
2112" METAL STUDS @ 16" O.C. W
I 21/2" METAL TRACK
FIRE STOPPING SEALANT
UNFINISHED FLOOR SLAB
TYPE 10 RATED WALL UL DES U465/U419
TYPE 10A 1 HOUR RATED STC 49
SMOKE BARRIER UL DES U4651U419
TYPE 10B
FIRE STUDS
WALL UL DES U465/U419
FASTEN RUNNER TO
FLOOR/ROOF DECK ABOVE AS
REQUIRED BY SPECIFICATIONS
CARRY WALLBOARD TO
UNDERSIDE OF STRUCTURAL
SYSTEM ABOVE
FINISHED CEILING
SOUND ATTENUATION
BLANKET
_518" MOLD /MOISTURE RESISTANT TYPE
X GYPSUM WALLBOARD
- 21/2" METAL STUDS @ 16" O.C. MAX
-2112" METAL TRACK
UNFINISHED FLOOR SLAB
TYPE 7 PLUMBING CHASE BETWEEN PATIENT TOILETS
�- DOOR LOCATION
JAMB STUDS AS
REQUIRED
HOLLOW METAL
FRAME
TAPE AND JOINT
COMPOUND TYP
LOWER PRIORITY
PARTITION
HIGHER PRIORITY
PARTITION
INTERSECTION AT CROSS CORRIDOR DOOR TWO
n HOUR RATED PARTITION
DJ " 1' -0"
LOWER PRIORITY
HIGHER PRIORITY
HIGHER PRIORITY
LOWER PRIORITY
7
PARTITION TYPES GENERAL NOTES
1. ALL FIRE RATED AND SMOKE BARRIER PARTITIONS MUST BE INSTALLED
PER THEIR UL DESIGN NUMBERS.
2. INSTALL FIRE SEALANT AROUND THE ENTIRE PERIMETER TO PREVENT THE
PASSAGE OF SMOKE IN ALL RATED AND SMOKE PARTITIONS.
3. INSTALL SOUND ATTENUATION BLANKET IN ALL PARTITIONS THAT FORM ANY
PART OF THE ENCLOSURE OF THE FOLLOWING ROOMS: PATIENT ROOMS,
TOILET ROOMS, EXAM ROOMS, TREATMENT ROOMS, OFFICES AND MECHANICAL
ROOMS. THESE PARTITIONS SHALL HAVE 3 -1/2" FIBERGLASS BATT SOUND
ATTENUATION BLANKETS AND MEET MINIMUM SOUND TRANSMISSION RATING OF
STC 45. USE ACOUSTICAL SEALANT AROUND THE ENTIRE PERIMETER ON NOW
RATED PARTITIONS.
4. REPLACE 5/8" GYPSUM WALLBOARD WITH 518" DENS - SHIELD IN ALL AREAS
TO RECEIVE CERAMIC TILE. SKIM COAT ENTIRE SURFACE NOT COVER BY TILE.
5. REPLACE 5/8" GYPSUM WALLBOARD WITH 5/8" MOISTURE AND MOLD -
RESISTANT GYPSUM WALL BOARD ON ALL PLUMBING WALL OTHER THAN THOSE
TYPE COVERED IN NOTE # 4 ABOVE.
X. 6. FOR HEIGHTS UP TO AND INCLUDING 14' -0" TYPICAL INTERIOR METAL
STUDS ARE 20 GA. AT 16" O.C.; FOR HEIGHTS ABOVE 14' -0 ", USE 18 GA AT 16"
O.C.; USE DOUBLE 20 GA. STUDS AT DOORS AND BORROWED LIGHT FRAMES;
USE DOUBLE 18 GA. STUDS AT ICU SLIDING DOORS AND LEAD LINED DOORS AND
BORROWED LIGHT FRAMES.
7. NOTIFY ARCHITECT OF WORK TO BE PERFORMED ON EXISTING PARTITIONS
AND PROVIDE PRICING ACCORDING TO UNIT PRICES OUTLINED IN
SPECIFICATION SECTION 012200.
8. INSTALL SUPPLEMENTARY FRAMING, BLOCKING, AND BRACING IN
PARTITIONS TO SUPPORT FIXTURES, EQUIPMENT SERVICES, HEAVY TRIM, GRAB
BARS, TOILET ACCESSORIES, DOOR HARDWARE, FURNISHINGS, OR SIMILAR
CONSTRUCTION. COMPLY WITH DETAILS INDICATED AND WITH
RECOMMENDATIONS OF "GYPSUM CONSTRUCTION HANDBOOK".
9. WHEN INFILLING OR ABUTTING EXISTING PARTITIONS CONTRACTOR TO ADD
AN ADDITIONAL LAYER OF GYPSUM WALLBOARD TO PARTITION TYPE AND /OR
SKIM COAT WALL AS REQUIRED TO PROVIDE A FLUSH SURFACE. THICKNESS OF
GYPSUM WALLBOARD AND / OR STUD SIZE TO BE DETERMINED IN FIELD TO
PROVIDE A FLUSH SURFACE.
10. EXTEND ALL WALLS TO UNDERSIDE OF STRUCTURE ABOVE. PROVIDE SLIP
TRACK AT TOP OR ANOTHER APPROVED METHOD TO ALLOW FOR A 1"
DEFLECTION OF THE STRUCTURE.
tCAVJ ® S0Qp s
oRID! 10 g1CX 0NCEI
ItY 1G�� BOARD Ae
LOWER PRIORITY
HIGHER PRIORITY
A. . �•
_a, r c- -h i t _e, c t s
ARRAY- ARCHITECTS.COM
6800 Broken Sound Pkwy NW, Ste 125
Boca Raton, FL. 33487
o: 561 - 995 -1700
f: 561 - 995 -1701
SEAL: firm license # AA26000880
I/
+'
-� .).
It
it CIS
�. ` �\
,111 j•• ' •+ r � {t,
F M1' c
Mark D. Taudien AR0011821
CONSULTANTS:
STRUCTURAL ENGINEER
O'Donnell, Naccarato,
Mignogna & Jackson
321 15th St., Suite 200
West Palm Beach, Florida
33401, USA
Phone: 561.835.9994
Fax: 561.835.8255
MEP ENGINEER
Smith, Seckman & Reid, Inc.
600 West Hillsboro Blvd, Suite 300
Deerfield Beach, FL 33441
Phone: 954.421.1260
Fax: 954.421.1466
OWNER:
BAPTIST HEALTH SOUTH
FLORIDA
HOSPITAL:
SOUTH MIAMI HOSPITAL
PROJECT:
PAVILION RENOVATIONS
FLOORS 4 -7
6200 Southwest 73rd Street
South Miami, FL 33143
4
Bulletin #B1 -02
01 -15 -14
3
PRICING SET
04 -10 -13
2
50% CONSTRUCTION SET
03 -11 -13
1
AHCA STAGE II
10 -17 -12
NO.
DESCRIPTION
DATE
REVISIONS /ISSUES
SHEET TITLE:
PARTITION TYPES
--------- - - - - -- ------- - - - - -- ------------------------------------------ - - - - -- - - - --
DRAWN: EAS CHECKED: FB
CON /REF No. AHCA 23/100154 -191
PROJECT No. 3593
DATE: 05/03/13 SCALE: As indicated
SHEET NO.
A621