13-62R-017^
�
SEQUENCE OF OPERATION
1. FIRE ALARM
DURING FIRE ALARM ACTIVATION, THE FOLLOWING SHALL OCCUR:
- SHUTDOWN THE AHU-7A SUPPLY FAN
- CLOSE AHU-7A OUTSIDE AIR DAMPER,
- CLOSE THE RETURN SMOKE DAMPER.
KITCHEN HOOD EXHAUST FAN EF-1 REMAINS IN OPERATION.
2. FIRE SUPPRESSION SYSTEM
UPON ACTIVATION OF THE KITCHEN HOOD FIRE SUPPRESSION SYSTEM (FIRE ALARM OR PULL STATION) THE
FOLLOWING IS TO OCCUR.
- SOLENOID GAS MAIN SHUT-OFF VALVE CLOSES TO TURN OFF ALL GAS APPLIANCES.
- SEND SIGNAL TO BUILDING FIRE ALARM SYSTEM.
- THE HOOD EXHAUST FAN EF-1 SHALL OPERATE WHENEVER THE EXTINGUISHING SYSTEM IS ACTIVATED.
SMOKE DAMPER SEQUENCE OF OPERATION.
THE SMOKE DAMPER SHALL CLOSE UPON ACTUATION OF A LISTED SMOKE DETECTOR OR DETECTORS
INTALLED WITHIN A DUCT AS PER F.B.C.M./2010, SECTION 607.5.4.1-1. SMOKE DETECTOR SHALL BE
INSTALLED WITHIN 5FT OF THE DAMPER WITH NO AIR OUTLETS BETWEEN THE DETECTOR AND THE DAMPER.
AIR DISTRIBUTION SCHEDULE
AREA SERVED
CAFETERIA,
KITCHEN HOOD AND PIZZA OVEN HOOD
AIR FLOW - CFM
2060
3450
LOCATION
ROOF
ROOF
2
EXISTING EXHAUST FAN EF-6 AND EF-1 (AFTER DEMOLITION)
MODEL NO. AND OR
TDC-AA
TDC-AA
350 FIL
350 FIL
223
CATALOG NO.
ALL ALUM.
ALL ALUM.
ALL ALUM.
ALL ALUM.
2747
183
9
1647
FOOD PREPARATION
FRAME TYPE
6
SURFACE
102
PROJ. No. 22016 CA 924
LAY-IN
LOW J. AGUNRE & ASSOCIATES P.A.
LAY-IN
NOTE: BREATHING ZONE OUTDOOR AIRFLOWS, (CFM REQUIRED) WAS CALCULATED ACCORDING TO ASHRAE 62.1-2004 SECTION 6.2.2.1
FIXED LOUVERED
FIXED LOUVERED
LOUVERED
LOUVERED
DEVICE TYPE
VANES
VANES
350, 3/4" SPACING
350, 3/4" SPACING
FUNCTION
SUPPLY
SUPPLY
R/A, EXH OR TRANS.
R/A OR EXH
Architects Project Number
ROUND NECK
FOR PERMIT
Drawing Issue 11113/2012
18 x 18
REVISIONS
NO,
DESCRIPTION
NECK SIZE
LOUVERED FACE
SEE DRAWINGS
SEE DRAWINGS
SEE DRAWINGS
NECK SIZE
01.15.13
ON DRAWING
PATTERN
SEE DRAWINGS
SEE DRAWINGS
SEE DRAWINGS
SEE DRAWINGS
OPPOSED BLADE DAMPERS
YES
YES
YES
YES
1. ALTERNATE MANUFACTURERS OF EQUAL QUALITY MAY BE SUBMITTED FOR APPROVAL.
2. ALL AIR DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION AND FULLY GASKETED.
3. UNLESS OTHERWISE NOTED, FINISH OF ALL AIR DEVICES SHALL BE BAKED OFF-WHITE.
4 FOR SQUARE NECK OUTLETS CONNECTED TO A ROUND FLEXIBLE OR RIGID DUCT, .
5. MOUNTING BORDERS TO BE CONSISTENT WITH ACTUAL CEILING TYPE; COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLANS.
EXISTING EXHAUST FAN EF-6 AND EF-1 (BEFORE DEMOLITION)
AREA SERVED
CAFETERIA,
KITCHEN HOOD AND PIZZA OVEN HOOD
AIR FLOW - CFM
2060
3450
LOCATION
ROOF
ROOF
2
EXISTING EXHAUST FAN EF-6 AND EF-1 (AFTER DEMOLITION)
34
AREA SERVED
CAFETERIA
AIR FLOW - CFM
223
3170
LOCATION
ROOF
ROOF
EST, 1915
OUTSIDE AIR CALCULATIONS SCHEDULE
SOUTH MIAMI HOSPITAL
BASED ON ASHRAE STANDARD 62.1-2004
SPACE SYSTEM AREA (SQ.FT.)
TOTAL PERSONS
CFM/PERSON
CFM REQUIRED CFM PROVIDED
GRIDDLE ROOM
AHU-7A
194
2
17
34
SERVERY
1562
223
9
2007
DINING
EST, 1915
2747
183
9
1647
FOOD PREPARATION
573
6
17
102
PROJ. No. 22016 CA 924
LOW J. AGUNRE & ASSOCIATES P.A.
CONSULTING ENGINEERS
NOTE: BREATHING ZONE OUTDOOR AIRFLOWS, (CFM REQUIRED) WAS CALCULATED ACCORDING TO ASHRAE 62.1-2004 SECTION 6.2.2.1
-
SOUTH MIAMI HOSPITAL
SUNSET CAFE
CAFETERIA RENOVATION
6200 S.W. 73rd STREET
MIAMI, FIL 33143
General Contractor
PLANNING
ARCHITECTURE
L-M- A DALY NT ERIC) R,
EST, 1915
3390 Mary Street, Suite 216
Miami Florida 33133 USA
T: 305.461.9480 F: 305.461.3686
Associate Architect
PROJ. No. 22016 CA 924
LOW J. AGUNRE & ASSOCIATES P.A.
CONSULTING ENGINEERS
9150 SOUTH DADELAND BLVD. SUITE 900
MIAMI, FLORIDA 33156
TELEPHONE: (305) 670-0141
FAX: (305) 670-0144
CAFETERIA
Not to Scale
Architects Project Number
FOR PERMIT
Drawing Issue 11113/2012
REVISIONS
NO,
DESCRIPTION
DATE
AHU REPLACEMENT
01.10.13
AHCA COMMENTS
01.15.13
LEO A DALY COMPANY Copyright 2012
wt
1 EN 7864
Seal
SCHEDULES
HVAC
Sheet Title
M6mOO
I I
Sheet Number