13-62R-017^ � SEQUENCE OF OPERATION 1. FIRE ALARM DURING FIRE ALARM ACTIVATION, THE FOLLOWING SHALL OCCUR: - SHUTDOWN THE AHU-7A SUPPLY FAN - CLOSE AHU-7A OUTSIDE AIR DAMPER, - CLOSE THE RETURN SMOKE DAMPER. KITCHEN HOOD EXHAUST FAN EF-1 REMAINS IN OPERATION. 2. FIRE SUPPRESSION SYSTEM UPON ACTIVATION OF THE KITCHEN HOOD FIRE SUPPRESSION SYSTEM (FIRE ALARM OR PULL STATION) THE FOLLOWING IS TO OCCUR. - SOLENOID GAS MAIN SHUT-OFF VALVE CLOSES TO TURN OFF ALL GAS APPLIANCES. - SEND SIGNAL TO BUILDING FIRE ALARM SYSTEM. - THE HOOD EXHAUST FAN EF-1 SHALL OPERATE WHENEVER THE EXTINGUISHING SYSTEM IS ACTIVATED. SMOKE DAMPER SEQUENCE OF OPERATION. THE SMOKE DAMPER SHALL CLOSE UPON ACTUATION OF A LISTED SMOKE DETECTOR OR DETECTORS INTALLED WITHIN A DUCT AS PER F.B.C.M./2010, SECTION 607.5.4.1-1. SMOKE DETECTOR SHALL BE INSTALLED WITHIN 5FT OF THE DAMPER WITH NO AIR OUTLETS BETWEEN THE DETECTOR AND THE DAMPER. AIR DISTRIBUTION SCHEDULE AREA SERVED CAFETERIA, KITCHEN HOOD AND PIZZA OVEN HOOD AIR FLOW - CFM 2060 3450 LOCATION ROOF ROOF 2 EXISTING EXHAUST FAN EF-6 AND EF-1 (AFTER DEMOLITION) MODEL NO. AND OR TDC-AA TDC-AA 350 FIL 350 FIL 223 CATALOG NO. ALL ALUM. ALL ALUM. ALL ALUM. ALL ALUM. 2747 183 9 1647 FOOD PREPARATION FRAME TYPE 6 SURFACE 102 PROJ. No. 22016 CA 924 LAY-IN LOW J. AGUNRE & ASSOCIATES P.A. LAY-IN NOTE: BREATHING ZONE OUTDOOR AIRFLOWS, (CFM REQUIRED) WAS CALCULATED ACCORDING TO ASHRAE 62.1-2004 SECTION 6.2.2.1 FIXED LOUVERED FIXED LOUVERED LOUVERED LOUVERED DEVICE TYPE VANES VANES 350, 3/4" SPACING 350, 3/4" SPACING FUNCTION SUPPLY SUPPLY R/A, EXH OR TRANS. R/A OR EXH Architects Project Number ROUND NECK FOR PERMIT Drawing Issue 11113/2012 18 x 18 REVISIONS NO, DESCRIPTION NECK SIZE LOUVERED FACE SEE DRAWINGS SEE DRAWINGS SEE DRAWINGS NECK SIZE 01.15.13 ON DRAWING PATTERN SEE DRAWINGS SEE DRAWINGS SEE DRAWINGS SEE DRAWINGS OPPOSED BLADE DAMPERS YES YES YES YES 1. ALTERNATE MANUFACTURERS OF EQUAL QUALITY MAY BE SUBMITTED FOR APPROVAL. 2. ALL AIR DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION AND FULLY GASKETED. 3. UNLESS OTHERWISE NOTED, FINISH OF ALL AIR DEVICES SHALL BE BAKED OFF-WHITE. 4 FOR SQUARE NECK OUTLETS CONNECTED TO A ROUND FLEXIBLE OR RIGID DUCT, . 5. MOUNTING BORDERS TO BE CONSISTENT WITH ACTUAL CEILING TYPE; COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLANS. EXISTING EXHAUST FAN EF-6 AND EF-1 (BEFORE DEMOLITION) AREA SERVED CAFETERIA, KITCHEN HOOD AND PIZZA OVEN HOOD AIR FLOW - CFM 2060 3450 LOCATION ROOF ROOF 2 EXISTING EXHAUST FAN EF-6 AND EF-1 (AFTER DEMOLITION) 34 AREA SERVED CAFETERIA AIR FLOW - CFM 223 3170 LOCATION ROOF ROOF EST, 1915 OUTSIDE AIR CALCULATIONS SCHEDULE SOUTH MIAMI HOSPITAL BASED ON ASHRAE STANDARD 62.1-2004 SPACE SYSTEM AREA (SQ.FT.) TOTAL PERSONS CFM/PERSON CFM REQUIRED CFM PROVIDED GRIDDLE ROOM AHU-7A 194 2 17 34 SERVERY 1562 223 9 2007 DINING EST, 1915 2747 183 9 1647 FOOD PREPARATION 573 6 17 102 PROJ. No. 22016 CA 924 LOW J. AGUNRE & ASSOCIATES P.A. CONSULTING ENGINEERS NOTE: BREATHING ZONE OUTDOOR AIRFLOWS, (CFM REQUIRED) WAS CALCULATED ACCORDING TO ASHRAE 62.1-2004 SECTION 6.2.2.1 - SOUTH MIAMI HOSPITAL SUNSET CAFE CAFETERIA RENOVATION 6200 S.W. 73rd STREET MIAMI, FIL 33143 General Contractor PLANNING ARCHITECTURE L-M- A DALY NT ERIC) R, EST, 1915 3390 Mary Street, Suite 216 Miami Florida 33133 USA T: 305.461.9480 F: 305.461.3686 Associate Architect PROJ. No. 22016 CA 924 LOW J. AGUNRE & ASSOCIATES P.A. CONSULTING ENGINEERS 9150 SOUTH DADELAND BLVD. SUITE 900 MIAMI, FLORIDA 33156 TELEPHONE: (305) 670-0141 FAX: (305) 670-0144 CAFETERIA Not to Scale Architects Project Number FOR PERMIT Drawing Issue 11113/2012 REVISIONS NO, DESCRIPTION DATE AHU REPLACEMENT 01.10.13 AHCA COMMENTS 01.15.13 LEO A DALY COMPANY Copyright 2012 wt 1 EN 7864 Seal SCHEDULES HVAC Sheet Title M6mOO I I Sheet Number