- ENLARGED MECHANICAL ROOM - ELECTRICAL
DEMOLITION NOTES:
1� EXISTING AHU -7 AND AHU -10 DISCONNECTS AND ASSOCIATED FEEDERS TO BE
REMOVED. REMOVE CONDUIT AND WIRING BACK TO EXISTING PANEL SERVING UNITS
AND LEAVE TWO BREAKERS AS "SPARE" FOR FUTURE USE BY OTHERS.
2. EXISTING CONTROL PANELS TO BE REMOVED.
�3 EXISTING AHU -7 AND AHU -10 BELOW TO BE REMOVED. SEE MECHANICAL DRAWINGS.
�4J EXISTING AHU -2 AND AHU -5 TO REMAIN.
G5. EXISTING AHU -7 AND AHU -10 FIRE ALARM DUCT SMOKE DETECTORS TO BE REMOVED.
NEW WORK
SCALE: 1/4`-1'-0*
- ENLARGED MECHANICAL ROOM - ELECTRICAL
NEW WORK NOTES:
10 NEW AHU-7A FEEDER TO RUN ABOVE CEILING UP TO EXISTING PANEL "1 EQHZ"
LOCATED IN "ESSENTIAL LOADS" ELECTRICAL ROOM. ELECTRICAL CONTRACTOR TO
COORDINATE EXACT ROUTING AT FIELD BASED ON EXISTING CONDITIONS. SEE PANEL
SCHEDULE.
�2 NEW VFD FOR AHU -7A TO BE PROVIDED. SEE MECHANICAL DRAWINGS.
NEW AHU -7A TO REPLACE AHU -7 AND AHU -10.
(4. NEW DDC CONTROL PANEL TO REPLACE EXISTING CONTROL SYSTEM. PROVIDE A
NEW DUPLEX RECEPTACLE SERVED OUT OF EXISTING CONTROL SYSTEM PANEL TO
SERVE NEW PANEL. COORDINATE EXACT LOCATION /CONDITIONS AT FIELD.
�5 NEW DUCT DETECTORS TO BE PROVIDED IN COORDINATION WITH MECHANICAL
CONTRACTOR FOR NEW AHU -7A. NEW DEVICES SHALL BE FULLY COMPATIBLE WITH
EXISTING HOSPITAL FIRE ALARM SYSTEM.
OPROVIDE NEW AHU SHUT -DOWN RELAY.
(@2' 0 2' 4'
SCALE: 1/4 " =1' -0"
SOUTH MIAMI HOSPITAL
SUNSET CAFE
CAFETERIA RENOVATION
6200 S.W. 73rd STREET
MIAMI, FL 33143
o.Mr
General Contractor
ARCHITECTURE PLANNING
LEDA DALE INTERIO SBNG
0
EST. 1915
3390 Mary Street, Suite 216
Miami Florida 33133 USA
T: 305.461.9480 F: 305.461.3686
Architect
Associate Architect
PROJ. No. 22016 CA 924
LOUIS J. AGURRE & ASSOCIATES P.A.
CONSULTING ENGINEERS
9150 SOUTH DADELAND BLVD. SUITE 900
MIAMI, FLORIDA 33156
TELEPHONE: (305) 670 -0141
FAX: (305) 670 -0144
www.ljaapo.com
N
CAFETERIA
Not to Scale
061 -10064 -020
Architects Project Number
FOR PERMIT
11/13/2012
Drawing Issue
REVISIONS
NO.
DESCRIPTION
DATE
2
AHU REPLACEMENT
01.10.13
LEO A DALY COMPANY Copyright 2012
t �
ELEC'TEI l t t t
E9 ,
MARIO D. PAZOS "P.E': e`
LICENSE u 52078
Seal
ENLARGED
MECHANICAL ROOM
ELECTRICAL
Sheet Title
■ 2
Sheet Numb