13-62-033System No. C -AJ -1226 F Rating - 3 Hr T Rating - 0 Hr L Rating At Ambient - Less Than 1 CFM /Sq Ft L Rating At 400 F - 4 CFM /Sq Ft A L -� A - SECTION A -A 1. 1. Floor or Wall Assembly — Min 4 -1/2 in. thick reinforced lightweight or normal weight (100 -150 pcf) concrete. Wall may also be constructed of any UL Classified Concrete Blocks *. Max diam of opening is 32 in. 2. Metallic Sleeve — (Optional) Nom 32 in. diam (or smaller) Schedule 40 (or heavier) steel sleeve cast or grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3 in. above floor or beyond both surfaces of wall. 3. Sheet Metal Sleeve — (Optional) Max 6 in. diam, min 26 ga galy steel provided with a 26 ga galy steel square flange spot welded to the sleeve at approx mid - height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in. below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor. 4. Sheet Metal Sleeve — (Optional) - Max 12 in. diam, min 24 ga galy steel provided with a 24 ga galy steel square flange spot welded to the sleeve at approx mid - height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in. below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor. 5. Through - Penetrant — One metallic pipe, tube or conduit to be installed either concentrically or eccentrically within the firestop system. The annular space between penetrant and periphery of opening shall be rnin 0 in. (point contact) to max 1 -7/8 in. Penetrant may be installed with continuous point contact. Penetrant to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic penetrants may be used: A. Steel Pipe — Nom 30 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe — Nom 30 in. diam (or smaller) cast or ductile iron pipe. C. Copper Pipe — Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe. D. Copper Tubing — Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing. E. Conduit — Nom 6 in. diam (or smaller) steel conduit. F. Conduit — Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT). 6. Firestop System — The firestop system shall consist of the following: A. Packing Material — Min 4 in. thickness of min 4 pcf mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or sleeve or from both surfaces of wall or sleeve as required to accommodate the required thickness of fill material B. Fill, Void or Cavity Material* — Sealant — Min 1/4 in. thickness of fill material applied within the annulus, flush with top surface of floor or sleeve or with both surfaces of wall or sleeve. At the point or continuous contact locations between penetrant and concrete or sleeve, a min 1/4 in. diam bead of fill material shall be applied at the concrete or sleeve/ pipe penetrant interface on the top surface of floor and on both surfaces of wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS -One Sealant *Bearing the UL Classification Mark ASS Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. FIRESTOP SYSTEMS June 27, 2007 C L u S FINISH FLOOR OR FDS JDULET (THREADLESS FOR D THICK WALL ZUIT 'K WALL CONDUIT E: USE 2 HUBS ,,LL STUBS 3/4" SMALLER IPLING FLUSH FEEDING CONDUIT -- I � -LOOK LOOPING CONDUIT FEEDING 2ND OUTLET OR STUB ONLY FOR STRENGTH OUTLET STUB UP DETAIL N.T.S. NOTE: TO BE USED IN SERVING LINE AREA. System No. W -L -1054 F Ratings -1 and 2 Hr (See Items 1 and 3) T Rating - 0 Hr t L Rating At Ambient j Less Than 1 CFM /Sq Ft L Rating At 400 F - 4 CFM /Sq Ft SECTION A -A 1. Wall Assembly -- The 1 or 2 hr' fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory 2. Through- Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space shall be min 0 in. to max 2 -1/4 in. Pipe may be installed with continuous point contact. Pipe, conduit or tubing may be!,installed at an angle not greater than 45 degrees from perpendicular. Pipe, conduit or tubing to be rigidly supported on both,, sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe -- Nom 30 in diam lil(or smaller) Schedule 10 (or (heavier) steel pipe. B. Iron Pipe -- Nom 30 in. diam �or smaller) cast or ductile iron pipe. C. Conduit -- Nom 4 in diam (or smaller) steel electrical metallic tubing or 6 in. diam steel conduit. D. Copper Tubing -- Nom 6 in. diiam (or smaller) Type L (or heavier) copper tubing. E. Copper Pipe -- Nom 6 in. diam (or smaller) regular (or heavier) copper pipe. I F. Fill, Void or Cavity Material* -- !''Sealant -- Min 5/8 in. thickness of fill material applied within the annulus, flush with both surfaces of wall. At the point on continuous contact locations between pipe and wall, a min 1/2 in. diam bead of fill material shall be applied at the pipe wall interface on both surfaces of wall . HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- FS -One Sealant *Bearing the UL Classification Mark UL F-1® Reproduced by HILTI, Inc. Courtesy of ��P ) Underwriters Laboratories, Inc. FIRESTOP SYSTEMS December 4, 2002 ® US i I EXPANSION JOINT MATERIAL CONDUIT EXPANSION FITTING O -Z CO. TYPE "AX" CONCRETE SLAB BONDING JUMPER O -Z CO. TYPE "AJ "' EXPANSION: FITTING DE N.T.S. :-TAIL LIGHTING FIXTURE SCHEDULE ctla,# MANUFACTURER & CATALOG No. LAMPS FIXTURE Q TYPE (OR APPROVED EQUIVALENT) MOUNTING rw REMARKS r-o ¢w SERVICE TOTAL w n TO TEST o a_ NO. TYPE WATTS Q U E w LEDA DALY 'IN N EHNIEUE IC ITN �ZE VOLTS WATTS EST. 1915 BDL 3390 Mary Street, Suite 216 Miami Florida 3.3133 USA T: 305.461 .9480 F: 305.46 1 .3686 A PENDANT 2 CF26 35K 26 UNV 54 D B L -A C -W H -2 C -2 77 -1.8 K LIGHTING ARTISTRY S J. AGUIRRE & ASSOCIATES P.A. CONSULTING ENGINEERS 9150 SOUTH DADELAND BLVD. SUITE 900 MIAMI, FLORIDA 33156 TELEPHONE: (305) 670 -0141 FAX: (305) 670 -0144 www.ljaapa.com B PENDANT 1 G76.35 T4 35 120 35 Not to Scalc ET -MINX 061- 10064 -020 Architects Project Number FOR PERMIT 11/13/2012 LIGHTING ARTISTRY REVISIONS NO. DESCRIPTION C PENDANT 1 CF32 835 32 120 32 TLA22- 700 -TD -DL N P W- N- S -CF277 DELTA D SURFACE 4 WW LED 4.2 120 16.8 A �' TM. \• 14 q r „;t a e a q �. ia' ,fig • � ` 4 6 275 07 24 277 MARIO, D. PAZOS RE, LICENSE a 52078 Scat INFINITY LIGHTING FIXTURE SCHEDULE AND DETAILS ELECTRICAL sheet vale E RECESSED 2 CF26 35K 26 UNIV 54 PH60- 226QEB2 -CS -UNV -M WT FINELITE F024T5H0 F GRID 2 24 120 48 HPR -A- 2X2- DC- 2T5HO- 277V- SC -C1 -IS 835 HE WILLIAMS G 50G -S24- 332- SAl2125- G3 -EB3 -UNV- GRID 3 F032T8 835 28 UNIV 84 F338 -LP835 BEGHELLI X UNIVERSAL LED 4 UNIV INC VA4RSA BEGHELLI XE RECESSED LED 4 UNIV INC O L2- SA -LR -1 /2 -M CR REMARKS: 1. PROVIDE ELECTRONIC BALLAST AND IN -LINE FUSES FOR ALL FLOURESCENT FIXTURES. CONCRETE SLAB FINISH FLOOR — NOTE: THIS DETAIL SHALL APPLY TO ALL CONDUITS THRU FINISH FLOOR. FOR STUBS UP FROM FIN, FL, FOR SPECIFIED EXTENSION ABOVE FLOOR OR FOR FUTURE USE. l� On /Off Control Device • Relay • Powerpock • Wall Switch Normal Line [I� Normal Lighting Normal Neutral "Sensing" Line Emergency Line Emergency Neutral SLOTTED BRASS PIPE PLUG — CONDUIT COUPLING RIGID WALL CONDUIT CONDUIT TERMINATION AT FIN. FLR. DETAIL N.T.S. NOTE: TO BE USED IN SERVING AREAS, WHERE REQUIRED "Switching" Line Norval Switched Sense (RED 18AWG) Normal Neutral (WHITE 18AWG) Normal Power Sense (BLACK 18AWG0 Emergency Power out (RED 12AWG) Emer_q ency Neutral — (WHITE 18AWG) Emerger)cv Power In (BLACK 12AWG) Emergency Lighting Cut ,jumper loop to use with Normally Closed -Test Switch -Eire Alarm Panel - Security Panel -❑ther Emergency Lighting Control Unit ELCU -200 Typical Wiring ctla,# SOUTH MIAMI HOSPITAL Co) Q CAFETERIA RENOVATION wz <Q� rw r-o ¢w caw PUSH °� F a � 03 w n TO TEST o a_ LD w rwe General Contractor Q U E w Emergency Lighting Cut ,jumper loop to use with Normally Closed -Test Switch -Eire Alarm Panel - Security Panel -❑ther Emergency Lighting Control Unit ELCU -200 Typical Wiring SOUTH MIAMI HOSPITAL SUNSET CAFE CAFETERIA RENOVATION 6200 S.W. 73rd STREET MIAMI, FL 33.143 ownw General Contractor LEDA DALY 'IN N EHNIEUE IC ITN �ZE EST. 1915 3390 Mary Street, Suite 216 Miami Florida 3.3133 USA T: 305.461 .9480 F: 305.46 1 .3686 Architect Associate Architcc:L T No. 22016 CA 924 S J. AGUIRRE & ASSOCIATES P.A. CONSULTING ENGINEERS 9150 SOUTH DADELAND BLVD. SUITE 900 MIAMI, FLORIDA 33156 TELEPHONE: (305) 670 -0141 FAX: (305) 670 -0144 www.ljaapa.com N CAFETERIA Not to Scalc 061- 10064 -020 Architects Project Number FOR PERMIT 11/13/2012 [hawing Issue, REVISIONS NO. DESCRIPTION DATE LEO A DALY COMPANY Copyright 2012 A �' TM. \• 14 q r „;t a e a q �. ia' ,fig • � ` 4 *ELECTPICAL: MARIO, D. PAZOS RE, LICENSE a 52078 Scat LIGHTING FIXTURE SCHEDULE AND DETAILS ELECTRICAL sheet vale EO,01 Sheet Number