13-62-027SHEET METAL MAIN --- - - - - -- T STEEL RODS OR STRAPS SUPPLY TRUNK TO STRUCTURE �\ TYPICAL TRANSITION MAX, 20- ANGLE VOLUME DAMPER W/ LOCKING DEVICE E 2" STANDOFF o/ SHEET METAL BRANCH DUCT / STRUCTURAL CHANNEL 452 PEEL TAP - - -- - -- FITTING BRANCH DUCT TAKEOFF DETAIL N.T,S HVAC DUCT CONSTRUCTION STANDARDS ALL DUCTWORK MUST COMPLY WITH SMACNA HVAC CONSTRUCTION STANDARD. ,--- -- -CLIP ANGLE THIS TYPE SHALL BE USED ,.__3/8 "0 MIN. DIA. EXPANSION BOLTS FOR ONLY IN SLABS OR BEAMS EXISTING SLAB EXISTING CONSTRUCTION OF 4 "MIN DEPTH. 17 '71 v 17 P - -STEEL EXPANSION ANCHOR FOR > a EXISTING CONSTRUCTION (A) I 1/2"0 MIN. DIA. HANGER RODS. 17 V (B) 9 "�—_ EXISTING CONCRETE BEAM TURN BUCKLE e DOUBLE NUTS `ra WASHERS DISTANCE (A) SHALL NOT -1/2 "0 MIN. DIA. HANGER RODS. EXCEED 1/3 OF DISTANCE (B) ANCHOR EMBEDMENT TABLE HANGED? ROD DIA. MIN. ANCHOR EMBEDMENT - SP 1 9/16" 1/2" 2" ------- - - -- 5/8" 2 9/16" TYPICAL. METHODS FOR SECURING HANGER RODS NTS DUCT OR -� -- SMOKE BARRIER SLEEVE FASTENER DAMPER Ir ACCESS DOOR OR PANEL AIR FLOW OPERATOR i d L _l CAULKING SEALANT FULL = 24" PERIMETER OF MAX. DAMPER (TYP. BOTH SIDES) MULTIBLADE DAMPER NOTE: SMOKE DAMPERS MUST BE INSTALLED AT OR ADJACENT TO THE POINT WHERE THE DUCT PASSES THROUGH THE SMOKE PARTITION IN ACCORDANCE WITH NFPA 90A. THE MAXIMUM INSTALLATION DISTANCE IS 24' FROM THE SMOKE PARTITION, HOWEVER THE PREFERRED LOCATION OF LEAKAGE RATED SMOKE DAMPERS IS RIGHT AT THE PARTITION, DUCT AIR OUTLETS, INLETS OR BRANCHES SHALL NOT BE LOCATED BETWEEN THE SMOKE DAMPER AND THE SMOKE PARTITION, PROVIDE A DUCT HANGER AT SMOKE DAMPER LOCATIONS WHERE THE DUCT STRENG`FH IS INADEQUATE FOR THE DAMPER AND ITS OPERATOR. ACCESS DOORS MUST BE PROVIDED AT ALL SMOKE DAMPERS. SMOKE DAMPERS DETAIL NT.S. NOTES: 1. INSTALLATION OF THE DAMPER SHALL BE IN STRICT ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND UL555S. 2. DAMPER RUSKIN SD60 OR APPROVED EQUIVALENT, UPPER ATTACHMENT PER SMACNA FLEXIBLE DUCT -- T -O" MAX. 5' -0" MIN. LENGTH -- 0 MAXIMUM D/8 OFFSET ALLOWED IN LAST D INCHES TO DEVICE WHERE D IS THE INTERNAL FLEX DIAMETER --- NECK SIZE TO MATCH FLEX DUCT SIZE INDICATED MAX. SAG 1/2" PER FOOT BETWEEN SUPPORT POINTS 452 RECTANGULAR TO ROUND LEAD -IN OR ROUND BELLMOUTH COLLAR MOUNT ON SIDE OF DUCT " ADJUSTABLE CLAMP SADDLE 22 GUAGE GALVINIZED STEEL STRAP HANGER AS PER SMACNA FIG. 3 -10 ADJUSTABLE CLAMP DUCT SEALER INSULATE TOP PANEL OF DIFFUSER OR GRILLE CEILING (T -BAR SHOWN. AIR DISTRIBUTION DEVICE GYP. BOARD SIMILAR) (LOUVERED TYPE) LAYIN SHOWN, SURFACE MOUNT SIMILAR NOTES I. FLEXIBLE DUCTS SHALL BE ONE PIECE AND SHALL NOT BE SPLICED TOGETHER, 2. EXTEND FLEXIBLE DUCT INSULATION TO DUCT /DIFFUSER PANEL INSULATION AND SEAL WITH MASTIC. 3. FLEXIBLE AIR DUCT SHALL NOT EXCEED 8 FT. WHEN EXTENDED. ELBOW RADIUS SIZED FOR NO LESS THAN R / D = 1.0. 4. 24 INCH ORANGE SURVEY TAPE SHALL BE PROVIDED ON ALL DUCT QUADRANT LOCKING LEVERS. FLEXIBLE DUCT TAKEOFF DETAIL N.T.S ^ P. BOARD WALL >NSTRUCTION. ISONRY WALL >NSTRUCTION. PLY ACOUSTI( ALANT ALL AR - 22 GA SHEET ANGLE FRAM DUCT SEALER AT 45- TAKEOFF OR ROUND BELLMOUTH COLLAR CONNECTION TO MAIN SUPPY AIR DUCT \�i GYP. BOARD PARTITION MASONRY PARTITION WALL DUCT PENETRATION DETAIL N.T.S. SHEET METAL RUNNER TOP AND BOTTOM SECURED TO DUCT WITH SHEET METAL SCREWS SHEET METAL SINGLE THICKNESS QUARTER ROUND TURNING VANES SINGLE VANE SCHEDULE SOUTH MIAMI HOSPITAL "R" SP GA. SMALL 2" 1 \2" 24 LARGE 4° 31/4" 22 TYPICAL FABRICATED SHEET METAL ELBOW SHEET METAL SINGLE THICKNE, TURNING VANES WITH FLANGEE FASTENERS TOP AND BOTTOM SHEET METAL RUNNER FASTENE DUCT WITH SHEET METAL SCREE NOTE: SINGLE THICKNESS TURNING VANES SHOWN. PROVIDE DOUBLE THICKNESS WHERE SPECIFIED. DUCT TURNING VANE DETAIL N.T.S. VOLUME DAMPER W/ LOCKING QUADRANT E 2" STANDOFF _ASS 0 6rt DENSITY). d d )I I Y I SOUTH MIAMI HOSPITAL SUNSET CAFE CAFETERIA RENOVATION 6200 S.W. 73rd STREET MIAMI, FL 33143 owner General Contractor LEDA DALY N T INTERIORS E zTNI< ES r.l9ls 3390 Mary Street, Suite 216 Miami Florida 33133 USA T: 305.461 .94£30 F: 305.461.36136 Architect Associate Architect PROJ. No. 22016 CA 924 LOUIS J. AGUIRRE & ASSOCIATES P.A. CONSULTING ENGINEERS 9150 SOUTH DADELAND BLVD. SUITE 900 MIAMI, FLORIDA 33156 TELEPHONE: (305) 670 -0141 FAX: (305) 670 -0144 www.ljaapa.com N CAFETERIA N<t tdd sale 061 - 10064 -020 Architects Project Number FOR PERMIT Drawing Issue 11/13/2012 REVISIONS NO. DESCRIPTION DATE LEO A DALY COMPANY Copyright 2012 C..' 1 AJ MECHA IG w SERGIO' S NO P.E. LION 57864 seal DETAILS HVAC Sheet Title M7.00 Sheet Number