13-62-027SHEET METAL MAIN
--- - - - - -- T STEEL RODS OR STRAPS SUPPLY TRUNK
TO STRUCTURE �\
TYPICAL TRANSITION
MAX, 20- ANGLE
VOLUME DAMPER W/ LOCKING
DEVICE E 2" STANDOFF
o/
SHEET METAL
BRANCH DUCT
/
STRUCTURAL CHANNEL
452 PEEL TAP - - -- - --
FITTING
BRANCH DUCT TAKEOFF DETAIL
N.T,S
HVAC DUCT CONSTRUCTION STANDARDS
ALL DUCTWORK MUST COMPLY WITH SMACNA HVAC
CONSTRUCTION STANDARD.
,--- -- -CLIP ANGLE
THIS TYPE SHALL BE USED
,.__3/8 "0 MIN. DIA. EXPANSION BOLTS FOR ONLY IN SLABS OR BEAMS
EXISTING SLAB EXISTING CONSTRUCTION OF 4 "MIN DEPTH.
17 '71 v 17 P - -STEEL EXPANSION ANCHOR FOR
> a EXISTING CONSTRUCTION
(A)
I 1/2"0 MIN. DIA. HANGER RODS.
17 V
(B) 9
"�—_ EXISTING CONCRETE BEAM
TURN BUCKLE
e
DOUBLE NUTS `ra WASHERS
DISTANCE (A) SHALL NOT -1/2 "0 MIN. DIA. HANGER RODS.
EXCEED 1/3 OF DISTANCE (B)
ANCHOR EMBEDMENT TABLE
HANGED? ROD DIA.
MIN. ANCHOR
EMBEDMENT
-
SP
1 9/16"
1/2"
2"
------- - - --
5/8" 2 9/16"
TYPICAL. METHODS FOR SECURING HANGER RODS
NTS
DUCT OR -� --
SMOKE BARRIER
SLEEVE
FASTENER
DAMPER
Ir
ACCESS
DOOR OR
PANEL
AIR FLOW
OPERATOR
i
d L _l
CAULKING
SEALANT FULL = 24"
PERIMETER OF MAX.
DAMPER (TYP.
BOTH SIDES)
MULTIBLADE DAMPER
NOTE:
SMOKE DAMPERS MUST BE INSTALLED AT OR ADJACENT TO THE POINT WHERE THE DUCT PASSES THROUGH
THE SMOKE PARTITION IN ACCORDANCE WITH NFPA 90A. THE MAXIMUM INSTALLATION DISTANCE IS 24' FROM
THE SMOKE PARTITION, HOWEVER THE PREFERRED LOCATION OF LEAKAGE RATED SMOKE DAMPERS IS RIGHT
AT THE PARTITION, DUCT AIR OUTLETS, INLETS OR BRANCHES SHALL NOT BE LOCATED BETWEEN THE SMOKE
DAMPER AND THE SMOKE PARTITION, PROVIDE A DUCT HANGER AT SMOKE DAMPER LOCATIONS WHERE THE
DUCT STRENG`FH IS INADEQUATE FOR THE DAMPER AND ITS OPERATOR. ACCESS DOORS MUST BE PROVIDED
AT ALL SMOKE DAMPERS. SMOKE DAMPERS DETAIL
NT.S.
NOTES:
1. INSTALLATION OF THE DAMPER SHALL BE IN STRICT ACCORDANCE
WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND UL555S.
2. DAMPER RUSKIN SD60 OR APPROVED EQUIVALENT,
UPPER ATTACHMENT
PER SMACNA
FLEXIBLE DUCT -- T -O" MAX.
5' -0" MIN. LENGTH --
0
MAXIMUM D/8 OFFSET ALLOWED
IN LAST D INCHES TO DEVICE
WHERE D IS THE INTERNAL FLEX
DIAMETER ---
NECK SIZE TO MATCH FLEX
DUCT SIZE INDICATED
MAX. SAG 1/2" PER FOOT
BETWEEN SUPPORT POINTS
452 RECTANGULAR TO ROUND
LEAD -IN OR ROUND BELLMOUTH
COLLAR MOUNT ON SIDE OF DUCT "
ADJUSTABLE CLAMP
SADDLE
22 GUAGE GALVINIZED STEEL
STRAP HANGER AS PER
SMACNA FIG. 3 -10
ADJUSTABLE CLAMP
DUCT SEALER
INSULATE TOP PANEL
OF DIFFUSER OR GRILLE
CEILING (T -BAR SHOWN. AIR DISTRIBUTION DEVICE
GYP. BOARD SIMILAR) (LOUVERED TYPE) LAYIN SHOWN,
SURFACE MOUNT SIMILAR
NOTES
I. FLEXIBLE DUCTS SHALL BE ONE PIECE AND SHALL NOT BE SPLICED TOGETHER,
2. EXTEND FLEXIBLE DUCT INSULATION TO DUCT /DIFFUSER PANEL INSULATION
AND SEAL WITH MASTIC.
3. FLEXIBLE AIR DUCT SHALL NOT EXCEED 8 FT. WHEN EXTENDED. ELBOW RADIUS
SIZED FOR NO LESS THAN R / D = 1.0.
4. 24 INCH ORANGE SURVEY TAPE SHALL BE PROVIDED ON ALL DUCT
QUADRANT LOCKING LEVERS.
FLEXIBLE DUCT TAKEOFF DETAIL
N.T.S
^ P. BOARD WALL
>NSTRUCTION.
ISONRY WALL
>NSTRUCTION.
PLY ACOUSTI(
ALANT ALL AR
- 22 GA SHEET
ANGLE FRAM
DUCT SEALER AT 45- TAKEOFF
OR ROUND BELLMOUTH COLLAR
CONNECTION TO MAIN
SUPPY AIR DUCT
\�i
GYP. BOARD PARTITION MASONRY PARTITION
WALL DUCT PENETRATION DETAIL
N.T.S.
SHEET METAL RUNNER TOP AND BOTTOM
SECURED TO DUCT WITH SHEET METAL SCREWS
SHEET METAL SINGLE THICKNESS
QUARTER ROUND TURNING VANES
SINGLE VANE SCHEDULE
SOUTH MIAMI HOSPITAL
"R"
SP
GA.
SMALL
2"
1 \2"
24
LARGE
4°
31/4"
22
TYPICAL FABRICATED SHEET
METAL ELBOW
SHEET METAL SINGLE THICKNE,
TURNING VANES WITH FLANGEE
FASTENERS TOP AND BOTTOM
SHEET METAL RUNNER FASTENE
DUCT WITH SHEET METAL SCREE
NOTE: SINGLE THICKNESS TURNING VANES SHOWN. PROVIDE DOUBLE
THICKNESS WHERE SPECIFIED.
DUCT TURNING VANE DETAIL
N.T.S.
VOLUME DAMPER W/ LOCKING
QUADRANT E 2" STANDOFF
_ASS
0 6rt DENSITY).
d d
)I I
Y I
SOUTH MIAMI HOSPITAL
SUNSET CAFE
CAFETERIA RENOVATION
6200 S.W. 73rd STREET
MIAMI, FL 33143
owner
General Contractor
LEDA DALY N T INTERIORS E zTNI<
ES r.l9ls
3390 Mary Street, Suite 216
Miami Florida 33133 USA
T: 305.461 .94£30 F: 305.461.36136
Architect
Associate Architect
PROJ. No. 22016 CA 924
LOUIS J. AGUIRRE & ASSOCIATES P.A.
CONSULTING ENGINEERS
9150 SOUTH DADELAND BLVD. SUITE 900
MIAMI, FLORIDA 33156
TELEPHONE: (305) 670 -0141
FAX: (305) 670 -0144
www.ljaapa.com
N
CAFETERIA
N<t tdd sale
061 - 10064 -020
Architects Project Number
FOR PERMIT
Drawing Issue 11/13/2012
REVISIONS
NO.
DESCRIPTION
DATE
LEO A DALY COMPANY Copyright 2012
C..'
1 AJ
MECHA IG
w SERGIO' S NO P.E.
LION 57864
seal
DETAILS
HVAC
Sheet Title
M7.00
Sheet Number