13-62-02675 CFM (MAKE -UP
AIR FROM DOOR
UNDERCUTS)
`1 FAIR BALANCE DIAGRAM
SCALE: N.T.S.
AIR BALANCING
TABLE
MECHANICAL /ELECTRICAL
TOTAL OUTSIDE AIR
KITCHEN HOOD EXHAUST FAN = 3170 CFM
ANU -7 = 1800 CFM 0/A
GENERAL EXHAUST = 705 CFM
AHU -10 = 2000 CFM 0/A
ROOM
TITUS
TOTAL = 3875 CFM
TOTAL = 3800 CFM O/A
O/A = 3800 CFM
MODEL. NO. AND / OR
E/A = 3875 CFM
TDC -AA
- 75 CFM ( MAKE -UP AIR FROM DOOR UNDERCUTS)
350 FL
LSL 106H
RETURN AIR
�y
ALL ALUM.
ALL ALUM.
ALL ALUM.
ALL ALUM.
HORIZONTAL DRAW
THRU
HORIZONTAL DRAW
THRU
2' x 2'
5
rAHU-7
SURFACE
1800 CFM
460/3/60
SURFACE
460/3/60
460/3/60
SUPPLY AIR
CAFETERIA
(DIA7)
0/A
LAY -IN
LOCATION
MECHANICAL
/ELECTRICAL ROOM
_
FIXED LOUVERED
FIXED LOUVERED
LOUVERED
EXISTING
2500
DEVICE TYPE
2800
3170 CFM E/A
2090
2500
VANES
— —1
ANU -10
350, 3/4" SPACING
2000 CFM
2800
EXISTING EXHAUST
SUPPLY
SUPPLY
R /A, EXH OR TRANS.
SUPPLY AIR
1035
OUTSIDE AIR -CFM
LDIAB)
1555
O/A
Drawing Issue 11/13/2012
FAN ON ROOF
530
18 x 18
625
1035
DESIGN AIR FLOW REQUIREMENTS FOR EXISTING AHU'S
_ J ��
NECK SIZE
LOUVERED FACE
SEE DRAWINGS
SEE DRAWINGS
SEE DRAWINGS
1800
2000
NECK SIZE
100% 0/A
1200
1200
1 �I /(EF -I)
NOTE: ALL AIR HANDLING UNIT FILTERS SHALL BE REPLACED WITH FILTER TO MATCH EXISTING FILTER EFFICIENCY (MERV 7).
PATTERN
SEE DRAWINGS
EXISTING
SEE DRAWINGS
SEE DRAWINGS
OPPOSED BLADE DAMPERS
YES
YES
YES
YES
NOTES:
1. ALTERNATE MANUFACTURERS OF EQUAL QUALITY MAY BE SUBMITTED FOR APPROVAL.
2. ALL AIR DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION AND FULLY GASKETED.
3. UNLESS OTHERWISE NOTED, FINISH OF ALL AIR DEVICES SHALL BE BAKED OFF - WHITE,
4. FOR SQUARE NECK OUTLETS CONNECTED TO A ROUND FLEXIBLE OR RIGID DUCT, .
5. MOUNTING BORDERS TO BE CONSISTENT WITH ACTUAL CEILING TYPE; COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLANS.
LEO A DALY COMPANY Copyright 2012
ME C IVICA "r
J R 0 S RRANO P.E.
1200 CFM R/A
3000 CFM S/A 2000 CFM S/A
Seal
I
705 CFM E/A
HVAC
Sheet Title
EXISTING EXHAUST-
- -
- - -�
�- - --I
FAN ON ROOF
I
KITCHEN HOOD)
(EF -6)
EXISTING
L _ _ J
A /C -I (WEST!,)
DIA7C1
(EXISTING)
3170 CFM E/A
�^
— °_":3
1200 CFM S/A
1200 CFM R/A
L___J
A /C -2 (EST)
DIA7C1
I CAFETERIA
(EXISTING)
2000 CFM S/A
2000 CFM R/A
75 CFM (MAKE -UP
AIR FROM DOOR
UNDERCUTS)
`1 FAIR BALANCE DIAGRAM
SCALE: N.T.S.
AIR BALANCING
TABLE
TOTAL EXHAUST
TOTAL OUTSIDE AIR
KITCHEN HOOD EXHAUST FAN = 3170 CFM
ANU -7 = 1800 CFM 0/A
GENERAL EXHAUST = 705 CFM
AHU -10 = 2000 CFM 0/A
(EXISTING EXH. FAN EF -6)
TITUS
TOTAL = 3875 CFM
TOTAL = 3800 CFM O/A
O/A = 3800 CFM
MODEL. NO. AND / OR
E/A = 3875 CFM
TDC -AA
- 75 CFM ( MAKE -UP AIR FROM DOOR UNDERCUTS)
AIR DISTRIBUTION SCHEDULE -- —
DESIGNATION
A
B
C
D
UNIT DESIGNATION
MANUFACTURER
TITUS
TITUS
TITUS
TITUS
Mc QUAY
MODEL. NO. AND / OR
TDC -AA
TDC -AA
350 FL
350 FL
LSL 106H
CATALOG NO.
ALL ALUM.
ALL ALUM.
ALL ALUM.
ALL ALUM.
HORIZONTAL DRAW
THRU
HORIZONTAL DRAW
THRU
2' x 2'
5
2' X 2'
SURFACE
1
FRAME TYPE
460/3/60
SURFACE
460/3/60
460/3/60
AREA SERVED
CAFETERIA
LAY -IN
CAFETERIA
LAY -IN
LOCATION
MECHANICAL
/ELECTRICAL ROOM
_
FIXED LOUVERED
FIXED LOUVERED
LOUVERED
LOUVERED
2500
DEVICE TYPE
2800
OUTSIDE AIR -CFM
2090
2500
VANES
VANES
350, 3/4" SPACING
350, 3/4" SPACING
2800
FUNCTION
SUPPLY
SUPPLY
R /A, EXH OR TRANS.
R/A OR EXH
1035
OUTSIDE AIR -CFM
ROUND NECK
1555
Drawing Issue 11/13/2012
RETURN AIR - CFM
530
18 x 18
625
1035
DESIGN AIR FLOW REQUIREMENTS FOR EXISTING AHU'S
AIR FLOW - CFM
NECK SIZE
LOUVERED FACE
SEE DRAWINGS
SEE DRAWINGS
SEE DRAWINGS
1800
2000
NECK SIZE
RETURN AIR - CFM
1200
1200
ON DRAWING
NOTE: ALL AIR HANDLING UNIT FILTERS SHALL BE REPLACED WITH FILTER TO MATCH EXISTING FILTER EFFICIENCY (MERV 7).
PATTERN
SEE DRAWINGS
SEE DRAWINGS
SEE DRAWINGS
SEE DRAWINGS
OPPOSED BLADE DAMPERS
YES
YES
YES
YES
NOTES:
1. ALTERNATE MANUFACTURERS OF EQUAL QUALITY MAY BE SUBMITTED FOR APPROVAL.
2. ALL AIR DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION AND FULLY GASKETED.
3. UNLESS OTHERWISE NOTED, FINISH OF ALL AIR DEVICES SHALL BE BAKED OFF - WHITE,
4. FOR SQUARE NECK OUTLETS CONNECTED TO A ROUND FLEXIBLE OR RIGID DUCT, .
5. MOUNTING BORDERS TO BE CONSISTENT WITH ACTUAL CEILING TYPE; COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLANS.
EXISTING AHU'S ORIGINAL DESIGN DATA
AREA SERVED
AHU -7
AHU -10
A /C -1 (WEST)
A /C -2 (EAST)
UNIT DESIGNATION
(D1A7)
(D1A8)
(D1A7C1)
(D1A7C1)
MANUFACTURER
Mc QUAY
Mc QUAY
TRANE
TRANE
MODEL NUMBER
MS 108H
LSL 106H
VCH054
VCA40F
.TYPE
HORIZONTAL DRAW
THRU
HORIZONTAL DRAW
THRU
HORIZONTAL DRAW
THRU
HORIZONTAL DRAW
THRU
FAN MOTOR (H.P.)
5
5
1
1
ELECTRICAL SERVICE
460/3/60
460/3/60
460/3/60
460/3/60
AREA SERVED
CAFETERIA
CAFETERIA
CAFETERIA
CAFETERIA
LOCATION
MECHANICAL
/ELECTRICAL ROOM
MECHANICAL
/ELECTRICAL ROOM
ABOVE CEILING
ABOVE CEILING
AIRFLOW - CFM
4090
2500
1500
2800
OUTSIDE AIR -CFM
2090
2500
RETURN AIR - CFM
2000
1500
2800
EXISTING AHU'S T & B REPORT DATED 7/23/2012
AIR FLOW - CFM
920
1555
625
1035
OUTSIDE AIR -CFM
390
1555
Drawing Issue 11/13/2012
RETURN AIR - CFM
530
625
1035
DESIGN AIR FLOW REQUIREMENTS FOR EXISTING AHU'S
AIR FLOW - CFM
3000
2000
1200
2000
OUTSIDE AIR -CFM
1800
2000
RETURN AIR - CFM
1200
1200
2000
NOTE: ALL AIR HANDLING UNIT FILTERS SHALL BE REPLACED WITH FILTER TO MATCH EXISTING FILTER EFFICIENCY (MERV 7).
EXISTING EXHAUST FAN EF -6 AND EF -1 (BEFORE DEMOLITION)
DESIGNATION EF -6 EF -1
AREA SERVED
CAFETERIA
KITCHEN HOOD AND PIZZA OVEN HOOD
AIR FLOW - CFM
2060
3450
LOCATION
ROOF
ROOF
Ownr
EXISTING EXHAUST FAN EF -6 AND EF -1 (AFTER DEMOLITION)
DESIGNATION EF -6 EF -1
AREA SERVED
CAFETERIA
KITCHEN HOOD
AIR FLOW - CFM
705
3170
LOCATION
ROOF
ROOF
DINING
OUTSIDE AIR CALCULATIONS SCHEDULE
SOUTH MIAMI HOSPITAL
SUNSET CAFE
BASED ON ASHRAE STANDARD 62.1 -2004
SPACE SYSTEM AREA (SQ.FT.)
TOTAL PERSONS CFM /PERSON
CFM REQUIRED CFM PROVIDED
KITCHEN
A /C -1 & 2
772
8
Ownr
17
136
SERVERY
A /C -1 & 2
1562
223
R C H I T E C E R 10 IZyTNJG E
LEDA DALY N L ANN ING
9
2007
DINING
AHU -7 & 10
2747
183
1
9
19647
Architect
Associate ArchlLect
PROJ. No. 22016 CA 924
TOTAL
CONSULTING ENGINEERS
9150 SOUTH DADELAND BLVD. SUITE 900
3790
3800
NOTE: BREATHING ZONE OUTDOOR AIRFLOWS (CFM REQUIRED) WAS CALCULATED ACCORDING TO ASHRAE 62.1 -2004 SECTION 6.2.2.1
(VBz= RPPz +RAAz).
SOUTH MIAMI HOSPITAL
SUNSET CAFE
CAFETERIA RENOVATION
6200 S.W. 73rd STREET
MIAMI, FL 33143
Ownr
General Contractor
R C H I T E C E R 10 IZyTNJG E
LEDA DALY N L ANN ING
EST. 1915
3390 Mary Street, Suite 216
Miami Florida 33133 USA
T: 305.461 .9480 F: 305.461 .3686
Architect
Associate ArchlLect
PROJ. No. 22016 CA 924
LOUIS J. AGUIRRE & ASSOCIATES P.A.
CONSULTING ENGINEERS
9150 SOUTH DADELAND BLVD. SUITE 900
MIAMI, FLORIDA 33156
TELEPHONE: (305) 670 -0141
FAX: (305) 670 -0144
www.ljaapa.com
N
CAFETERIA
Not to scale
061 -10064 -020
Architects Project Number
FOR PERMIT
Drawing Issue 11/13/2012
REVISIONS
NO.
[DESCRIPTION
DATE
LEO A DALY COMPANY Copyright 2012
ME C IVICA "r
J R 0 S RRANO P.E.
"LICENSE 57864
Seal
SCHEDULES
HVAC
Sheet Title
M6,00
Shoe[ Number