13-62-02675 CFM (MAKE -UP AIR FROM DOOR UNDERCUTS) `1 FAIR BALANCE DIAGRAM SCALE: N.T.S. AIR BALANCING TABLE MECHANICAL /ELECTRICAL TOTAL OUTSIDE AIR KITCHEN HOOD EXHAUST FAN = 3170 CFM ANU -7 = 1800 CFM 0/A GENERAL EXHAUST = 705 CFM AHU -10 = 2000 CFM 0/A ROOM TITUS TOTAL = 3875 CFM TOTAL = 3800 CFM O/A O/A = 3800 CFM MODEL. NO. AND / OR E/A = 3875 CFM TDC -AA - 75 CFM ( MAKE -UP AIR FROM DOOR UNDERCUTS) 350 FL LSL 106H RETURN AIR �y ALL ALUM. ALL ALUM. ALL ALUM. ALL ALUM. HORIZONTAL DRAW THRU HORIZONTAL DRAW THRU 2' x 2' 5 rAHU-7 SURFACE 1800 CFM 460/3/60 SURFACE 460/3/60 460/3/60 SUPPLY AIR CAFETERIA (DIA7) 0/A LAY -IN LOCATION MECHANICAL /ELECTRICAL ROOM _ FIXED LOUVERED FIXED LOUVERED LOUVERED EXISTING 2500 DEVICE TYPE 2800 3170 CFM E/A 2090 2500 VANES — —1 ANU -10 350, 3/4" SPACING 2000 CFM 2800 EXISTING EXHAUST SUPPLY SUPPLY R /A, EXH OR TRANS. SUPPLY AIR 1035 OUTSIDE AIR -CFM LDIAB) 1555 O/A Drawing Issue 11/13/2012 FAN ON ROOF 530 18 x 18 625 1035 DESIGN AIR FLOW REQUIREMENTS FOR EXISTING AHU'S _ J �� NECK SIZE LOUVERED FACE SEE DRAWINGS SEE DRAWINGS SEE DRAWINGS 1800 2000 NECK SIZE 100% 0/A 1200 1200 1 �I /(EF -I) NOTE: ALL AIR HANDLING UNIT FILTERS SHALL BE REPLACED WITH FILTER TO MATCH EXISTING FILTER EFFICIENCY (MERV 7). PATTERN SEE DRAWINGS EXISTING SEE DRAWINGS SEE DRAWINGS OPPOSED BLADE DAMPERS YES YES YES YES NOTES: 1. ALTERNATE MANUFACTURERS OF EQUAL QUALITY MAY BE SUBMITTED FOR APPROVAL. 2. ALL AIR DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION AND FULLY GASKETED. 3. UNLESS OTHERWISE NOTED, FINISH OF ALL AIR DEVICES SHALL BE BAKED OFF - WHITE, 4. FOR SQUARE NECK OUTLETS CONNECTED TO A ROUND FLEXIBLE OR RIGID DUCT, . 5. MOUNTING BORDERS TO BE CONSISTENT WITH ACTUAL CEILING TYPE; COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLANS. LEO A DALY COMPANY Copyright 2012 ME C IVICA "r J R 0 S RRANO P.E. 1200 CFM R/A 3000 CFM S/A 2000 CFM S/A Seal I 705 CFM E/A HVAC Sheet Title EXISTING EXHAUST- - - - - -� �- - --I FAN ON ROOF I KITCHEN HOOD) (EF -6) EXISTING L _ _ J A /C -I (WEST!,) DIA7C1 (EXISTING) 3170 CFM E/A �^ — °_":3 1200 CFM S/A 1200 CFM R/A L___J A /C -2 (EST) DIA7C1 I CAFETERIA (EXISTING) 2000 CFM S/A 2000 CFM R/A 75 CFM (MAKE -UP AIR FROM DOOR UNDERCUTS) `1 FAIR BALANCE DIAGRAM SCALE: N.T.S. AIR BALANCING TABLE TOTAL EXHAUST TOTAL OUTSIDE AIR KITCHEN HOOD EXHAUST FAN = 3170 CFM ANU -7 = 1800 CFM 0/A GENERAL EXHAUST = 705 CFM AHU -10 = 2000 CFM 0/A (EXISTING EXH. FAN EF -6) TITUS TOTAL = 3875 CFM TOTAL = 3800 CFM O/A O/A = 3800 CFM MODEL. NO. AND / OR E/A = 3875 CFM TDC -AA - 75 CFM ( MAKE -UP AIR FROM DOOR UNDERCUTS) AIR DISTRIBUTION SCHEDULE -- — DESIGNATION A B C D UNIT DESIGNATION MANUFACTURER TITUS TITUS TITUS TITUS Mc QUAY MODEL. NO. AND / OR TDC -AA TDC -AA 350 FL 350 FL LSL 106H CATALOG NO. ALL ALUM. ALL ALUM. ALL ALUM. ALL ALUM. HORIZONTAL DRAW THRU HORIZONTAL DRAW THRU 2' x 2' 5 2' X 2' SURFACE 1 FRAME TYPE 460/3/60 SURFACE 460/3/60 460/3/60 AREA SERVED CAFETERIA LAY -IN CAFETERIA LAY -IN LOCATION MECHANICAL /ELECTRICAL ROOM _ FIXED LOUVERED FIXED LOUVERED LOUVERED LOUVERED 2500 DEVICE TYPE 2800 OUTSIDE AIR -CFM 2090 2500 VANES VANES 350, 3/4" SPACING 350, 3/4" SPACING 2800 FUNCTION SUPPLY SUPPLY R /A, EXH OR TRANS. R/A OR EXH 1035 OUTSIDE AIR -CFM ROUND NECK 1555 Drawing Issue 11/13/2012 RETURN AIR - CFM 530 18 x 18 625 1035 DESIGN AIR FLOW REQUIREMENTS FOR EXISTING AHU'S AIR FLOW - CFM NECK SIZE LOUVERED FACE SEE DRAWINGS SEE DRAWINGS SEE DRAWINGS 1800 2000 NECK SIZE RETURN AIR - CFM 1200 1200 ON DRAWING NOTE: ALL AIR HANDLING UNIT FILTERS SHALL BE REPLACED WITH FILTER TO MATCH EXISTING FILTER EFFICIENCY (MERV 7). PATTERN SEE DRAWINGS SEE DRAWINGS SEE DRAWINGS SEE DRAWINGS OPPOSED BLADE DAMPERS YES YES YES YES NOTES: 1. ALTERNATE MANUFACTURERS OF EQUAL QUALITY MAY BE SUBMITTED FOR APPROVAL. 2. ALL AIR DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION AND FULLY GASKETED. 3. UNLESS OTHERWISE NOTED, FINISH OF ALL AIR DEVICES SHALL BE BAKED OFF - WHITE, 4. FOR SQUARE NECK OUTLETS CONNECTED TO A ROUND FLEXIBLE OR RIGID DUCT, . 5. MOUNTING BORDERS TO BE CONSISTENT WITH ACTUAL CEILING TYPE; COORDINATE WITH ARCHITECTURAL REFLECTED CEILING PLANS. EXISTING AHU'S ORIGINAL DESIGN DATA AREA SERVED AHU -7 AHU -10 A /C -1 (WEST) A /C -2 (EAST) UNIT DESIGNATION (D1A7) (D1A8) (D1A7C1) (D1A7C1) MANUFACTURER Mc QUAY Mc QUAY TRANE TRANE MODEL NUMBER MS 108H LSL 106H VCH054 VCA40F .TYPE HORIZONTAL DRAW THRU HORIZONTAL DRAW THRU HORIZONTAL DRAW THRU HORIZONTAL DRAW THRU FAN MOTOR (H.P.) 5 5 1 1 ELECTRICAL SERVICE 460/3/60 460/3/60 460/3/60 460/3/60 AREA SERVED CAFETERIA CAFETERIA CAFETERIA CAFETERIA LOCATION MECHANICAL /ELECTRICAL ROOM MECHANICAL /ELECTRICAL ROOM ABOVE CEILING ABOVE CEILING AIRFLOW - CFM 4090 2500 1500 2800 OUTSIDE AIR -CFM 2090 2500 RETURN AIR - CFM 2000 1500 2800 EXISTING AHU'S T & B REPORT DATED 7/23/2012 AIR FLOW - CFM 920 1555 625 1035 OUTSIDE AIR -CFM 390 1555 Drawing Issue 11/13/2012 RETURN AIR - CFM 530 625 1035 DESIGN AIR FLOW REQUIREMENTS FOR EXISTING AHU'S AIR FLOW - CFM 3000 2000 1200 2000 OUTSIDE AIR -CFM 1800 2000 RETURN AIR - CFM 1200 1200 2000 NOTE: ALL AIR HANDLING UNIT FILTERS SHALL BE REPLACED WITH FILTER TO MATCH EXISTING FILTER EFFICIENCY (MERV 7). EXISTING EXHAUST FAN EF -6 AND EF -1 (BEFORE DEMOLITION) DESIGNATION EF -6 EF -1 AREA SERVED CAFETERIA KITCHEN HOOD AND PIZZA OVEN HOOD AIR FLOW - CFM 2060 3450 LOCATION ROOF ROOF Ownr EXISTING EXHAUST FAN EF -6 AND EF -1 (AFTER DEMOLITION) DESIGNATION EF -6 EF -1 AREA SERVED CAFETERIA KITCHEN HOOD AIR FLOW - CFM 705 3170 LOCATION ROOF ROOF DINING OUTSIDE AIR CALCULATIONS SCHEDULE SOUTH MIAMI HOSPITAL SUNSET CAFE BASED ON ASHRAE STANDARD 62.1 -2004 SPACE SYSTEM AREA (SQ.FT.) TOTAL PERSONS CFM /PERSON CFM REQUIRED CFM PROVIDED KITCHEN A /C -1 & 2 772 8 Ownr 17 136 SERVERY A /C -1 & 2 1562 223 R C H I T E C E R 10 IZyTNJG E LEDA DALY N L ANN ING 9 2007 DINING AHU -7 & 10 2747 183 1 9 19647 Architect Associate ArchlLect PROJ. No. 22016 CA 924 TOTAL CONSULTING ENGINEERS 9150 SOUTH DADELAND BLVD. SUITE 900 3790 3800 NOTE: BREATHING ZONE OUTDOOR AIRFLOWS (CFM REQUIRED) WAS CALCULATED ACCORDING TO ASHRAE 62.1 -2004 SECTION 6.2.2.1 (VBz= RPPz +RAAz). SOUTH MIAMI HOSPITAL SUNSET CAFE CAFETERIA RENOVATION 6200 S.W. 73rd STREET MIAMI, FL 33143 Ownr General Contractor R C H I T E C E R 10 IZyTNJG E LEDA DALY N L ANN ING EST. 1915 3390 Mary Street, Suite 216 Miami Florida 33133 USA T: 305.461 .9480 F: 305.461 .3686 Architect Associate ArchlLect PROJ. No. 22016 CA 924 LOUIS J. AGUIRRE & ASSOCIATES P.A. CONSULTING ENGINEERS 9150 SOUTH DADELAND BLVD. SUITE 900 MIAMI, FLORIDA 33156 TELEPHONE: (305) 670 -0141 FAX: (305) 670 -0144 www.ljaapa.com N CAFETERIA Not to scale 061 -10064 -020 Architects Project Number FOR PERMIT Drawing Issue 11/13/2012 REVISIONS NO. [DESCRIPTION DATE LEO A DALY COMPANY Copyright 2012 ME C IVICA "r J R 0 S RRANO P.E. "LICENSE 57864 Seal SCHEDULES HVAC Sheet Title M6,00 Shoe[ Number