13-62-025FLOOR PLAN
SCALE: 3/16 " =1' -0"
- HVAC NEW WORK
NEW WORK KEY NOTES:
10 EXISTING AHU'S # 7 (D1A7) AND 10 (D1A8) LOCATED IN MECHANICAL /ELECTRICAL ROOM, SHALL
BE REFURBISHED. BOTH UNITS SHALL BE THOROUGHLY CHECKED AND RECONDITIONED AS
REQUIRED (CLEAN AND COMB EVAPORATOR COIL, REPACK OR REPLACE BEARINGS, REPLACE
FAN BELTS, LUBRICATE, PURGE CONDENSATE DRAINAGE PIPING, REPLACE FILTERS, CLEAN
CASING, REMOVE RUSTED AREAS AND PAINT WITH RUST INHIBITOR, REPLACE ANY SECTION OF
UNIT DAMAGED INSULATION, ETC.). ALL EXISTING THERMOSTATS AND CONTROL DEVICES SHALL
ALSO BE THOROUGHLY CHECKED AND RECONDITIONED (OR REPLACED) AS REQUIRED, TO
ASSURE THE PROPER OPERATION OF THE AIR CONDITIONING SYSTEMS. ADJUST AHU'S TO
DELIVER THE INDICATED AMOUNT OF SUPPLY AND OUTSIDE AIR CFM. IF A CHANGE IN DRIVE
SIZE IS REQUIRED IN ORDER FOR THE AHU'S TO ACHIEVE THE SPECIFIED CFM VALUES,
CONTRACTOR SHALL PROCEED TO PROVIDE THE REQUIRED DRIVE SIZE.
20 EXISTING FAN COIL UNITS'S # D1A7C1 (EAST) AND D1A7C1(WEST) INSTALLED ABOVE THE
CAFETERIA'S CEILING, SHALL BE REFURBISHED. BOTH UNITS SHALL BE THOROUGHLY CHECKED
AND RECONDITIONED AS REQUIRED (CLEAN AND COMB EVAPORATOR COIL, REPACK OR
REPLACE BEARINGS, REPLACE FAN BELTS, LUBRICATE, PURGE CONDENSATE DRAINAGE PIPING,
REPLACE FILTERS, CLEAN CASING, REMOVE RUSTED AREAS AND PAINT WITH RUST INHIBITOR,
REPLACE ANY SECTION OF UNIT DAMAGED INSULATION, ETC.). ALL EXISTING THERMOSTATS
AND CONTROL DEVICES SHALL ALSO BE THOROUGHLY CHECKED AND RECONDITIONED (OR
REPLACED) AS REQUIRED, TO ASSURE THE PROPER OPERATION OF THE AIR CONDITIONING
SYSTEMS. ADJUST AHU'S TO DELIVER THE INDICATED AMOUNT OF SUPPLY AND OUTSIDE AIR
CFM. IF A CHANGE IN DRIVE SIZE IS REQUIRED IN ORDER FOR THE AHU'S TO ACHIEVE THE
SPECIFIED CFM VALUES, CONTRACTOR SHALL PROCEED TO PROVIDE THE REQUIRED DRIVE
SIZE.
0 4' 8'
SCALE: 3/16 " =1' -0"
I
SOUTH MIAMI HOSPITAL
SUNSET CAFE
CAFETERIA RENOVATION
6200 S.W. 73rd STREET
MIAMI, FL 33143
Owner
General Contractor
LEA DA V IIN�TE1t1 1I ." E
EST. 1915
3:390 Mary Street, Suite 216
Miami Florida :33133 USA
T: 305.461.9480 F: 305.461.3686
Architect
Associate Architect
PROJ. No. 22016 CA 924
LOUIS J. AGUIRRE & ASSOCIATES P.A.
CONSULTING ENGINEERS
9150 SOUTH DADELAND BLVD, SUITE 900
MIAMI, FLORIDA 33156
TELEPHONE: (305) 670 -0141
FAX: (305) 670 -0144
www.ljaapa.com
N
CAFETERIA
Not to Scale
061 -10064 -020
Architects Project Nurnber
FOR PERMIT
Drawing Issue 11/13/2012
REVISIONS
NO.
DESCRIPTION
DATE
LEO A DALY COMPANY Copyright 2012
assn ��TMa
erg i4 P �T
a+ '��<rdr
C-1
en
MECN .NICAL,
ERGIO RRANO P.E.
LICE SE # 57864
Seal
FLOOR PLAN
HVAC
Shea Titic
M3,02
Shcct Number