13-62-020O O 0 1= CONSTRUCTION FLOOR PLAN - FIRE PROTECTION SCALE: 1/8"=l'—Om 4' 0 4' 8' SCALE: 1 /8 " =1' -0" PIPE SIZING PROCEDURES NOTE: CONTRACTOR IS TO FIELD VERIFY THE EXISTING PIPE SIZES AND SHALL REPLACE ANY PIPING AS REQUIRED TO COMPLY WITH NFPA 13 SECTION 11.2.2 "PIPE SHEDULE METHOD ". REFER TO TABLE 14.5.2.2.1 BELOW, WHERE THE " PIPE SCHEDULE METHOD" WILL NOT BE USED, CONTRACTOR IS TO PERFORM HYDRAULIC CALCULATIONS PER NFPA SECTION 11.2.3 " HYDRAULIC CALCULATION METHODS ". NFPA 13 (2002) Table 14.5.2.2.1 LIGHT HAZARD PIPE SCHEDULES STEEL PIPE SIZE (IN) # OF SPRINKLERS 1 1 -2 _ 1 1/4 3 1 1/2 4 -5 2 6 -10 GENERAL NOTES 1. EXISTING BUILDING IS FULLY SPRINKLERED. CONTRACTOR IS TO RELOCATE / OFFSET EXISTING MAINS AND BRANCH PIPING AS REQUIRED TO CONNECT TO NEW SPRINKLER HEADS SHOWN ON THIS SHEET IN COORDINATION WITH THE EXISTING AND NEW SYSTEMS, DUCTWORK, ECT. LOCATED IN THE PLENUM. 2. NEW ARMOVERS SHALL BE IN ACCORDANCE WITH THE DETAILS ON SHEET FP7.00. 3. ALL SPRIKLERS SHALL BE NEW AND SPRINKLER HEADS NOT USED SHALL BE CAPPED OFF. CONCEPTUAL DESIGN ONLY FIRE PROTECTION CONTRACTOR'S WORKING PLANS AS PER NFPA 13 MUST BE SUBMITTED TO AND APPROVED BY THE AUTHORITY HAVING JURISDICTION BEFORE ANY FIRE PROTECTION SYSTEM IS INSTALLED OR REMODELED. i' i3, f' y_ p,„ �' 3iLL��):": YS .k'"f"4"Vs12:�iti&RI`4�T`^.z° .'.�L...___— _. 9. ( ,�W'm�ftrti tat� ) 1 y �• +m: a.^'eik,� +r. 1 slit-101111IFTED FOR AW011 'D 6 Coup I' �5F bk`1�i��� SOUTH MIAMI HOSPITAL SUNSET CAFE CAFETERIA RENOVATION 6200 S.W. 73rd STREET MIAMI, FL 33143 owner General Contractor PLANNING LEDA DALY E N T; R N SING E EST. 1915 3390 Mary Street, Suite 216 Miami Florida ., 313 3 USA T: 305.461 .9480 F: 305.461 .3686 Arc:hllecf Associate Architect PROD. No. 22016 CA 924 LOUIS J. AGUIRRE & ASSOCIATES P.A. CONSULTING ENGINEERS 9150 SOUTH DADELAND BLVD. SUITE 900 MIAMI, FLORIDA 33156 TELEPHONE: (305) 670 -0141 FAX: (305) 670 -0144 www.ljoapa.com N e)91C 7Efr A F 1E IR 11A Nut to Scale 061 - 10064 -020 Architects Project Number FOR PERMIT 11/13/2012 Drawing 155uc REVISIONS NO. DESCRIPTION DATE LEO A DALY COMPANY Copyright 2012 t "� ,5 , k z0 MECHANICAL: EDUARDO A. SUAREZ, RE, Seal LICENSE u 64759 CONSTRUCTION FLOOR PLAN FIRE PROTECTION Sheet Title FP3000 Sheet Numbcr