Loading...
13-62-007TAG EXITING SUMMARY SMOKE COMPARTMENT REFERENCE TYPE /FACTOR WIDTH IN INCHES PROVIDED CAPACITY IN PERSONS CODE - NUMBER LIFE SAFETY COMMENT /ISSUE PLAN FOR IMPROVEMENT PFI NfPA 101 -2006 LIFE SAFETY COMMENTS 1 1 hr Rated wall not stenciled Add 1 hr stencil Per AHCA req's 2 2 hr Rated wall not stenciled Add 2 hr stencil Per AHCA req's 3 Non Rated wall stenciled Remove wall stencil Per AHCA req's 84" 480 Remove 1 hr stencil - Replace with 2 hr E 4 2 hr Rated wall stenciled 1 HR stencil Per AHCA req's F EXT. OR, /.2 Remove 2 hr stencil - Replace with 1 hr 480 5 1 hr Rated wall stenciled 2 HR stencil Per AHCA req's 300 566 H EXT, OR. /.2 48" 240 300 SF 18,17A 6 Unsealed fire rated wall penetrations Seal all penetrations with fire caulking 8.5.6 J EXT. DR. /.2 60" 18.3.7 A 7 Unsealed smoke wall penetrations Seal all penetrations Ithcaulking 8.5.6 210 11 Extend wall to underside of the floor or EXT. DR. /.2 84" 480 roof deck above - seal any penetrations M 8 Corridor wall is not continous through the wal I for smoke resistance 19.3,62 EXIT CAPACITY AVAILABLE 4,490 Extend wall to bottom of structure - seal 19,31.1 240 SF 33 any penetrations through the wall with 19.3.2.1.5 9 1 hr Wall does not go up to deck fire caulking - add 1hr stencil 19.3.5.2 Extend wall to bottom of structure on both 10 Gypsum board goes up on one side only sides 19,3.6.2 18.2.3.7- (4) 11 Door needs astragal Add door astragal 18.3.6.2.1 12 Door needs positive latching Add positive latching to door 19,3.6.3.5 13 Door needs closer Add door closer 19.3.6.3.5 14 Door not smoke tight Add smoke seals 19.3.63.1 Clearance between bottom of the corridor door and the floor covering 15 exceeds Vn Add sweep 193.6.3A 16 No door frame rating Install rated door frame or field rate 19.3.6,3.12 17 Label on door was painted over Install new label 19.35.3.12 18 No door rating - needs45min Install 45 min fire rated door or field rate 19,3.1.1 19 No door rating - needs 90min Install 90 min fire rated dooror field rate 193.1.1 20 Exit sl missing direction arrow Add direction arrow 7.10.2 21 Exit sign not required Remove exit stn 7.10,1,2 22 Missing exit sign _ Add new exit sign 7.10.1.2 Seal large opening? This occurs In Level 1, where the registration Is located, one option Is to combine compartments 1H 19.3.2.1 23 Wall opening in rated wall and 11? 19.3.2.1.5 Gift Shop needs to be resistant to smoke, 24 It exceeds 500sgft Apply notes: 9, 13 and 14 19.3.6.1(4) 25 Unsealed slab penetration Seal opening in slab 8.2.3 26 Hole in slab for conduit Seal opening in slab 8.2.3 Verify they are located within a suite. If 19.3.2.1 27 Mad gases open to corridor not, close room with smoke resistant wall 193.2A Penetrations in 1hr wall are sealed with Verify that all penetrations and head of 28 wrongcatjlkfng wall are sealed with proper fire caulking 8.5.6 Duct penetrating 1hr wall doesn't seem Verify fire dampers on all ducts 29 to have fire damper penetrating walls Plywood is being used to seal Remove plywood and seal penetrations 30 penetrations with proper caulkin FBC603.1 31 jAccess door has broken handle Install new handle 19.3.6.3.5 32 Access door doesn't have a closer Add access door closer 193.6.3.5 Facility may want to consider re- routing pipe and conduit to comply with current 33 Conduit and exhaust pipe in stair well code standards 74.3,11 (6) 71.2A,1.1 34 No handrail on side ofstairs Fasten new handrail towall 7.2.2AA.5 7.2.2A.1.1 35 No handrail on either side of stairs Install handrails on both side of stairs 7.22AA 36 No extension on handrail Replace handrail to have proper extension 7.2.2AA.9 Missing door between corridor and 37 microbiolo within a suite Add smoke door Missing wall to seal corridor between 38 soiled utility room and nurse station Add new corridor smoke wall Verify if beam is gravity loaded, if it is it 39 Exposed steel beam needs to be fire proof 40 Door needs flush bolts and coordinator Add automatic flush bolt and coordinator 19.3.6.3.5 There is a 3" pipe above ceiling that is cut Seal penetration around pipe with proper 41 not sealed around or capped caulking and close pipe with proper cap 8.5.6 42 Hole in slab for conduit Seal opening in slab 8.2.3 Glass door in 1hr wall to corridor needs to Replace doorwlth proper fire rated glass 8,3,3 43 be rated door 193.63.1 Glass wall to corridor, window opening Verify wall and window are smoke 83.3 44 34 "x34" resistant 19.3,6.5 Verify that door is fire rated and add proper label. If not, install new proper fire 45 No Label on door rated door or field rate 19.3,1.1 46 Door is missing knob Add knob to door 19.36.3 Storage room needs to be rated and Extend wall to bottom of structure - add 47 ceiling tiles are In bad condition lhrstencil - replaceceilin tiles 48 Door doesn't have a coordinator Add door coordinator 19.3.6.3.5 Walls around Labs need to be 1h rated Extend wall to bottom of structure - add 49 and doors should be 45 min rated door stencil - Install 45 min rated door 19.311 Walls around "shaft" doesn't go all the 50 way up to deck and have stencil Verify existence of shaft 51 Not an exit identify door as a not exit door 7.103.3 52 Exit discharge from P -Stair 2 I deficient Take exit designation off stair 53.1 Remove doors to provide line of sight to exit 53.2 Add exit door In Doctor's Lounge 53.3 Add new double egress doors to 53 Exit discharge from P -Stair 3 Is deficient extend smoke zone SD 54.1 Move stair door to corridor 54.2 Move door to Mech. Room to corridor 54 Exit discharge from MB -Stair 1 Is deficient 54.3 Upgrade walls to 2hr and add stencil SMOKE COMPARTMENT SUMMARY EXITING SUMMARY SMOKE COMPARTMENT EXIT TYPE /FACTOR WIDTH IN INCHES PROVIDED CAPACITY IN PERSONS N A EXT, DR. /.2 48" 240 60 B EXT. DR. /.2 48" 240 240 SF C EXT. OR.42 84" 480 3,758 9,209 D EXT. DR.42 84" 480 E EXT, OR.42 84" 480 8 11 93 F EXT. OR, /.2 84" 480 KITCHEN DINING SUB —TOTAL G EXT. OR. /,2 60" 300 566 H EXT, OR. /.2 48" 240 300 SF 1 EXT, OR. /.2 42" 210 8,440 J EXT. DR. /.2 60" 300 TREATMENT K EXT. DR. /.2 42" 210 11 L EXT. DR. /.2 84" 480 M EXT. DR. /.2 70" 350 24 EXIT CAPACITY AVAILABLE 4,490 EXIT CAPACITY REQUIRED 1,309 240 SF SMOKE COMPARTMENT SUMMARY SMOKE COMPARTMENT PRIMARY USE AREA SF OCCUPANT FAC LOAD P R TOR ON OCCUPANT LOAD N 1A TREATMENT 14,265 240 SF 60 a: 4 IB TREATMENT 15,215 240 SF 64 1C ASSEMBLY BUSINESS SUB —TOTAL 3,758 9,209 15 SF 100 SF 250 92 12.967 342 1D TREATMENT STORAGE BUSINESS SUB —TOTAL 1,995 3,343 9,340 240 SF 300 SF 100 SF 8 11 93 14,670 112 1E KITCHEN DINING SUB —TOTAL 91503 5,707 200 SF 11 SF 48 518 15,210 566 iF MECH. EQ. 5,330 300 SF 18 lG TREATMENT 8,440 240 SF 35 lH TREATMENT 5,905 240 SF 25 11 TREATMENT 7,195 240 SF 30 1J TREATMENT 5,585 240 SF 24 1K TREATMENT 7,775 240 SF 33 TOTAL • FIRST LEVEL 112.565 1,309 ARCHITECT HKS ARCHITECTS, INC. #AA F000119 1221 BRICKELL AVENUE, SUITE 1220 MIAMI, FL33131 305 - 416 -6100 HKS PROJECT NUMBER 14296.000 DATE 04.12.2011 ISSUE STATEMENT OF CONDITION /LIFE SAFETY STUDY SHEET TITLE PARTIAL FIRST FLOOR LIFE SAFETY PLAN SHEET NO, LS -12 M M M W O Qa O CIO n O MM� O HKS PROJECT NUMBER 14296.000 DATE 04.12.2011 ISSUE STATEMENT OF CONDITION /LIFE SAFETY STUDY SHEET TITLE PARTIAL FIRST FLOOR LIFE SAFETY PLAN SHEET NO, LS -12