13-62-007TAG
EXITING SUMMARY
SMOKE
COMPARTMENT
REFERENCE
TYPE /FACTOR
WIDTH IN
INCHES
PROVIDED
CAPACITY IN
PERSONS
CODE -
NUMBER
LIFE SAFETY COMMENT /ISSUE
PLAN FOR IMPROVEMENT PFI
NfPA 101 -2006
LIFE SAFETY COMMENTS
1
1 hr Rated wall not stenciled
Add 1 hr stencil
Per AHCA req's
2
2 hr Rated wall not stenciled
Add 2 hr stencil
Per AHCA req's
3
Non Rated wall stenciled
Remove wall stencil
Per AHCA req's
84"
480
Remove 1 hr stencil - Replace with 2 hr
E
4
2 hr Rated wall stenciled 1 HR
stencil
Per AHCA req's
F
EXT. OR, /.2
Remove 2 hr stencil - Replace with 1 hr
480
5
1 hr Rated wall stenciled 2 HR
stencil
Per AHCA req's
300
566
H
EXT, OR. /.2
48"
240
300 SF
18,17A
6
Unsealed fire rated wall penetrations
Seal all penetrations with fire caulking
8.5.6
J
EXT. DR. /.2
60"
18.3.7 A
7
Unsealed smoke wall penetrations
Seal all penetrations Ithcaulking
8.5.6
210
11
Extend wall to underside of the floor or
EXT. DR. /.2
84"
480
roof deck above - seal any penetrations
M
8
Corridor wall is not continous
through the wal I for smoke resistance
19.3,62
EXIT CAPACITY AVAILABLE
4,490
Extend wall to bottom of structure - seal
19,31.1
240 SF
33
any penetrations through the wall with
19.3.2.1.5
9
1 hr Wall does not go up to deck
fire caulking - add 1hr stencil
19.3.5.2
Extend wall to bottom of structure on both
10
Gypsum board goes up on one side only
sides
19,3.6.2
18.2.3.7- (4)
11
Door needs astragal
Add door astragal
18.3.6.2.1
12
Door needs positive latching
Add positive latching to door
19,3.6.3.5
13
Door needs closer
Add door closer
19.3.6.3.5
14
Door not smoke tight
Add smoke seals
19.3.63.1
Clearance between bottom of the
corridor door and the floor covering
15
exceeds Vn
Add sweep
193.6.3A
16
No door frame rating
Install rated door frame or field rate
19.3.6,3.12
17
Label on door was painted over
Install new label
19.35.3.12
18
No door rating - needs45min
Install 45 min fire rated door or field rate
19,3.1.1
19
No door rating - needs 90min
Install 90 min fire rated dooror field rate
193.1.1
20
Exit sl missing direction arrow
Add direction arrow
7.10.2
21
Exit sign not required
Remove exit stn
7.10,1,2
22
Missing exit sign
_
Add new exit sign
7.10.1.2
Seal large opening? This occurs In Level 1,
where the registration Is located, one
option Is to combine compartments 1H
19.3.2.1
23
Wall opening in rated wall
and 11?
19.3.2.1.5
Gift Shop needs to be resistant to smoke,
24
It exceeds 500sgft
Apply notes: 9, 13 and 14
19.3.6.1(4)
25
Unsealed slab penetration
Seal opening in slab
8.2.3
26
Hole in slab for conduit
Seal opening in slab
8.2.3
Verify they are located within a suite. If
19.3.2.1
27
Mad gases open to corridor
not, close room with smoke resistant wall
193.2A
Penetrations in 1hr wall are sealed with
Verify that all penetrations and head of
28
wrongcatjlkfng
wall are sealed with proper fire caulking
8.5.6
Duct penetrating 1hr wall doesn't seem
Verify fire dampers on all ducts
29
to have fire damper
penetrating walls
Plywood is being used to seal
Remove plywood and seal penetrations
30
penetrations
with proper caulkin
FBC603.1
31 jAccess
door has broken handle
Install new handle
19.3.6.3.5
32
Access door doesn't have a closer
Add access door closer
193.6.3.5
Facility may want to consider re- routing
pipe and conduit to comply with current
33
Conduit and exhaust pipe in stair well
code standards
74.3,11 (6)
71.2A,1.1
34
No handrail on side ofstairs
Fasten new handrail towall
7.2.2AA.5
7.2.2A.1.1
35
No handrail on either side of stairs
Install handrails on both side of stairs
7.22AA
36
No extension on handrail
Replace handrail to have proper extension
7.2.2AA.9
Missing door between corridor and
37
microbiolo within a suite
Add smoke door
Missing wall to seal corridor between
38
soiled utility room and nurse station
Add new corridor smoke wall
Verify if beam is gravity loaded, if it is it
39
Exposed steel beam
needs to be fire proof
40
Door needs flush bolts and coordinator
Add automatic flush bolt and coordinator
19.3.6.3.5
There is a 3" pipe above ceiling that is cut
Seal penetration around pipe with proper
41
not sealed around or capped
caulking and close pipe with proper cap
8.5.6
42
Hole in slab for conduit
Seal opening in slab
8.2.3
Glass door in 1hr wall to corridor needs to
Replace doorwlth proper fire rated glass
8,3,3
43
be rated
door
193.63.1
Glass wall to corridor, window opening
Verify wall and window are smoke
83.3
44
34 "x34"
resistant
19.3,6.5
Verify that door is fire rated and add
proper label. If not, install new proper fire
45
No Label on door rated
door or field rate 19.3,1.1
46
Door is missing knob
Add knob to door 19.36.3
Storage
room needs to be rated and
Extend wall to bottom of structure - add
47 ceiling
tiles are In bad condition
lhrstencil - replaceceilin tiles
48
Door doesn't have a coordinator
Add door coordinator 19.3.6.3.5
Walls around Labs need to be 1h rated
Extend wall to bottom of structure - add
49 and
doors should be 45 min rated door stencil
- Install 45 min rated door 19.311
Walls around "shaft" doesn't go all the
50
way up to deck and have stencil
Verify existence of shaft
51
Not an exit identify
door as a not exit door 7.103.3
52 Exit
discharge from P -Stair 2 I deficient Take
exit designation off stair
53.1
Remove doors to provide line of sight
to
exit
53.2
Add exit door In Doctor's Lounge
53.3
Add new double egress doors to
53 Exit
discharge from P -Stair 3 Is deficient extend
smoke zone SD
54.1
Move stair door to corridor
54.2
Move door to Mech. Room to corridor
54 Exit
discharge from MB -Stair 1 Is deficient 54.3
Upgrade walls to 2hr and add stencil
SMOKE COMPARTMENT SUMMARY
EXITING SUMMARY
SMOKE
COMPARTMENT
EXIT
TYPE /FACTOR
WIDTH IN
INCHES
PROVIDED
CAPACITY IN
PERSONS
N
A
EXT, DR. /.2
48"
240
60
B
EXT. DR. /.2
48"
240
240 SF
C
EXT. OR.42
84"
480
3,758
9,209
D
EXT. DR.42
84"
480
E
EXT, OR.42
84"
480
8
11
93
F
EXT. OR, /.2
84"
480
KITCHEN
DINING
SUB —TOTAL
G
EXT. OR. /,2
60"
300
566
H
EXT, OR. /.2
48"
240
300 SF
1
EXT, OR. /.2
42"
210
8,440
J
EXT. DR. /.2
60"
300
TREATMENT
K
EXT. DR. /.2
42"
210
11
L
EXT. DR. /.2
84"
480
M
EXT. DR. /.2
70"
350
24
EXIT CAPACITY AVAILABLE
4,490
EXIT CAPACITY REQUIRED
1,309
240 SF
SMOKE COMPARTMENT SUMMARY
SMOKE
COMPARTMENT
PRIMARY
USE
AREA
SF
OCCUPANT
FAC
LOAD P R TOR
ON
OCCUPANT
LOAD
N
1A
TREATMENT
14,265
240 SF
60
a:
4
IB
TREATMENT
15,215
240 SF
64
1C
ASSEMBLY
BUSINESS
SUB —TOTAL
3,758
9,209
15 SF
100 SF
250
92
12.967
342
1D
TREATMENT
STORAGE
BUSINESS
SUB —TOTAL
1,995
3,343
9,340
240 SF
300 SF
100 SF
8
11
93
14,670
112
1E
KITCHEN
DINING
SUB —TOTAL
91503
5,707
200 SF
11 SF
48
518
15,210
566
iF
MECH. EQ.
5,330
300 SF
18
lG
TREATMENT
8,440
240 SF
35
lH
TREATMENT
5,905
240 SF
25
11
TREATMENT
7,195
240 SF
30
1J
TREATMENT
5,585
240 SF
24
1K
TREATMENT
7,775
240 SF
33
TOTAL • FIRST LEVEL
112.565
1,309
ARCHITECT
HKS ARCHITECTS, INC.
#AA F000119
1221 BRICKELL AVENUE, SUITE 1220
MIAMI, FL33131
305 - 416 -6100
HKS PROJECT NUMBER
14296.000
DATE
04.12.2011
ISSUE
STATEMENT OF
CONDITION /LIFE
SAFETY STUDY
SHEET TITLE
PARTIAL FIRST FLOOR
LIFE SAFETY
PLAN
SHEET NO,
LS -12
M
M
M
W
O
Qa
O
CIO
n
O
MM�
O
HKS PROJECT NUMBER
14296.000
DATE
04.12.2011
ISSUE
STATEMENT OF
CONDITION /LIFE
SAFETY STUDY
SHEET TITLE
PARTIAL FIRST FLOOR
LIFE SAFETY
PLAN
SHEET NO,
LS -12