Loading...
13-62-006ai Q w iv z z m C; A 0 R. TAG NUMBER LIFE SAFETY COMMENT /ISSUE PLAN FOR IMPROVEMENT(PFI ) REFERENCE CODE - NWA101 4006 LIFE SAFETY COMMENTS 1 1 hr Rated wall not stenciled Add 1 hr stencil Per AHCA req's 2 2 hr Rated wail not stenciled Add 2 hr stencil Per AHCA req's 3 Non Rated wall stenciled Remove wall stencil Per AHCA req's 4 2 hr Rated wall stenciled 1 HR Remove 1 hr stencil - Replace with 2 hr stencil Per AHCA req's 5 1 hr Rated wall stenciled 2 HR Remove 2 hr stencil - Replace with 1 hr stencil Per AHCA req's 6 Unsealed fire rated wall penetrations Seat all penetrations with fire caulking 18.3.7 A 8.5,6 7 Unsealed smoke wall penetrations Seal all penetrations with caulking 18.3.7A 8.5.6 8 Corridor wall is not continous Extend wall to underside of the floor or roof deck above - seal any penetrations through the wall forsmoke resistance 19.3.6.2 9 1 h Wall does not oup to deck Extend wall to bottom of structure - seal any penetrations through the wall with fire caulking - add lhr stencil 19.3.2.1 19.3.2.1.5 19,3.6.2 10 Gypsum board goes up on one side only Extend wall to bottom of structure on both sides 19.3.6.2 11 Door needs astragal Add door astragal 18.2.3.7- (4) 18.3.6.2.1 12 Door needs positive latching Add positive latching to door 19.3.6.3.5 13 Door needs closer Add door closer 19.3.6.3.5 14 Door not smoke tight Add smoke seals 19.3.6.3.1 15 Clearance between bottom of the corridor door and the floor covering exceeds lin Add sweep 19.3.6.3A 16 No door frame rating Install rated doorframe or field rate 19.3.6.3.12 17 Label on door was painted over Install new label 19,3.6.3.12 18 No door rating - needs 45 min Install 45 min fire rated door or field rate 19.3.1.1 19 No door rating- needs 90 min Install 90 min fire rated door or field rate 19.3.1.1 20 Exit sign missing direction arrow Add direction arrow 7.10.2 21 Exit sign not required Remove exit sign 7,10.12 22 Missing exit sign Add new exit sign 7.10.1.2 23 Wall opening in rated wall Seal large opening? This occurs in Level 1, where the registration is located, one option is to combine compartments 1H and 11? 19.3.2.1 19.3.2.1.5 24 Gift Shop needs to be resistant to smoke, it exceeds 500sgft Apply notes: 9, 13 and 14 19.3.6.1(4) 25 Unsealed slab penetration Seal opening in slab 8.2.3 26 Hole In slab for conduit Seal opening in slab 8.2.3 27 Med gases open to corridor Verify they are located within a suite. If not, close room with smoke resistant wall 19.3.2.1 19.32.4 28 Penetrations in lhr wall are sealed with wrongcaulking Verify that all penetrations and head of wall are sealed with proper fire caulking 8.5.6 29 Duct penetrating lhrwall doesn't seem to have fire damper Verify fire dampers on all duds penetrating walls 8.5.6 30 Plywood is being used to seal penetrations Remove plywood and seal penetrations with propercaulking FBC 603.1 31 Access door has broken handle Install new handle 193.6.3.5 32 Access doordoesn't have a closer Add access door closer 19.3.6.3.5 33 Conduit and,exhaust pipe in stairwell Facility may want to consider re- routing pipe and conduit to comply with current code standards 7.1.3.2.1(6) 34 No handrail on side of stairs Fasten new handrail to wall 7.2.2A.1.1 7.2.2AA.5 35 No handrail on either side of stairs Install handrails on both side of stairs 7.2.2A.1,1 7.2.2AA 36 No extension on handrail Replace handrail to have properextension 7.2.2AA.9 37 Missing door between corridor and microbiology within a suite Add smoke door 38 Missing wall to seal corridor between soiled utility room and nurse station Add new corridor smoke wall 39 Exposed steel beam Verify If beam is gravity loaded, if it is it needs to be fire roof 40 Door needs flush bolts and coordinator Add automatic flush bolt and coordinator 19.3.6.3.5 41 There is a 3" pipe above ceiling that Is cut not sealed around or capped Seal penetration around pipe with proper caulking and close pipe with propercap 8.5.6 42 Hole in slab for conduit Seal opening in slab 8.2.3 43 Glass doorin 1hrWall to corriclorneeds to be rated Replace doorwith proper fire rated glass door 8.3.3 19.3.6.3.1 44 Glass wall to corridor, window opening 34 "x34" Verify wall and window are smoke resistant 8.3.3 19.3.6.5 45 No label on door Verify that door is fire rated and add proper label. If not, install new proper fire rated door or field rate 19.3.1.1 46 Door is missing knob Add knob to door 19.3.63 47 Storage room needs to be rated and ceiling tiles are In bad condition Extend wall to bottom of structure - add lhrstencil - replace ceiling tiles 48 Doordoesn't have a coordinator Add door coordinator 19.3.6.3.5 49 Walls around Labs need to be lh rated and doors should be 45 min rated door Extend wall to bottom of structure - add stencil - install 45 min rated door 19.32.2 50 Walls around "shaft" doesn't go all the way up to deck and have stencil Verify existence of shaft 51 Not an exit Identify door as a not exit door 7.109.3 52 Exit dischar a from P -Stair 2 is deficient Take exit designations off stair 53 Exit discharge from P -Stair 3 is deficient 53.1 Remove doors to provide line of sight to exit 53.2 Add exit door in Doctor's Lounge 53.3 Add new double egress doors to extend smoke zone 1D 54 Exit discharge from MB -Stair 1 is deficient 54.1 Move stair doo r to corridor 54.2 Move door to Mech. Room to corridor 54.3 Upgrade walls to 2hr and add stencil QIw I LIFE SAFETY PLAN LEGEND 1 HR FIRE BARRIER,,,,... =- ��aN = =� 1 HR SMOKE BARRIER EXIT 1 HR FIRE BARRIER /SHAFT WALL +—••— __. 2 HR FIRE BARRIER J N 2 HR FSMOKE BARRIER EXT. DR. /.2 2 HR BARRIER /SHAFT WALL 240 4 HR FIRE BARRIER B SMOKE PARTITION (NON RATED) 48" NON RATED 240 SF EXIT ACCESS CORRIDOR / EXIT PASSAGE 480 2 HOUR D SUITE ROOMS 84" PERIMETER INSTITUTIONAL EXT. DR. /.2 OCCUPANCY 480 BUSINESS F OCCUPANCY 84" 480 + ++ + ASSEMBLY ++ + OCCUPANCY +r + AREA UNDER r/ CONSTRUCTION 48" SMOKE 300 SF COMPARTMENT EXT. DR. /.2 WALL 210 EXIT ► EXIT SIGN - HATCH 60" INDICATES EXIT TEXT ® ® �y AND ARROW H INDICATES DIRECTION 210 FIRE DEPARTMENT FIDC CONNECTION 84" 480 FEC FIRE EXTINGUISHER CABINET EXT. DR. /,2 70" FE FIRE EXTINGUISHER EXIT CAPACITY AVAILABLE PULL STATION EXIT CAPACITY REQUIRED STROBE LIGHT / HORN '- TOTAL TRAVEL DISTANCE 200' -0" TO AN EXIT TRAVEL DISTANCE TO ADJACENT 200' -0" — — SMOKE ZONE A � 1 PROJECT INFORMATION i PROJECT NAME: BAPTIST HEALTH SOUTH MIAMI HOSPITAL FIFE SAFETY SURVEY ADDRE53: 6200 SW 73 STREET. SOUTH MIAMI FL 33143 PROPOSED USE: LIFE SAFETY SURVEY OWNER- CONTACT PERSON: LUIS FERNANDEZ DE CASTRO PHONE: 786- 6624660 APPLICABLE CODES - BUILDING CODE: 2007 FLORIDA BUILDING CODE W /2009 SUPPLEMENTS AND AJA GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND HEALTHCARE FACILITIES -2006 EDITION -FIRE CODE: 2006 NFPA 1, UNIFORM FIRE CODE / FLORIDA FIRE PREVENTION CODE 2007 -LIFE SAFETY CODE: NPFA 101 - LIFE SAFETY CODE 2006 - ACCESIBILITY CODE: 2007 FLORIDA BUILDING CODE W/2009 SUPPLEMENTS - CH.11 -STATE FIRE MARSHALL'S RULE 6943.012 FAC: NFPA 10 -2002. STANDARD FOR PORTABLE FIRE EXTINGUISHERS NFPA 13 -2002, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS NFPA 72 -2002, NATIONAL FIRE ALARM CODE NFPA 80 -1999 STANDARD FOR FIRE DOORS AND FIRE WINDOWS NFPA 99 -2005. STANDARD FOR HEALTH- CARE FACILITIES NFPA 105 -2003 SMOKE CONTROL DOOR ASSEMBLIES NFPA 221 -2006 STANDARD ON FIRE WALLS AND FIRE BARRIER WALLS BUILDING PLANNING OCCUPANCY: INSTITUTIONAL GROUP 1 (F8C 2006) MIXED OCCUPANCY? YES / NO REQUIRED FIRE SEPARATION: 1 HR TYPE OF CONSTRUCTION CONSTRUCTION TYPE: FBC TYPE IB - NFPA 220 - TYPE II (2 -2 -2) SMOKE COMPARTMENT SUMMARY EXITING SUMMARY SMOKE COMPARTMENT EXIT TYPE /FACTOR WIDTH IN INCHES PROVIDED CAPACITY IN PERSONS J N A EXT. DR. /.2 48" 240 60 B EXT. DR. /.2 48" 240 240 SF C EXT. DR. /.2 84" 480 3,758 9,209 D EXT. DR. /.2 84" 480 E EXT. DR. /.2 84" 480 8 11 93 F EXT. DR./.2 84" 480 KITCHEN DINING SUB -TOTAL G EXT. DR. /.2 60" 300 566 H EXT. DR. /.2 48" 240 300 SF 1 EXT. DR. /.2 42" 210 8,440 J EXT. DR. /.2 60" 300 TREATMENT K EXT. DR. /.2 42" 210 11 L EXT. DR. /.2 84" 480 M EXT. DR. /,2 70" 350 24 EXIT CAPACITY AVAILABLE 4,490 EXIT CAPACITY REQUIRED T 1,309 240 SF A � 1 PROJECT INFORMATION i PROJECT NAME: BAPTIST HEALTH SOUTH MIAMI HOSPITAL FIFE SAFETY SURVEY ADDRE53: 6200 SW 73 STREET. SOUTH MIAMI FL 33143 PROPOSED USE: LIFE SAFETY SURVEY OWNER- CONTACT PERSON: LUIS FERNANDEZ DE CASTRO PHONE: 786- 6624660 APPLICABLE CODES - BUILDING CODE: 2007 FLORIDA BUILDING CODE W /2009 SUPPLEMENTS AND AJA GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS AND HEALTHCARE FACILITIES -2006 EDITION -FIRE CODE: 2006 NFPA 1, UNIFORM FIRE CODE / FLORIDA FIRE PREVENTION CODE 2007 -LIFE SAFETY CODE: NPFA 101 - LIFE SAFETY CODE 2006 - ACCESIBILITY CODE: 2007 FLORIDA BUILDING CODE W/2009 SUPPLEMENTS - CH.11 -STATE FIRE MARSHALL'S RULE 6943.012 FAC: NFPA 10 -2002. STANDARD FOR PORTABLE FIRE EXTINGUISHERS NFPA 13 -2002, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS NFPA 72 -2002, NATIONAL FIRE ALARM CODE NFPA 80 -1999 STANDARD FOR FIRE DOORS AND FIRE WINDOWS NFPA 99 -2005. STANDARD FOR HEALTH- CARE FACILITIES NFPA 105 -2003 SMOKE CONTROL DOOR ASSEMBLIES NFPA 221 -2006 STANDARD ON FIRE WALLS AND FIRE BARRIER WALLS BUILDING PLANNING OCCUPANCY: INSTITUTIONAL GROUP 1 (F8C 2006) MIXED OCCUPANCY? YES / NO REQUIRED FIRE SEPARATION: 1 HR TYPE OF CONSTRUCTION CONSTRUCTION TYPE: FBC TYPE IB - NFPA 220 - TYPE II (2 -2 -2) SMOKE COMPARTMENT SUMMARY w SMOKE COMPARTMENT PRIMARY USE AREA SF OCCUPANT LOAD FACTOR PER PERSON OCCUPANT LOAD J N 1A TREATMENT 14,265 240 SF 60 a• 18 TREATMENT 15,215 240 SF 64 1C ASSEMBLY BUSINESS SUB -TOTAL 3,758 9,209 15 SF 100 SF 250 92 12,967 342 1D TREATMENT STORAGE BUSINESS SUB -TOTAL 1,995 3,343 9,340 240 5F 300 SF 100 SF 8 11 93 14,676 112 1E KITCHEN DINING SUB -TOTAL 9,503 5,707 200 SF 11 SF 48 518 15,210 566 IF MECH. EQ. 5,330 300 SF 18 1G TREATMENT 8,440 240 SF 35 iH TREATMENT 5.905 240 SF 25 11 TREATMENT 7,195 240 SF 30 1J TREATMENT 5,585 240 SF 24 1K TREATMENT 7,775 240 SF 33 TOTAL- FIRST LEVEL 112.565 1,309 PARTIAL FIRST FLOOR LIFE SAFETY PLAN 1/16" = 1'-0" 0 4' W 16' 32, 48' 64' 80' 9 1 "M GRAPHIC SCALE 1/16" -1' -0' 9) 2011 HKS, INC. Zh R HI<S ARCHITECT HKS ARCHITECTS, INC. #AA F000119 1221 BRICKELL AVENUE, SUITE 1220 MIAMI, FL 33131 305 -416 -6100 r1 M O � M M O CIS Q, � KEYPLAN cq p q 9 °> 923990�, REVISION HKS PROJECT NUMBER 14296.000 DATE 04.12.2011 ISSUE STATEMENT OF CONDITION/LIFE SAFETY STUDY SHEET TITLE PARTIAL FIRST FLOOR LIFE SAFETY PLAN SHEET NO. LS -11 V Vk: 4�-4^a r�.lJY p �t 9 � T