13-62-006ai
Q
w
iv
z
z
m
C;
A
0
R.
TAG
NUMBER
LIFE SAFETY COMMENT /ISSUE
PLAN FOR IMPROVEMENT(PFI )
REFERENCE
CODE -
NWA101 4006
LIFE SAFETY COMMENTS
1
1 hr Rated wall not stenciled
Add 1 hr stencil
Per AHCA req's
2
2 hr Rated wail not stenciled
Add 2 hr stencil
Per AHCA req's
3
Non Rated wall stenciled
Remove wall stencil
Per AHCA req's
4
2 hr Rated wall stenciled 1 HR
Remove 1 hr stencil - Replace with 2 hr
stencil
Per AHCA req's
5
1 hr Rated wall stenciled 2 HR
Remove 2 hr stencil - Replace with 1 hr
stencil
Per AHCA req's
6
Unsealed fire rated wall penetrations
Seat all penetrations with fire caulking
18.3.7 A
8.5,6
7
Unsealed smoke wall penetrations
Seal all penetrations with caulking
18.3.7A
8.5.6
8
Corridor wall is not continous
Extend wall to underside of the floor or
roof deck above - seal any penetrations
through the wall forsmoke resistance
19.3.6.2
9
1 h Wall does not oup to deck
Extend wall to bottom of structure - seal
any penetrations through the wall with
fire caulking - add lhr stencil
19.3.2.1
19.3.2.1.5
19,3.6.2
10
Gypsum board goes up on one side only
Extend wall to bottom of structure on both
sides
19.3.6.2
11
Door needs astragal
Add door astragal
18.2.3.7- (4)
18.3.6.2.1
12
Door needs positive latching
Add positive latching to door
19.3.6.3.5
13
Door needs closer
Add door closer
19.3.6.3.5
14
Door not smoke tight
Add smoke seals
19.3.6.3.1
15
Clearance between bottom of the
corridor door and the floor covering
exceeds lin
Add sweep
19.3.6.3A
16
No door frame rating
Install rated doorframe or field rate
19.3.6.3.12
17
Label on door was painted over
Install new label
19,3.6.3.12
18
No door rating - needs 45 min
Install 45 min fire rated door or field rate
19.3.1.1
19
No door rating- needs 90 min
Install 90 min fire rated door or field rate
19.3.1.1
20
Exit sign missing direction arrow
Add direction arrow
7.10.2
21
Exit sign not required
Remove exit sign
7,10.12
22
Missing exit sign
Add new exit sign
7.10.1.2
23
Wall opening in rated wall
Seal large opening? This occurs in Level 1,
where the registration is located, one
option is to combine compartments 1H
and 11?
19.3.2.1
19.3.2.1.5
24
Gift Shop needs to be resistant to smoke,
it exceeds 500sgft
Apply notes: 9, 13 and 14
19.3.6.1(4)
25
Unsealed slab penetration
Seal opening in slab
8.2.3
26
Hole In slab for conduit
Seal opening in slab
8.2.3
27
Med gases open to corridor
Verify they are located within a suite. If
not, close room with smoke resistant wall
19.3.2.1
19.32.4
28
Penetrations in lhr wall are sealed with
wrongcaulking
Verify that all penetrations and head of
wall are sealed with proper fire caulking
8.5.6
29
Duct penetrating lhrwall doesn't seem
to have fire damper
Verify fire dampers on all duds
penetrating walls
8.5.6
30
Plywood is being used to seal
penetrations
Remove plywood and seal penetrations
with propercaulking
FBC 603.1
31
Access door has broken handle
Install new handle
193.6.3.5
32
Access doordoesn't have a closer
Add access door closer
19.3.6.3.5
33
Conduit and,exhaust pipe in stairwell
Facility may want to consider re- routing
pipe and conduit to comply with current
code standards
7.1.3.2.1(6)
34
No handrail on side of stairs
Fasten new handrail to wall
7.2.2A.1.1
7.2.2AA.5
35
No handrail on either side of stairs
Install handrails on both side of stairs
7.2.2A.1,1
7.2.2AA
36
No extension on handrail
Replace handrail to have properextension
7.2.2AA.9
37
Missing door between corridor and
microbiology within a suite
Add smoke door
38
Missing wall to seal corridor between
soiled utility room and nurse station
Add new corridor smoke wall
39
Exposed steel beam
Verify If beam is gravity loaded, if it is it
needs to be fire roof
40
Door needs flush bolts and coordinator
Add automatic flush bolt and coordinator
19.3.6.3.5
41
There is a 3" pipe above ceiling that Is cut
not sealed around or capped
Seal penetration around pipe with proper
caulking and close pipe with propercap
8.5.6
42
Hole in slab for conduit
Seal opening in slab
8.2.3
43
Glass doorin 1hrWall to corriclorneeds to
be rated
Replace doorwith proper fire rated glass
door
8.3.3
19.3.6.3.1
44
Glass wall to corridor, window opening
34 "x34"
Verify wall and window are smoke
resistant
8.3.3
19.3.6.5
45
No label on door
Verify that door is fire rated and add
proper label. If not, install new proper fire
rated door or field rate
19.3.1.1
46
Door is missing knob
Add knob to door
19.3.63
47
Storage room needs to be rated and
ceiling tiles are In bad condition
Extend wall to bottom of structure - add
lhrstencil - replace ceiling tiles
48
Doordoesn't have a coordinator
Add door coordinator
19.3.6.3.5
49
Walls around Labs need to be lh rated
and doors should be 45 min rated door
Extend wall to bottom of structure - add
stencil - install 45 min rated door
19.32.2
50
Walls around "shaft" doesn't go all the
way up to deck and have stencil
Verify existence of shaft
51
Not an exit
Identify door as a not exit door
7.109.3
52
Exit dischar a from P -Stair 2 is deficient
Take exit designations off stair
53
Exit discharge from P -Stair 3 is deficient
53.1 Remove doors to provide line of sight
to exit
53.2 Add exit door in Doctor's Lounge
53.3 Add new double egress doors to
extend smoke zone 1D
54
Exit discharge from MB -Stair 1 is deficient
54.1 Move stair doo r to corridor
54.2 Move door to Mech. Room to corridor
54.3 Upgrade walls to 2hr and add stencil
QIw
I
LIFE SAFETY PLAN LEGEND
1 HR FIRE BARRIER,,,,...
=- ��aN = =�
1 HR SMOKE BARRIER
EXIT
1 HR FIRE BARRIER /SHAFT WALL
+—••— __.
2 HR FIRE BARRIER
J
N
2 HR FSMOKE BARRIER
EXT. DR. /.2
2 HR BARRIER /SHAFT WALL
240
4 HR FIRE BARRIER
B
SMOKE PARTITION (NON RATED)
48"
NON RATED
240 SF
EXIT ACCESS CORRIDOR
/
EXIT PASSAGE
480
2 HOUR
D
SUITE ROOMS
84"
PERIMETER
INSTITUTIONAL
EXT. DR. /.2
OCCUPANCY
480
BUSINESS
F
OCCUPANCY
84"
480
+
++ +
ASSEMBLY
++
+
OCCUPANCY
+r +
AREA UNDER
r/
CONSTRUCTION
48"
SMOKE
300 SF
COMPARTMENT
EXT. DR. /.2
WALL
210
EXIT
►
EXIT SIGN - HATCH
60"
INDICATES EXIT TEXT
® ® �y
AND ARROW
H
INDICATES DIRECTION
210
FIRE DEPARTMENT
FIDC
CONNECTION
84"
480
FEC
FIRE EXTINGUISHER CABINET
EXT. DR. /,2
70"
FE
FIRE EXTINGUISHER
EXIT CAPACITY AVAILABLE
PULL STATION
EXIT CAPACITY REQUIRED
STROBE LIGHT / HORN
'-
TOTAL TRAVEL DISTANCE
200' -0"
TO AN EXIT
TRAVEL DISTANCE TO
ADJACENT
200' -0"
— —
SMOKE ZONE
A �
1
PROJECT INFORMATION
i
PROJECT NAME: BAPTIST HEALTH SOUTH MIAMI HOSPITAL
FIFE SAFETY SURVEY
ADDRE53: 6200 SW 73 STREET. SOUTH MIAMI FL 33143
PROPOSED USE: LIFE SAFETY SURVEY
OWNER- CONTACT PERSON: LUIS FERNANDEZ DE CASTRO
PHONE: 786- 6624660
APPLICABLE CODES
- BUILDING CODE: 2007 FLORIDA BUILDING CODE W /2009
SUPPLEMENTS AND AJA GUIDELINES FOR
DESIGN AND CONSTRUCTION OF HOSPITALS
AND HEALTHCARE FACILITIES -2006 EDITION
-FIRE CODE: 2006 NFPA 1, UNIFORM FIRE CODE /
FLORIDA FIRE PREVENTION CODE 2007
-LIFE SAFETY CODE: NPFA 101 - LIFE SAFETY CODE 2006
- ACCESIBILITY CODE: 2007 FLORIDA BUILDING CODE W/2009
SUPPLEMENTS - CH.11
-STATE FIRE MARSHALL'S RULE 6943.012 FAC:
NFPA 10 -2002. STANDARD FOR PORTABLE
FIRE EXTINGUISHERS
NFPA 13 -2002, STANDARD FOR THE
INSTALLATION OF SPRINKLER SYSTEMS
NFPA 72 -2002, NATIONAL FIRE ALARM
CODE
NFPA 80 -1999 STANDARD FOR FIRE
DOORS AND FIRE WINDOWS
NFPA 99 -2005. STANDARD FOR HEALTH-
CARE FACILITIES
NFPA 105 -2003 SMOKE CONTROL DOOR
ASSEMBLIES
NFPA 221 -2006 STANDARD ON FIRE
WALLS AND FIRE BARRIER WALLS
BUILDING PLANNING
OCCUPANCY: INSTITUTIONAL GROUP 1 (F8C 2006)
MIXED OCCUPANCY? YES / NO
REQUIRED FIRE SEPARATION: 1 HR
TYPE OF CONSTRUCTION
CONSTRUCTION TYPE: FBC TYPE IB - NFPA 220
- TYPE II (2 -2 -2)
SMOKE COMPARTMENT SUMMARY
EXITING SUMMARY
SMOKE
COMPARTMENT
EXIT
TYPE /FACTOR
WIDTH IN
INCHES
PROVIDED
CAPACITY IN
PERSONS
J
N
A
EXT. DR. /.2
48"
240
60
B
EXT. DR. /.2
48"
240
240 SF
C
EXT. DR. /.2
84"
480
3,758
9,209
D
EXT. DR. /.2
84"
480
E
EXT. DR. /.2
84"
480
8
11
93
F
EXT. DR./.2
84"
480
KITCHEN
DINING
SUB -TOTAL
G
EXT. DR. /.2
60"
300
566
H
EXT. DR. /.2
48"
240
300 SF
1
EXT. DR. /.2
42"
210
8,440
J
EXT. DR. /.2
60"
300
TREATMENT
K
EXT. DR. /.2
42"
210
11
L
EXT. DR. /.2
84"
480
M
EXT. DR. /,2
70"
350
24
EXIT CAPACITY AVAILABLE
4,490
EXIT CAPACITY REQUIRED
T 1,309
240 SF
A �
1
PROJECT INFORMATION
i
PROJECT NAME: BAPTIST HEALTH SOUTH MIAMI HOSPITAL
FIFE SAFETY SURVEY
ADDRE53: 6200 SW 73 STREET. SOUTH MIAMI FL 33143
PROPOSED USE: LIFE SAFETY SURVEY
OWNER- CONTACT PERSON: LUIS FERNANDEZ DE CASTRO
PHONE: 786- 6624660
APPLICABLE CODES
- BUILDING CODE: 2007 FLORIDA BUILDING CODE W /2009
SUPPLEMENTS AND AJA GUIDELINES FOR
DESIGN AND CONSTRUCTION OF HOSPITALS
AND HEALTHCARE FACILITIES -2006 EDITION
-FIRE CODE: 2006 NFPA 1, UNIFORM FIRE CODE /
FLORIDA FIRE PREVENTION CODE 2007
-LIFE SAFETY CODE: NPFA 101 - LIFE SAFETY CODE 2006
- ACCESIBILITY CODE: 2007 FLORIDA BUILDING CODE W/2009
SUPPLEMENTS - CH.11
-STATE FIRE MARSHALL'S RULE 6943.012 FAC:
NFPA 10 -2002. STANDARD FOR PORTABLE
FIRE EXTINGUISHERS
NFPA 13 -2002, STANDARD FOR THE
INSTALLATION OF SPRINKLER SYSTEMS
NFPA 72 -2002, NATIONAL FIRE ALARM
CODE
NFPA 80 -1999 STANDARD FOR FIRE
DOORS AND FIRE WINDOWS
NFPA 99 -2005. STANDARD FOR HEALTH-
CARE FACILITIES
NFPA 105 -2003 SMOKE CONTROL DOOR
ASSEMBLIES
NFPA 221 -2006 STANDARD ON FIRE
WALLS AND FIRE BARRIER WALLS
BUILDING PLANNING
OCCUPANCY: INSTITUTIONAL GROUP 1 (F8C 2006)
MIXED OCCUPANCY? YES / NO
REQUIRED FIRE SEPARATION: 1 HR
TYPE OF CONSTRUCTION
CONSTRUCTION TYPE: FBC TYPE IB - NFPA 220
- TYPE II (2 -2 -2)
SMOKE COMPARTMENT SUMMARY
w
SMOKE
COMPARTMENT
PRIMARY
USE
AREA
SF
OCCUPANT
LOAD FACTOR
PER PERSON
OCCUPANT
LOAD
J
N
1A
TREATMENT
14,265
240 SF
60
a•
18
TREATMENT
15,215
240 SF
64
1C
ASSEMBLY
BUSINESS
SUB -TOTAL
3,758
9,209
15 SF
100 SF
250
92
12,967
342
1D
TREATMENT
STORAGE
BUSINESS
SUB -TOTAL
1,995
3,343
9,340
240 5F
300 SF
100 SF
8
11
93
14,676
112
1E
KITCHEN
DINING
SUB -TOTAL
9,503
5,707
200 SF
11 SF
48
518
15,210
566
IF
MECH. EQ.
5,330
300 SF
18
1G
TREATMENT
8,440
240 SF
35
iH
TREATMENT
5.905
240 SF
25
11
TREATMENT
7,195
240 SF
30
1J
TREATMENT
5,585
240 SF
24
1K
TREATMENT
7,775
240 SF
33
TOTAL- FIRST LEVEL
112.565
1,309
PARTIAL FIRST FLOOR LIFE SAFETY PLAN
1/16" = 1'-0"
0 4' W 16' 32, 48' 64' 80'
9 1 "M
GRAPHIC SCALE 1/16" -1' -0'
9) 2011 HKS, INC.
Zh
R
HI<S
ARCHITECT
HKS ARCHITECTS, INC.
#AA F000119
1221 BRICKELL AVENUE, SUITE 1220
MIAMI, FL 33131
305 -416 -6100
r1 M
O �
M
M
O
CIS
Q, �
KEYPLAN
cq p q 9
°>
923990�,
REVISION
HKS PROJECT NUMBER
14296.000
DATE
04.12.2011
ISSUE
STATEMENT OF
CONDITION/LIFE
SAFETY STUDY
SHEET TITLE
PARTIAL FIRST FLOOR
LIFE SAFETY
PLAN
SHEET NO.
LS -11
V Vk:
4�-4^a r�.lJY p
�t 9 � T