13-62-004EXCEPT WHERE MODIFIED BY PROPOSED WORK, EXISTING LIFE SAFETY
INFORMATION CONTAINED HEREIN INCLUDING BUT NOT LIMITED TO:
WALL RATINGS, EXIT SIGN LOCATIONS, EXIT CALCULATIONS, EXIT
CAPACITY, AND BUILDING TYPE WAS OBTAINED FROM EXISTING
DRAWINGS PROVIDED BY THE OWNER. CONTRACTOR SHALL NOTIFY A/E
IF EXISTING CONDITIONS ENCOUNTERED DO NOT CONCUR WITH
INFORMATION DEPICTED ON DRAWINGS.
CODE INFORMATION
GENERAL DESCRIPTION
A. APPLICABLE CODES:
1. FLORIDA BUILDING CODE - 2010
2. FLORIDA EXISTING BUILDING CODE - 2010 EDITION ALTERATIONS: LEVEL 2
3. FLORIDA FIRE PREVENTION CODE - 2010 EDITION.
4. 2010 NATIONAL ELECTRICAL CODE
5. FLORIDA ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION
BUILDING CLASSIFICATION:
B.
1. OCCUPANCY TYPE:
GROUP 1 -2, INSTITUTION
II. TYPES OF CONSTRUCTION - FIRE RESISTANCE REQUIREMENTS
A. REQUIRED WIDTH OF OPENINGS FBC SECTION 1005.1 -REFER TO LIFE
SAFETY ANALYSIS, REQUIRED EGRESS CAPACITY
B. EXIT ACCESS TRAVEL DISTANCE - 250' (FBC TABLE 1016.1) IN FULLY
SPRINKLERED FACILITIES
C. EGRESS WIDTH - INCHES /PERSON (FBC 1005.1, NFPA TABLE 7.3.3.1)
STAIRS - 0.3
OTHER - 0.20
D. MINIMUM CORRIDOR WIDTH REQUIRED = 44" (FBC SECTION 1018.2)
E. MINIMUM DISTANCE BETWEEN REQUIRED EXITS = 1/3 DIAGONAL (FBC
SECTION 1015.2.1)
F MINIMUM NUMBER OF EXITS FOR ASSEMBLY OCCUPANT LOAD = 1 WITH
MAX. OCCUPANT LOAD OF 49 (FBC 1015.1)
G. MAXIMUM COMMON PATH = 75' (NFPA TABLE A7.6 - 1014.3)
H, DEAD END CONDITION = 20 FT IN FULLY SPRINKLERED FACILITIES (1018.4)
LEVEL OF PROTECTION OF MEANS OF EGRESS SHALL NOT BE REDUCED
UNTIL ARRIVAL AT EXIT DISCHARGE - 1018.6
J. WOOD USED FOR FRAMING AND MILLWORK SHALL BE FIRE - RETARDANT
TREATED
FIRE PROTECTION SYSTEMS
FULLY AUTOMATIC SPRINKLER SYSTEM PROVIDED THROUGHOUT EXISTING
BUILDING
1. FIRE EXTINGUISHERS: PROVIDED AT 75' -0" MAX. PATH OF TRAVEL FROM
ANY POINT IN THE SPACE.
2. FIRE ALARM SYSTEM PROVIDED
NOTE:
1. SPACE IS FULLY SPRINKLERED WITH AN EXISTING SYSTEM
1 LIFE ! SAFETY PLAN 4 0 4 8
A0.02 SCALE: 1/8 " =1' -0"
SCALE: 1/8"=V-0"
LIFE SAFETY ANALYSIS
FLORIDA BUILDING CODE EGRESS REQUIREMENTS
OCCUPANCY
MAXIMUM DISTANCE
COMMON PATH OF
REQUIRED EGRESS
MIN CLEAR OP'G
REQUIRED MIN,
PROVIDED
CLASSIFICATION
TO TRAVEL EXIT (FT.)
EGRESS TRAVEL
CAPACITY
OF EXIT DOORS
NUMBER OF EXITS
EXITS
FOOD PREP= 6
REQUIRED
1014.3
SECTION 1005
TABLE SECTION
TABLE 1021.1
TABLE 1016.1
N
CAFETERIA
Not to Scale
1008.1.1
OR AS MODIFIED
Architects Project Number
FOR PERMIT
11/13/2012
Drawing Issue
REVISIONS
BY 1015.1- 1021.2
DESCRIPTION
ASSEMBLY
250
75' UNSPRINKLERED
414 x 0.2= 83"
32" - MINIMUM
2 (1 -500 OCC)
2
A -2
SPRINKLERED
100' SPRINKLERED
REQUIRED WIDTH
42" CLEAR DOOR WIDTH
68" CLEAR DOOR WIDTH
110" TOTAL PROVIDED
OCCUPANT LOAD
AREA (S.F.)
OCCUPANT FACTOR
OCCUPANT LOAD
TOTAL OCCUPANT
LOAD
DINING =2747 SF
DINING = 15 PER
DINING= 183
SERVERY= 1562 SF
SERVERY= 7 PER
SERVERY= 223
414
FOOD PREP= 573 SF
FOOD PREP= 100 PER
FOOD PREP= 6
GRIDDLE ROOM= 194 SF
GRIDDLE ROOM= 100 PER
GRIDDLE ROOM= 2
LIFE SAFETY LEGEND
EXISTING PARTITION TO REMAIN KITCHEN AREA
NEW PARTITION. SEE WALL TYPE /
/ SERVERY AREA
EXISTING NOT IN THE SCOPE OF WORK
1 HR. SMOKE BARRIER DINING AREA
SMOKE PARTITION ® EXIT LIGHT. SEE ELECTRICAL DWGS.
TRAVEL DISTANCE
EMERGENCY LIGHT. SEE ELECTRICAL DWGS.
MILLWORK F FIRE ALARM HORN /STROBE COMBINATION. SEE
.. ............................... � ELECTRICAL DWGS.
— — — — — EQUIPMENT LINE
FIRE ALARM PULL STATION
OCCUPANT LOAD /CAPACITY OF EXIT F E
EXISTING WALL MOUNTED FIRE EXTINGUISHER
NOTE: 0S
G.C. TO FURNISH AND INSTALL NEW RECESSED STAINLESS STEEL CABINETS FOR
EXISTING EXTINGUISHERS
WALL MOUNTED STROBE LIGHT
SOUTH MIAMI HOSPITAL-.
SUNSET CAFE
CAFETERIA RENOVATION
6200 S.W. 73rd STREET
MIAMI, FL 33143
Owner
General Contractor
IDADALY INGEKN0Ek�rNGE
EST. 1915
3390 Mary Street, Suite 216
Miami Florida 33133 USA
T: 305.461 .9480 F: 305.461 .3686
Architect
Associate Architect
ww
N
CAFETERIA
Not to Scale
__
061 - 10064 -020
Architects Project Number
FOR PERMIT
11/13/2012
Drawing Issue
REVISIONS
NO.
DESCRIPTION
DATE
LEO A DALY COMPANY Copyright 2012
� 1w
/ � A
p-
C � y Rf, ':•C �
C •-T-'I
SERGIO PENDAS, AIA
REGISTERED ARCHITECT
AR 0013943
Seal
LIFE SAFETY
Sheet Title
A00`02