13-62 (2)-012---------------
AHU-2
L ----------------
r_______ __ ___________ ______-1 (9__1
----------
4 I 1 i [----Al-U-7 (DIA7)
AH1-5 INSTALLED ABOVE
��...-AHU-10 (DIA8)
INSTALLED BELLOW(�)
r--------- 7'-111
L----------------------------- II 11
(D EXISTING AHU-7 AND AHU-10 DISCONNECTS AND ASSOCIATED FEEDERS TO BE
REMOVED. REMOVE CONDUIT AND WIRING BACK TO EXISTING PANEL SERVING UNITS
AND LEAVE TWO BREAKERS AS "SPARE" FOR FUTURE USE BY OTHERS.
G EXISTING CONTROL PANELS TO BE REMOVED.
EXISTING AHU-7 AND AHU-10 BELOW TO BE REMOVED. SEE MECHANICAL DRAWINGS.
EXISTING AHU-2 AND AHU-5 TO REMAIN.
(D EXISTING AHU-7 AND AHU-10 FIRE ALARM DUCT SMOKE DETECTORS TO BE REMOVED.
NEW WORK
SCALE: 1/4" =1*-0*
NEW WORK NOTES:
(D NEW AHU-7A FEEDER TO RUN ABOVE CEILING UP TO EXISTING PANEL 'IEQHZ"
LOCATED IN 'ESSENTIAL LOADS" ELECTRICAL ROOM. ELECTRICAL CONTRACTOR TO
COORDINATE EXACT ROUTING AT FIELD BASED • EXISTING CONDITIONS. SEE PANEL
SCHEDULE.
NEW VFD FOR AHU-7A TO BE PROVIDED. SEE MECHANICAL DRAWINGS.
NEW AHU-7A
• REPLACE AHU-7 AND AHU-1 0.
NEW DDC CONTROL PANEL TO REPLACE EXISTING CONTROL SYSTEM. PROVIDE. A
NEW DUPLEX RECEPTACLE SERVED OUT OF EXISTING CONTROL SYSTEM PANEL TO
SERVE NEW PANEL. COORDINATE EXACT LOCATION/CONDITIONS AT FIELD.
NEW DUCT DETECTORS TO BE PROVIDED IN COORDINATION WITH MECHANICAL
CONTRACTOR FOR NEW AHU-7A. NEW DEVICES SHALL BE FULLY COMPATIBLE WITI`J
EXISTING HOSPITAL FIRE ALARM SYSTEM.
PROVIDE NEW AHU SHUT-DOWN RELAY.
III m n w Ili= WMEOW
SCALE: 1/4"=V-0"
SOUTHIMIAMI HOSPITAL
SUNSET NSET CAFE
CAFiTEK(A -RENOVATION
6200 -C W. -73rd STREET
KMAid, FL 33143
VLANNtNG
ARCHITECTURE
E N G I N E C R I N G
A r) Ad LY INTERIORS
EST, 19B
3390 Mary Street, Suite 216
Miami Florida 33133 USA
T: 305.461.9480 F: 305.4613686
Architect
Associate Architect
2
WFO-6-1-10 064-020
Jfffff. Architects Project Number
IBM
SEZIMM
REVISIONS
I DESCRIPTION
FAVIAHU REPLACEMENT
FAW
Im
•
ENLARGED
MECHANICAL ROOM
RI ` A
�I�J----------
Sheet Number`"'_, ._..
160
•
ENLARGED
MECHANICAL ROOM
RI ` A
�I�J----------
Sheet Number`"'_, ._..