Loading...
13-62 (2)-009System No. C -AJ -1226 F Rating — 3 Hr T Rating — 0 Hr L Rating At Ambient — Less Than 1 CFM /Sq Ft L Rating At 400 F — 4 CFM /Sq Ft A SECTION A-A 1 1. Floor or Wall Assembly — Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pco concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diarn of opening is 32 in. 2. Metallic Sleeve — (Optional) Norn 32 in. diarn (or smaller) Schedule 40 (or heavier) steel sleeve cast or grouted into floor or wall assembly, flush with floor or wall surfaces or extending a max of 3 in. above floor or beyond both surfaces of square 3. Sheet Metal Sleeve — (Optional) Max 6 in. diam, min 26 ga gaiv steel provided with a 26 ga gaiv steel square flanqe spot welded to the sleeve at approx mid-height, or flush with bottom of sleeve in floors, and sized to be a min of 2 in. larger than the sleeve diam, The sleeve is to be cast in place and may extend a max of 4 in. below the bottom of the deck and a max of 1 in. above the top surface of the concrete floor. 4. Sheet Metal Sleeve — (Optional) - Max 12 in. diam, min 24 ga gaiv steel provided with a 24 ga galv steel g e spot welded to the sleeve at .r• • mid-height, or flush with bottom of oo and sized to be a min of 2 in, larger than the sleeve diam. The sleeve is to be cast in place and may extend a max of 4 in. below the bottom of the deck and a max of I in, above the top surface of the concrete floor. 5. Through-Penetrant — One metallic pipe, tube or conduit to be installed either concentrically or eccentrically within the firestop system. The annular space between penetrant and periphery of opening shall be min 1 (point contact) to max 1-7/8 in. Penetrant may be installed with continuous point contact. Penetrant to be rigidly pport • on both sides of • • or - # The following • - s sizes of penetrants • - used: A. Steel Pipe — Norn 30 in. . . -. ti . pipe. B. Iron Pipe — Nom 30 in. diarn (or smaller) cast or ductile iron pipe. C. Copper Pipe — Norn 6 in. diarn (or smaller) Regular (or heavier) copper pipe. D. Copper Tubing — Nom 6 in. diarn (or smaller) Type L (or heavier) copper tubing. E. • iuit — Nom • in. f (or smaller) steel conduit. Conduit — • 4 in. ! # tubing 6. Firestop System — The firestop system shall consist of the following: A. Packing Material — Min 4 in. thickness of min 4 pcf mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or sleeve or from both surfaces of wall or sleeve as required to accommodate the required thickness of concrete B. Fill, Void or Cavity Material* — Sealant — Min 1/4 in. thickness of fill material applied within the annulus, flush with top surface of floor or sleeve or with both surfaces of wall or sleeve. At the point or continuous contact locations between penetrant and concrete or sleeve, a min 1/4 in. diam bead of fill material shall be applied at the or pipe pe on #s surface of rr and on both surfaces of CONSTRUCTION HILTI DIV O FS-One Sealant *Bearing Classification Mark 1 Reproduced by HILTI, Inc. Courtesy of Underwriters Laboratories, Inc. nRESTOP SYSMEMS June 27, 2007 r DR FDS IDULET (THREADLESS FOR D THICK WALL IDUIT +II N.T.S. NOTE: TO BE USED IN SERVING LINE AREA. System No. W -L -1054 F Ratings -1 and 2 Hr (See Items 1 and 3) T Rating - 0 Hr L Rating At Ambient - Less Than 1 CFIl Ft L Rating At 400 F - 4 CFM /Sq Ft SECTION A-A 1. Wall Assembly – The 1 or 2 hr fire -rated gypsum wallboard /stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300 or 0400 Series Wall and Partition Designs in the UL Fire Resistance Directory Z Through- Penetrants – One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. The annular space shall be min 0 in. to max 2 -1/4 in. Pipe may be installed with continuous point contact. Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular. Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe – Nom 30 in diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe – Nam 30 in. diam (or smaller) cast or ductile iron pipe. C. Conduit – Nom 4 in diam (or smaller) steel electrical metallic tubing or 6 in. diam steel conduit. D. Copper Tubing – Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing. E. Copper Pipe – Nom 6 in. diam (or smaller) regular (or heavier) copper pipe. F. Fill, Void or Cavity Material* – Sealant -- Min 5/8 in. thickness of fill material applied within the annulus, flush with both surfaces of wall. At the point or continuous contact locations between pipe and wall, a min 1/2 in. diam bead of fill material shall be applied at the pipe wall interface on both surfaces of wall. HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC – FS -One Sealant *Bearing the UL Classification Mark CONCRETE SLAB PIPE PLUG SLOTTED BRASS IFINISH FLOOR EXPANSION JOINT MATERIAL CONDUIT EXPANSION FITTING FO-Z CO. TYPE °AX- BONDING JUMPER O -Z CO. TYPE 'AJ" EXPANSION FITTING DETAIL. 1. PROVIDE ELECTRONIC BALLAST AND IN-LINE FUSES FOR ALL FLOURESCENT FIXTURES. i • iF ' • Relay • Powerpock • Wall Switch Normal Line j ' Normal Lighting _ r—a Normal Neutral "Sensing" Line Emergency Line Emergency Neutral "Switching" Line Normal LIGHTING FIXTURE S C H E D U L E Normal. Neutral (WHITE 18AWG) Normal Power Sense LAMPS FIXTURE TYPE MANUFACTURER & CATALOG No. MOUNTING (OR APPROVED EQUIVALENT) NO. TYPE WATTS SERVICE TOTAL VOLTS WATTS BDL A PENDANT 2 CF26 35K 26 UNV 54 DB L -AC-W H -2C -277 -1.8K LIGHTING ARTISTRY B PENDANT 1 676.35 T4 35 120 35 ET-MINX LIGHTING ARTISTRY C PENDANT 1 CF32 835 32 120 32 TL- 422- 700- TD-DLN P W- NS -CF277 DELTA D SURFACE 4 WW LED 4.2 120 16.8 6 275 07 24 277 INFINITY E RECESSED 2 CF26 35K 26 UNIV 54 P H60 -226 Q E B 2 -CS -U NV -M W T FINELITE F024T5H0 F GRID 2 24 120 48 H P R -A- 2X2- DC- 2T5HO- 277V -S C-C1 -I S 835 HE WILLIAMS G 50GS24- 332SA12125- G3- EB3 -UNV- GRID 3 F032T8 835 28 UNIV 84 F338 -LP835 LEUCOS USA GU-5.3 H RECESSED 1 N 50 INC 50 SD-88 BEGHELLI X UNIVERSAL LED 4 UNIV INC VA4RSA BEGHELLI XE RECESSED LED 4 UNIV INC OL2- SA- LR- 1 /2 -MCR 1. PROVIDE ELECTRONIC BALLAST AND IN-LINE FUSES FOR ALL FLOURESCENT FIXTURES. i • iF ' • Relay • Powerpock • Wall Switch Normal Line j ' Normal Lighting _ r—a Normal Neutral "Sensing" Line Emergency Line Emergency Neutral wolf # METAL GALVANIZED HOUSING / CIR.# t } Q _r r® ¢w claw PUSH '3;:: TO TEST 0r } ®� 0 a° W U Z W Emergency Lighting Control 11 Typical Wiring MW i ...ate )ITI H_MI/ EMI HOSPITAL w . Sup !!SET CAFE CAFETERI RENOVATION _ 6�OQ S`wW- '73rd STREET MIAMI, FL 33143 3390 Mary Street, Suite 216 Miami Florida 33133 USA T: 305.461.9480 F: 305.461.3686 Associate Architect 061 -10064 -020 Architects Project Number FUEL F'FFZMI I 11 /1 qoni 9 DATE 04.24.13 LIGHTING FIXTURE � SCHEDULE • r DETAILS ELECTRICAL Atoll "Switching" Line Normal Switched Sense (RED 18AWG) Normal. Neutral (WHITE 18AWG) Normal Power Sense wolf # METAL GALVANIZED HOUSING / CIR.# t } Q _r r® ¢w claw PUSH '3;:: TO TEST 0r } ®� 0 a° W U Z W Emergency Lighting Control 11 Typical Wiring MW i ...ate )ITI H_MI/ EMI HOSPITAL w . Sup !!SET CAFE CAFETERI RENOVATION _ 6�OQ S`wW- '73rd STREET MIAMI, FL 33143 3390 Mary Street, Suite 216 Miami Florida 33133 USA T: 305.461.9480 F: 305.461.3686 Associate Architect 061 -10064 -020 Architects Project Number FUEL F'FFZMI I 11 /1 qoni 9 DATE 04.24.13 LIGHTING FIXTURE � SCHEDULE • r DETAILS ELECTRICAL Atoll