13-501-008NEW COMBINATION FIRE/SMOKE , DETAIL 1" MINIMUM OPENING OVERLAP ON SIDES OF DAMPER. DUCT OPERATOR /ACTUATOR — (MAY BE REQUIRED TO BE OUT OF AIR STREAM). AUXILIARY OPERATING — JACK SHAFT. FUSIB E LINK WITH LOCK. (2857 MIN. MIN. 16 GAUGE) FIRE RATED CONCRETE BLOCK WALL AS REQUIRED. FUSIBLE ROD DAMPER >ii: NEGATOR SPRING MANUFACTURER: GREENHECK FSD -311 SUP JOINT, SLEEVE TO DUCT OR RIGID CONNECTION PER SMACNA CAULK BETWEEN WALL AND IUONG /A2NGLES /2x14 GA) ANGLE ALSO WHERE ANGLES MON. (FIRE RATED GYPSUM WALL--------' ALL 6" MAX. BOARD AS REQUIRED. OPERATION: A . FIRE DAMPER MODE: HIGH TEMPATURE MELTS FUSIBLE LINK, CLOSING FIRE DAMPER. B. SMOKE DAMPER MODE SMOKE DETECTOR UPON SENSING HEAT /SMOKE ACTUATES DAMPER MOTOR TO CLOSE DAMPER. C. RELAYS: ACTIVATED BY THE FIRE ALARM SYSTEM, TO SHUT DOWN H.VA.C. SYSTEM AND CLOSE FIRE /SMOKE DAMPERS. D. SHUT DOWN OF H.V.A.C. SYSTEM TO INITIATE CLOSING OF FIRE /SMOKE DAMPERS. NOTES: 1. A VERTICAL DAMPER IS SHOWN. HORIZONTAL DAMPER INSTALLATION IS SIMILAR. FOLLOW DAMPER MANUFACTURER'S INSTRUCTIONS, INCLUDING FASTENER OPTIONS AND GAGES FOR SLEEVE AND PERIMETER ANGLES. FIRE DAMPERS MUST BE INSTALLED IN THE PARTITION OR FLOOR, NOT OUTSIDE THE PARTITION. 2. GALVANIZED SLEEVE: SLEEVE NOT LESS THAN 16 GAAGE, FASTEN SLEEVE TO PERIMETER ANGLES ONLY. 3. PERIMETER ANGLES: GALVANIZED STEEL, NOT LESS THAN 1- 1/2 "x1 -1/2 "x14 GAGE, TO PROVIDE 1 INCH MINIMUM OVERLAP OF OPENING ON ALL 4 SIDES. CAULK PERIMETER ANGLES AT PARTITION. 4. BREAKAWAY DUCT CONNECTION: CONTRACTOR'S OPTION OF TYPES PER SMACNA OR MFGRS. INSTRUCTIONS. 5. ACCESS PANELS: SIZE AND LOCATION TO PERMIT SERVICING THE FUSIBLE UNK OR LINKS. 6. PROVIDE 1/8" PER FOOT CLEARANCE ON HEIGHT AND WIDTH. 7. DAMPER MUST BE WITHIN THE PLANE OF THE PARTITION, DAMPER MAY BE A MAXIMUM OF 12" OUTSIDE OF THE PARTITION, IF INSTALLED IN A 10 GAUGE SLEEVE. 8. DAMPER AND SLEEVE SHALL BE UL USTED AS AN ASSEMBLY. NOTES FOR WHEN USING COMBINATION FIRE /SMOKE DAMPERS FOR TRANSFER DUCTS IN FIRE RATED PARTITIONS: 1. PROVIDE 1/2" CLEARANCE AT TOP AND ONE SIDE OF OPENING FOR DAMPER EXPANSION. 2. RETAINING ANGLES SHALL BE 1 1/2" x 1 1/2" x1/8" STEEL ANGLES SECURED TO SLEEVE WITH 1/2" WELDS 6" O.C. DO NOT SECURE ANGLES TO PARTITION/WALL ASSEMBLY. PROVIDE RETAINING ANGLES ON ALL THREE SIDES OF SLEEVE, BOTH SIDES OF PARTITION /WALL ASSEMBLY. 3. TRANSFER DUCT IS TO BE PROVIDED WITH TRANSFER GRILLES AT EACH SIDE OF PARTITION WALL 4. TRANSFER DUCT IS TO PROTRUDE SUFFICIENTLY OFF THE WALL TO ALLOW PROPER DAMPER CLOSURE. 2 4 1 !. 71 M ;` Q PRE -RATED CONCRETE FLOORS OR BLOCK WALLS= MIN 3" THICK CONCRETE FLOOR ASSEMBLY MIN 3 -1/2" THICK CONCRETE WALL ASSEMBLIES. 2� METALUC PIPE. A) STEEL PIPE- 8 "DIAM (OR SMALLER) SCH. 40(OR HEAVIER) STEEL PIPE B) IRON PIPE - 8"DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE. C) CONDUIT- 4 "DIAM ( OR SMALLER) STEEL EMT OR CONDUIT D) COPPER TUBING - 4"DIAM ( OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING E) COPPER PIPE- DIAM (OR SMALLER) REGULAR ( OR HEAVIER) COPPER PIPE THE ANNULAR SPACE SHALL BE MIN 1/2" TO MAX 7/8" a PACKING MATERIAL- MIN 2 -1/2" THICKNESS OF MINERAL WOOL (MIN. 4.0 PCF) INSULATION, FIRMLY PACKED INTO THE OPENING AS PERMANENT FORM. 4� FYRE- SHIELD - MIN 1/2" THICKNESS OF SEALANT APPLIED WITHIN ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR BOTH SURFACES OF WALL ASSEMBLY. THROUGH PENETRATION FIRESTOPPING UL -1479 2 HOUR FIRE RATED PENETRATION FIRESTOP FOR SINGLE METAL PIPE DETAIL NOT TO SCALE M-4 TYPE SQUARED NQOD (EXIST.) MAIN BUS 60A M.CB. VOLTAGE MOUNTING SAFETY PANEL 1207208V, PH, 4W SURFACE FED FROM LSH1 "LSL 1 I LOCA11ON 1ST FLOOR ELEC. ROOM THRU T -LS1 VOLT AMP POLE TRIP CON DUIT WIRE REMARKS CKT. NO. R r> n CKT. NO. REMARKS WIRE CON DUIT TRIP POLE VOLT AMP 1 20 w LIGHTING CONTACTOR 1 Q 2 ELEV 71 CAB LIGHT i4 20 ON Z 1 1 20 a FIRE ALARM MECH. RM. 3 4 SPARE rn Q � 20 co r DESIGNED /DRAWN BY. A.V. CHECKED BY- F.A. SHEET No.: O 1 20 OF 7 O w � 1 ST FL AUTO DOOR 5 6 FIRE DAMPER 1ST FL. 12 1 2 20 1 194 i) (n C'l 1 20 w 1ST FL AUTO DOOR 7 8 SPARE c°a U Cn ''" w v u O 20 1 ,t A. 1 20 SPARE 9 10 PANEL 2ND FL. TEL RM. 20 1 M 1 20 ELEV. #1 SHUNT TRIP 11 12 SPACE 20 1 0 0 1 20 SPARE 13 14 SPACE 20 1 1 20 SPARE 15 16 SPACE 20 1 1 20 SPARE 17 18 SPACE 20 1 1 20 ® m SPARE 19 20 SPACE k20 1 11134 1 20 1/2'.3#12 SPARE 21 22 SPACE 20 1 1 20 SPACE 23 24 SPACE 3#12[11/2 20 1 1 TOTAL TOTAL TOTAL CONNECTED LOAD: 3 KVA* + 0.108KVA (BEING ADDED) = 3.108KVA . 1 = 8.63 AMPS 0 208V NOTES: 1� ONLY 108VA ARE BEING CONNECTED TO EXISTING CIRCUIT J6. * TOTAL CONNECTED LOAD OF PANEL "LSL1" WAS TAKEN FROM ORIGINAL BUILDING CONSTRUCTION DOCUMENTS PROVIDED BY OWNER. TYPE SQUARE D NQOD (EXIST.) MAIN BUS 60A M.CB. VOLTAGE MOUNTING SAFETY PH, 4W PANEL "LS L5 - LOCATION SURFACE FED FROM LSH5 THRU T -LS5 O 5TH FLOOR ELEC. ROOM VOLT AMP POLE TRIP CON DUIT WIRE REMARKS CKT. NO. R r> n CKT. NO. REMARKS WIRE CON DUIT TRIP POLE VOLT AMP 1 20 w LIGHTS ELEVATOR 1 Q 2 LIGHTS REC. ELEV.RM. i4 20 ON Z 20 a LIGHTS ELEVATOR 3 4 LIGHTS REC. ELEV.RM. rn Q � 20 co r DESIGNED /DRAWN BY. A.V. CHECKED BY- F.A. SHEET No.: O ME -7 20 OF 7 O w � LIGHTS ELEVATOR 5 6 LIGHTS ELEVATOR BRIDGE w c� E C'l `ACV 20 1 x to o�NC" i) (n C'l 20 w LIGHTS ELEVATOR BRIDGE 7 8 REC. TELRM. 3RD FL c°a U Cn ''" w v u O 20 1 ,t A. 1 20 REC. ELEC RM 3 -6 9 10 REC. TELRM. 3RD FL 20 1 M 20 REC. TELRM. 3RD FL 11 12 REC. TELRM. 4TH FL 20 1 0 0 1 20 REC. TELRM. 3RD FL 13 14 REC. TELRM. 4TH FL 20 1 20 REC. TELRM. 4TH FL. 15 16 REC. TELRM. 5TH FL 20 1 1 20 REC. TELRM. 4TH FL 17 18 REC. TELRM. 5TH FL 20 1 1 20 ® m REC. NAC F.A. 19 20 REC. TELRM. 6TH FL. 20 1 11134 1 20 1/2'.3#12 FIRE DAMPER 4TH FL. 21 22 REC. TELRM. 6TH FL 20 1 1 20 REC. TEL.RM. 4TH FL 23 24 FIRE DAMPER 3RD FL 3#12[11/2 20 1 1 1 20 REC. TELRM. 5TH FL. 25 26 FIRE DAMPER 6TH FL 20 1 1 20 REC. TELRM. 5TH FL 27 28 FIRE DAMPER 5TH FL 12 2' 20 1 1107 1 20 REC. TELRM. 5TH FL. 29 30 EXIST. LOAD 20 1 TOTAL TOTAL TOTAL CONNECTED LOAD: 10.8 KVA* + 0.216KVA (BEING ADDED) = 11 KVA . I = 30.6 AMPS 0 208V NOTES: 0 ONLY 27VA ARE BEING CONNECTED TO EXISTING CIRCUIT 124. ONLY 108VA ARE BEING CONNECTED TO EXISTING CIRCUIT #21. ONLY 81VA ARE BEING CONNECTED TO EXISTING CIRCUIT #28. * TOTAL CONNECTED LOAD OF PANEL "LSL5" WAS TAKEN FROM ORIGINAL BUILDING CONSTRUCTION DOCUMENTS PROVIDED BY OWNER. I c �41 a 14 Irk 0 1 a Q �. - J � r Q N R r> n � Z r0 .J Q4 Q 4 N N N s N Q W w � Q H � i4 N ON Z z a a W t/7 rn Q � q co r DESIGNED /DRAWN BY. A.V. CHECKED BY- F.A. SHEET No.: O ME -7 W OF 7 O w � w c� E C'l `ACV C:± :m x to o�NC" i) (n C'l w m cy o v o Q c°a U Cn ''" w v u O M Oa w ,t A. c � o a r w M M O O 0 0 S ® m a Qe O O Q � J � r Q W M M W � Z r0 .J __j V) J Q W w � Q H � cid ON Z _ 0 FILE: W t/7 rn Q � F•- co r DESIGNED /DRAWN BY. A.V. CHECKED BY- F.A. SHEET No.: O ME -7 W OF 7 C:± :m In i) (n O O m N Q CCU M W (� J J � Q � W W Z r0 V V) J Q J � Q H � cid Z 0 FILE: JOB NO.: 212 -1049 DATE : 04 -10 -13 PLOT SIZE: AS NOTED DESIGNED /DRAWN BY. A.V. CHECKED BY- F.A. SHEET No.: ME -7 SHEET 7 OF 7