13-1289-003LIFE SAFETY CALCULATIONS
EXIT CALCULATIONS
THIRD FLOOR
COMP'T
COMPARTMENT
AREA (S.F.)
OCP. LD.
(PERSONS)
120/240)
EXIT CAP. PROVIDED
(INCHES)
TOTAL EXIT
CAP. PROVIDED
(PERSONS)
SMOKE COMPARTMENT CALCULATIONS
SLEEPING
(120 S.F./P)
NON - SLEEPING
(240 S.F. /P)
OFFICE
(100 S.F. /P)
STAIR
LEVEL
NOTE: SHADED AREA INDICATES
SMALLEST
ADJACENT COMP'T
LIGHTED FACE
3A
10,720
'--
NOTE: SHADED AREA INDICATES
10,720 /120 = 90
44 / 0.3 = 147
42 / 0.2 = 210
357
30
8,803
2,632
1,940
4,603 / 120 = 73
2,6321240 = 11
1,940 /100 =19
88 / 0.3 = 253
128 / 0.2 = 640
533
COMPARTMENT
AREA (S.F.)
OCCUPANT
LOAD
(PERSONS)
ADJACENT
SMOKE
COMP'T
NO. OF
OCCUPANTS
REFUGE
AREA
3C
----
10,12
10,124 / 240 = 42
44 / 0.3 = 147
168 10.2 = 840
987
3D
11,380
_ °�
COMBINATION STAFF/ DUTY STATION
11.340 / 120 = 95
44 / 0.3 = 147
94 / 0.2 = 420
567
COMP'T
SLEEPING
(120 S.F. /P)
NON SLEEPING
(240 S.F. /P
OFFICE
(100 S.F. /P)
COMP'T
AREA
(S.F.)
SLEEPING
(30 S.F. /P )
NON- SLEEPING
(g S.F. /P)
3E
12,440
MGAP
MEDICAL GAS ALARM PANEL
12,440 /120 - 104
44 / 0.3 = 147
84 If 0.2 = 420
567
3A
10,720
(ti)
'- --
10,720 / 120 = 90
3e
3e
13,375
13,375 / 30 =446
---
COMPLIES
3F
9,080
- - -"'
9,080 1120 = 76
__-
84 IF 0.2 = 420
420
3d
8,803
2,32
1,940
6,603/120w73
2,:32 / 240 =11
1 940 / 100 =1!
3A, 3D
3A
10,834
10,634130 361
---
COMPLIES
3G
3,030
- - --
I
3,030 1 120 = 25
- ----
42 / 0.2 = 210
210
3C
--
-- --
10,126
10,126/240 =42
30
3D
11,380
11,360/30 =379
COMPLIES
_ii1 -__
_l.�
3D
11,380
-----
- - --
11.360 / 120 = 95
38, 3C, 3E,
3F, 3G
3G
3,030
3,030 r 30 =101
----
COMPLIES
3E
12,440
-
- - --
12,440 / 120 =104
3D, 3F
3F
9.060
9,040 / 30.302
""
COMPLIES
3F
5,080
-----
- - --
9,060 1120 = 76
3D, 3E, 3G
3G
3,030
3,030 If 30 =101
-----
COMPLIES
3G
3,030
-----
- - --
3,030 /120.26
3D, 3F
3F
5,060
9,060/30 =302
-
COMPLIES
TOTAL EXIT CAPACITY (PERSONS) 535 IS LESS THAN 4041
SYMBOL LEGEND
- -
ONE HOUR FIRE RATED PARTITION
- 1 FS -
ONE HOUR FIRE RATED/ SMOKE PARTITION
TWO HOUR FIRE RATED PARTITION
NEW
TWO HOUR FIRE RATED/ SMOKE PARTITION
■ ■ ■ ■ ■ ■ ■ ■ ■ ■ ■
FOUR HOUR RATED/ SMOKE PARTITION
6 II
- S.Q.
EXIT LIGHT
3D
NOTE: SHADED AREA INDICATES
LIGHTED FACE
1
EXIT LIGHT (DIRECTIONAL)
NOTE: SHADED AREA INDICATES
LIGHTED FACE
FE
FIRE EXTINGUISHER
FHC
FIRE HOSE CABINET
®
FIRE ALARM RELAY
aFIRE
ALARM PULL STATION
FIRE ALARM / VISUAL CHIME
FIRE ALARM AUDIBLE SIGNAL
FIRE ALARM VISUAL SIGNAL
(�L
REMOTE LOCATOR
CODE PINK STATION
CODE BLUE STATION
I�
PULL CORD STATION
(�
I N I
COMBINATION STAFF/ DUTY STATION
eHEAT
DETECTOR
THERMOSTAT
SMOKE DETECTOR
O
FIRE SPRINKLER HEAD
44
EXIT CAPACITY
IN INCHES
II I�
�
Z
INTERSECTION ZONE LIGHT
MGAP
MEDICAL GAS ALARM PANEL
CR
CARD READER
NC
NURSE CALL MASTER STATION
�-
DOME LIGHT
(ti)
CEILING PAGING SPEAKER
II
HATCH DEPICTS AREA OF SCOPE OF WORK
1 THFID FLOOR LFE SAFETY PLAN
Ls101 SCALE: 1/16 0 = 1''-0"
• INSTITUTIONAL (FLORIDA BUILDING CODE 2010 - SECTION 309.1 GROUP 1)
APPLICABLE CODES - LATEST EDITION:
• FLORIDA BUILDING CODE (F■C) - 2010
• AIA GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPRALS AND HEALTH CARE
FACILITIES - 2006 EDITION
• FLORIDA ACCESSIBILITY CODE - FBC 2010 CHAPTER 11
• FLORIDA STATUTES - FBC CHAPTER 407 & 419
• NI 101: 2010
•
CHAPTER 19, EXISTING HEALTH CARE OCCUPANCIES
• NFPA 220: CURRENT ADDITION
• NFPA 2000 CURRENT ADDITION
BUILDING CLASSIFICATION:
• FLORIDA BUILDING CODE - TYPE I NFPA 220 - TYPE II (2 -2 -2)
INTERIM LIFE SAFETY MEASURES
(I.L.S.M.)
A. THE CONTRACTOR SHALL MAINTAIN FREE AND UNOBSTRUCTED ACCESS TO FIRE EXITS.
B. THE CONTRACTOR SHALL MAINTAIN FREE AND UNOBSTRUCTED ACCESS TO THE
EMERGENCY DEPARTMENT.
C.ENGINEERING AND SECURITY SHALL BE NOTIFIED WHEN ANY FIRE PROTECTION SYSTEM IS
DOWN.
D. TEMPORARY CONSTRUCTION, PARTITIONS SHALL BE SMOKE TIGHT AND BUILT OF
NON - COMBUSTIBLE MATERIALS. (SEE DRAWING A -8.0 X13)
E. ADDITIONAL FIRE FIGHTING EQUIPMENT SHALL BE PROVIDED AND PERSONNEL SHALL BE
TRAINED IN ITS USE.
F. CONTRACTOR SHALL CLEARLY INDICATE - SMOKING IS PROHIBITED"
G. CONTRACTOR SHALL ILLUSTRATE THE PROCEDURE FOR THE STORAGE. HOUSEKEEPING,
AND DEBRIS REMOVAL PROCEDURES TO ALL CONSTRUCTION PERSONNEL
H. CONTRACTOR SHALL CONDUIT (FIRE DEBRIS AT MINIMUM 2 PER QUARTER SHIFT.
I. CONTRACTOR SHALL PROVIDE DAILY HAZARD SURVEILLANCE OF BUILDING OR AREA OF
CONSTRUCTION .GROUNDS.SPECIFICALLY STORAGE AREAS.
J. STAFF AND CONTRACTOR SHALL INFORM ALL AFFECTED AREA PERSONNELAISK
MANAGEMENT, SECURITY AND ENGINEERING IF A COMPARTMENT FEATURE OF FIRE SAFETY
IS COMPROMISED.
K. ALL PERSONNEL INVOLVED WITH THE CONSTRUCTION MUST BE EDUCATED BY THE
GENERAL CONTRACTOR TO ENSURE AWARENESS OF ANY EXISTING LIFE SAFETY CODE(LSC)
DEFICIENCIES, CONSTRUCTION HAZARD AND THESE ILSM.
L THERE SHALL BE AN EDUCATIONAL PROGRAM CONDUCTED BY GENERAL CONTRACTOR
FOR ALL STAFF ON THE PROCEDURES IN CASE OF FIRE. NOT ONLY TO PROTECT
THEMSELVES BUT THE BUILDINGS SO THAT OTHERS WOULD BE PROTECTED.
AREA OF PROJECT
' •` II
s"I
-ice - I� ■I�.�I� - �I�...�■16�
a 91�L.r�
X19_ � 69�r�
X19_ � 9_r�
�,1ww • + /,
II
III • r ,
■
►�' �'`-
I'
' ►�''' --I
6 II
- S.Q.
�I
3D
-7 III•
III•
1
I
I
I �
►►`� ►mot ►►=1 CA Q /.1 ►�� 11:' ►►:�� ►.1
"n w w it .e - II n.� n 11 - II rp-w w••MII w� I,00m II� n..M II rw,w.n w II .-rn•r• a 11 rnwwn n II rwM+n w••w 11 r w w
AREA OF PROJECT
--A
■� r
'L7=
i
C � ■
II II
t. 0 IN I ._
Az
0
A2
C
61
i
� 0101- 1 Will
x
■
T
Ijl wlrL
I�
■
11■
r 1
i1 C I ■ ,
.. ■... -�1 _ �I !J � � � III
- � R : I i�"���r• c� r fir. y _
r
0
W&MM"immin Ell
b , ® LZ
fd� Ike; ■�:. ■AAA � ri =� � III
R w •l'
�1
P
r OT
TR
M Am I ►►
njiTr •
•
�rI1'
• C W •
%%r }
• � 4 r %/
BERMELL-Q AJAMIL & PARTNERS, INC.
Architet >ture Engineering Planning
. In+_crr!br.D &i;r' Landscape Architecture
2601 South Bayshore Drive 10th Floor
Miami, Florida 33133
(305) 559 -2050 Fax (305) 860 -3700
H SOUTH M1 M1
HOSPITAL
O N' HO
ROL
�N
6574
REVISIONS:
PROJECT NAME:
SOUTH MIAMI HOSPITAL
NORTH TOWER / NICU DOOR REPLACEMENT
PROJECT ADDRESS:
7400 S.W. 62nd Ave.
South Miami, Florida 33143
KEY PLAN
0 9
COMM. NO. 40070.000
SCALE: AS SHOVM
DATE: MAY 30, 2013
DRAWN: -
CHECKED: sH
CADD FILE: H:INSTITUTIONAL
DRAWING TITLE:
THIRD FLOOR
LIFE SAFETY
PLAN
SHEET NO.
LS1 01
III • r ,
■
►�' �'`-
I'
' ►�''' --I
6 II
- S.Q.
�I
3D
-7 III•
III•
1
11
I
I�
.I
II I�
�
Iv► • , III
II
� II •
II
II
_
-- -
OEM
41
I
• 4 r
r r
r r
LI ��
/lil•_
�
-
- -- -i®►_
°
_ii1 -__
_l.�
r
� 0101- 1 Will
x
■
T
Ijl wlrL
I�
■
11■
r 1
i1 C I ■ ,
.. ■... -�1 _ �I !J � � � III
- � R : I i�"���r• c� r fir. y _
r
0
W&MM"immin Ell
b , ® LZ
fd� Ike; ■�:. ■AAA � ri =� � III
R w •l'
�1
P
r OT
TR
M Am I ►►
njiTr •
•
�rI1'
• C W •
%%r }
• � 4 r %/
BERMELL-Q AJAMIL & PARTNERS, INC.
Architet >ture Engineering Planning
. In+_crr!br.D &i;r' Landscape Architecture
2601 South Bayshore Drive 10th Floor
Miami, Florida 33133
(305) 559 -2050 Fax (305) 860 -3700
H SOUTH M1 M1
HOSPITAL
O N' HO
ROL
�N
6574
REVISIONS:
PROJECT NAME:
SOUTH MIAMI HOSPITAL
NORTH TOWER / NICU DOOR REPLACEMENT
PROJECT ADDRESS:
7400 S.W. 62nd Ave.
South Miami, Florida 33143
KEY PLAN
0 9
COMM. NO. 40070.000
SCALE: AS SHOVM
DATE: MAY 30, 2013
DRAWN: -
CHECKED: sH
CADD FILE: H:INSTITUTIONAL
DRAWING TITLE:
THIRD FLOOR
LIFE SAFETY
PLAN
SHEET NO.
LS1 01