13-1288-013ABBREVIATIONS /SUFFIXES
NOTE:
1. SYMBOLS IN DASHED LINE INDICATE EXISTING
DEVICES. POWER EQUIPMENT
2. ALL SYMBOLS MAY NOT BE USED IN THIS PROJECT.
A.F.F. ABOVE FINISHED FLOOR
A.F.G. ABOVE FINISHED GRADE
AWG AMERICAN WIRE GAUGE
BD. BOARD
C. CONDUIT
CAB. CABINET
C.B. CIRCUIT BREAKER
CKT. CIRCUIT
CCTV CLOSED CIRCUIT TELEVISION
CO -THW COPPER WIRE WITH THERMOPLASTIC, HEAT RESISTANT,
MOISTURE RESISTANT CHARACTERISTICS
E.A. EMPTY CONDUIT
E.W.C. ELECTRIC WATER COOLER
E EXISTING TO REMAIN
ER EXISTING TO BE RELOCATED OR REMOVED
EMT ELECTRICAL METALLIC TUBING
F.A. FIRE ALARM
G.F.I. GROUND FAULT INTERRUPTER
GND. GROUND
HID HIGH INTENSIVE DISCHARGE
HPS HIGH PRESSURE SODIUM
I.G. ISOLATED GROUND
LT. LIGHT
LTG. LIGHTING
MCB MAIN CIRCUIT BREAKER
MLO MAIN LUGS ONLY
MT. MOUNT
MTG. HT. MOUNTING HEIGHT
N.E.C. NATIONAL ELECTRICAL CODE
N.I.C. NOT IN CONTRACT
NL NIGHT LIGHT
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION.
LFMC LIQUID TIGHT FLEXIBLE METAL CONDUIT
P.A. PUBLIC ADDRESS
PNL. PANEL
PTZ PAN- TILT -ZOOM CAMERA
RECEPT. RECEPTACLE
RMC RIGID METAL CONDUIT
S.D.B.C. SOFT DRAWN BARE COPPER
SW. SWITCH
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION PANEL
U.O.N. UNLESS OTHERWISE NOTED
V.P. VAPOR PROOF
VOC VOLATILE ORGANIC COMPOUND
WAP WIRELESS ACCESS POINT
W.G. WIRE GUARD.
W.P. WEATHER PROOF (NEMA 3R ENCLOSURE)
X.P. EXPLOSION PROOF (CLASS TO MEET N.E.G.)
0
LIGHTING FIXTURE IDENTIFICATION. SEE SCHEDULE
Q
HID OR FLUORESCENT DOWN LIGHT
Q
ACCENT TYPE LIGHT FIXTURE
(J
HID OR FLUORESCENT WALL MOUNTED LIGHT FIXTURE
J
RECESSED / LAY -IN MOUNTED FLUORESCENT LIGHT FIXTURE
®
SURFACE OR PENDANT MOUNTED FLUORESCENT LIGHT FIXTURE
WALL MOUNTED FLUORESCENT LIGHT FIXTURE
I- -)
SURFACE OR PENDANT MOUNTED FLUORESCENT STRIP
HID DOWN LIGHT ON NIGHT LIGHT CIRCUIT & EQUIPPED WITH RESTRIKE SYSTEM
fj
HID WALL MOUNTED LIGHT FIXTURE ON NIGHT LIGHT CIRCUIT
RECESSED /FLUORESCENT LIGHT FIXTURE ON EMERGENCY CIRCUIT OR
EMERGENCY BATTERY PACT.
®
SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE ON LIGHT CIRCUIT OR
EMERGENCY BATTERY PACT
Q
EXIT LIGHT
WALL MOUNTED EXIT LIGHT SHADED QUADRANT INDICATES NUMBER OF FACES.
ARROWS AS SHOWN OR REQUIRED.
UNIT EQUIPMENT BATTERY BACKUP EMERGENCY LIGHT
COMBINATION EXIT / EMERGENCY LIGHT WITH BATTERY BACKUP.
LANDSCAPE LIGHT FIXTURE
C Q
POLE MOUNTED SINGLE SITE LIGHTING FIXTURE
000
POLE MOUNTED DOUBLE SITE LIGHTING FIXTURE
Q
CEILING MOUNTED OCCUPANCY SENSOR. INCLUDE POWER PACK AS REQUIRED.
®
OCCUPANCY SENSOR POWER PACK.
®
LTG. TRANSFER RELAY.
S
SINGLE POLE SWITCH - 20 AMP (48" A.F.F.)
S3
THREE WAY SWITCH - 20 AMP (48" A.F.F.)
S4
FOUR WAY SWITCH - 20 AMP (48" A.F.F.)
So
DIMMER SWITCH 2000 WATTS 48" A.F.F.)
SF
FAN SPEED CONTROL (48" A.F.F.)
SK
KEY OPERATED SWITCH - 20 AMP (48" A.F.F.)
SP
SINGLE POLE SWITCH WITH PILOT LIGHT - 20 AMP(48" A.F.F.)
Sm
MOTOR RATED SWITCH (ONE, TWO OR THREE POLE AS REQUIRED)
ST
TIME CONTROL SWITCH
SOS
OCCUPANCY SENSOR SINGLE POLE SWITCH - 20 AMP. (42" AFF).
SOS2
OCCUPANCY SENSOR 2 RELAY DUAL TECH SWITCH - 20 AMP. (42" AFF).
SOR
OVERRIDE SWITCH - 20 AMP. (42" AFF).
FIRE ALARM DEVICES
® FIRE ALARM PULL STATION (48" A.F.F.) SEMI FLUSH MOUNTED,
PROVIDE BREAKABLE GLASS COVER.
04 FIRE ALARM HORN WITH STROBE LIGHT (80 "A.F.F.) ADA
FIRE ALARM SPEAKER WITH STROBE LIGHT (80 "A.F.F.) ADA
® FIRE ALARM SPEAKER WITH STROBE LIGHT. CEILING MOUNTED
(S FIRE ALARM MASS NOTIFICATION SPEAKER. CEILING MOUNTED
FIRE ALARM STROBE LIGHT - 75 CANDELA MIN. - (80 " A.F.F.) OR 6" BELOW
CEILING WHISHEVER IS LOWER, INSTALLATION SHALL COMPLY WITH A.D.A.,
FIRE ALARM STROBE LIGHT. CEILING MOUNTED
24V SMOKE DETECTOR (PHOTOELECTRIC TYPE).
®H SMOKE AND HEAT DETECTOR
C)H 24V FIXED TEMPERATURE 135° F THERMAL DETECTOR.
® 24V PHOTOELECTRIC DUCT DETECTOR.
DH FIRE ALARM DOOR HOLDER
FS FIRE ALARM FLOW SWITCH
TS FIRE ALARM TAMPER SWITCH
FACP FIRE ALARM CONTROL PANEL
ray:• ;a
Itlllllll
►:f
►�4
HIGH VOLTAGE DISTRIBUTION PANELBOARD 277/480V
LOW VOLTAGE DISTRIBUTION PANELBOARD 120/208V
HIGH VOLTAGE PANELBOARD 277/48OV.
LOW VOLTAGE PANELBOARD 120/208V.
HD FUSIBLE DISCONNECT OR CIRCUIT BREAKER. NEMA 3R WHEN OUTDOORS.
3 =NO. OF POLES, 60= SWITCH SIZE, 50 =FUSE, NF= NON - FUSED,
' =FUSE SIZE AS REQUIRED BY LOAD.
MOTOR STARTER W /CONTROL XMFR, HOA SELECTOR SW. AND RED PILOT
LIGHT. NEMA SIZE BY MOTOR. PROVIDE NEMA 4 ENCLOSURE WHEN
OUTDOORS
COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH OR CB. SAME
ENCLOSURE AND ACCESSORIES AS INDICATED ABOVE
CONTACTOR. SAME ENCLOSURE AND ACCESSORIES AS STARTERS
FAN
MOTOR "2" WHEN SHOWN INDICATES HORSEPOWER
TRANSFORMER
POWER DEVICES
19�4 DUPLEX RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.) U.O.N.
el SINGLE RECEPT - 20 AMP NEMA 5 -20R (18 " A.F.F.) U.O.N.
DUPLEX RECEPT. MOUNTED ABOVE COUNTER - 20 AMP NEMA 5 -20R
(44" A.F.F.) U.O.N.
DUPLEX RECEPT. (UPS CONNECTION) - 20 AMP NEMA 5 -20R (18" A.F.F.)
Q� POWER RECEPT. TWIST LOCK - 20 AMP NEMA L5 -2OR (18" A.F.F.)
�j QUAD - PLEX RECEPT - 20 AMP NEMA 5 -20R (18" A.F.F.)
® DUPLEX RECEPT FLUSH FLOOR MOUNTED - 20 AMP NEMA 5 -20R
0 DUPLEX RECEPT FLUSH CEILING MOUNTED - 20 AMP NEMA 5 -20R
0- SPECIAL PURPOSE RECEPT (18" A.F.F.)
Q JUNCTION BOX
WALL MOUNTED JUNCTION BOX
FLOOR MOUNTED JUNCTION BOX UNDER RAISED FLOOR FOR CONNECTION
J TO WIREMOLD PLUG STRIP MOUNTED AT RACKS AND FURNITURE BY A
HARDWIRE FLEXIBLE CONNECTION BY ELECTRICAL CONTRACTOR.
PB PULL BOX
WIRING
BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT. NO TICKS INDICATES 2 #
12 CONDUCTORS & 1 # 12 GROUND IN, 3/4 " CONDUIT. TICK MARKS WHEN
SHOWN, INDICATES NUMBER OF # 12 CONDUCTORS IF OTHER THAN THREE,
(1) INDICATES GROUND. CONDUIT LARGER THAN 3/4" & CONDUCTOR
LARGER THAN # 12 SHALL BE AS INDICATED.
HOME RUN TO PANEL "A' = PANEL DESIGNATION, 1,3,5 = CIRCUIT NUMBERS.
U.O.N. MINIMUM SIZE OF 3/4 "C AND MAXIMUM OF THREE CIRCUITS PER
A-13,5 HOMERUN. (DEDICATED NEUTRAL FOR EACH HOT WIRES MUST BE PROVIDED)
�f�fti FLEXIBLE CONDUIT
CONDUIT RUN CONCEALED IN CEILING OR WALLS
-U /G - CONDUIT RUN UNDERGROUND OR IN SLAB
- - - - CONDUIT RUN EXPOSED
C CAPPED CONDUIT
-4-i -1 SYSTEM AND /OR EQUIPMENT GROUNDING CONDUCTOR
11 - GROUNDING ELECTRODE AND CONDUCTOR SYSTEM
XS CONDUIT SEAL
CABLE TRAY
DATA AND COMMUNICATIONS
V TELEPHONE & DATA OUTLET (4 "x 4 "x 2 1/2" OUTLET BOX) (18" A.F.F.)
® TELEPHONE & DATA OUTLET FLUSH FLOOR MOUNTED
0 DATA OUTLET (4"x 4 "x 2 1/2" OUTLET BOX) (18" A.F.F.)
Mn TELEPHONE OUTLET FLUSH FLOOR MOUNTED
V TELEPHONE OUTLET (4 "x 4 "x 2 1/2" OUTLET BOX)(18" A.F.F.)
VW WALL MOUNTED TELEPHONE OUTLET (60 "A.F.F.)
® CLOCK (8' -0" AFF)
D TERMINAL CABINET - TYPE INDICATED
® TELEPHONE TERMINAL BACK BOARD
N _F 11 WIRELESS ACCESS POINT
Q RADIO REMOTE
PAGER SPEAKER
ROOM RESERVATION SYSTEM. POWERED OVER ETHERNET.
TB RECESSED TABLE BOX, 2 CATEGORY 6 CABLE, 1VGAW / TV, 1 HDMI,
DUPLEX ELECTRICAL OUTLET (EXTRON 300S CABLE CUBBY)
FP AV. TOUCH PANEL
c w INTERCOM STATION (WALL MTD) -3GANG BOX @ 4' -0"
cc D INTERCOM (DOOR STATION) SAME AS WALL MTD
F0 INTERCOM @ 4' -0" A.F.F.
cT CAN STATIONS @ 2' -6" A.F.F. (U.N.O.)
Fe WALL MOUNTED AUDIOVISUAL OUTLET.
FT WALL MOUNTED TV OUTLET.
FS-71 CLOCK/ INTERCOM SPEAKER.
FE-M- NORMAL/ EMERGENCY CALL -IN PUSH BUTTON.
SECURITY SYSTEM DEVICES
® CLOSE CIRCUIT TV MONITORS
cCTU CCTV CAMERA
Z SECURITY DOOR RELEASE BUTTON
SECURITY DOOR BELL CHIME
KP SECURITY SYSTEM KEYPAD
CR SECURITY SYSTEM CARD READER
SECURITY SYSTEM UHF CARD READER
(�o SECURITY SYSTEM MOTION DETECTOR
GB SECURITY SYSTEM GLASS BREAKER SENSOR
DS SECURITY SYSTEM DOOR STRIKE
SECURITY SYSTEM DOOR CONTACT
,ML SECURITY SYSTEM MAGNETIC LOCK
RFZ SECURITY SYSTEM REQUEST TO EXIT. (CEILING MOUNTED)
PS POWER SUPPLY
GENERAL NOTES:
1. SITE INVESTIGATION: PRIOR TO BIDDING THE CONTRACTOR SHALL VISIT THE JOBSITE
AND BECOME ACQUAINTED WITH ALL OF THE EXISTING CONDITIONS WHICH WILL
AFFECT HIS WORK. FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR
REQUESTING EXTRA PAY WHERE THE EXISTING CONDITION RESULTS IN EXTRA
MATERIAL OR LABOR. THE CONTRACTOR SHALL SUBMIT IN HIS BID AN AMOUNT THAT
WOULD BE SET ASIDE FOR UNIDENTIFIED ITEMS.
2. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST
CLASS MANNER AND SHALL BE A COMPLETED AND FULLY OPERATIVE TO THE
ACCEPTANCE OF THE OWNER, GENERAL CONTRACTOR AND ENGINEER.
3. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT
NECESSARY FOR THE COMPLETE INSTALLATION OF THE ELECTRICAL SYSTEMS, ALL IN
ACCORDANCE WITH THESE CONSTRUCTION DOCUMENTS. ALL WORK PERFORMED
UNDER THIS CONTRACT SHALL COMPLY WITH THE FLORIDA BUILDING CODE 2010 AND
NFPA CODES INCLUDING, BUT NOT LIMITED TO NFPA 70 - (2008 NEC), NFPA 72 (2007) -
(FIRE ALARM) AND NFPA 101 - LIFE SAFETY CODE (2009).
4. THIS CONTRACTOR SHALL PAY FOR ALL FEES, INSPECTIONS, TESTS, FINES, ETC., AS
REQUIRED.
5. MINIMUM STANDARDS: THE MATERIAL, EQUIPMENT, INSTALLATIONS, AND
WORKMANSHIP FURNISHED UNDER THIS SECTION SHALL CONFORM AT LEAST TO THE
REQUIREMENTS OF THE REGULATING AGENCIES AS LISTED IN ITEM (3) ABOVE.
6. RESPONSIBILITIES: CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A
COMPLETE INSTALLATION OF THE RACEWAY SYSTEM, EQUIPMENT AND WIRING IN
ACCORDANCE WITH THE CONTRACT DOCUMENTS.
7. GUARANTEE: THE CONTRACTOR/SUB- CONTRACTOR SHALL FURNISH A WRITTEN
GUARANTEE THAT ALL WORK EXECUTED UNDER THIS CONTRACT SHALL BE FREE FROM
DEFECTS OF WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR FROM THE
DATE OF FINAL ACCEPTANCE AND THAT HE, AT HIS OWN EXPENSE, WILL REPAIR OR
REPLACE ALL WORK WHICH BECOMES DEFECTIVE DURING THE TIME OF THE
GUARANTEE.
8. ALL EQUIPMENT, SYSTEMS AND SYSTEM COMPONENTS SHALL BE FROM THE SAME
MANUFACTURER AND SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURERS RECOMMENDATIONS AND SPECIFICATIONS.
9. VERIFY ALL DIMENSIONS WITH ARCHITECTURAL PLANS PRIOR TO ANY FABRICATIONS
OR INSTALLATION.
10. OBTAIN FULL INFORMATION REGARDING PECULIARITIES AND LIMITATIONS OF SPACE
AVAILABLE FOR INSTALLATION OF THE EQUIPMENT AND MATERIALS UNDER CONTRACT,
AND PROVIDE READY ACCESSIBILITY TO ELECTRICAL EQUIPMENT, INCLUDING ANY
PART OF SYSTEM REQUIRED TO BE REACHED FOR MAINTENANCE AND OPERATIONS.
11. PROVIDE ACCURATE LAYOUT, GRADES AND ELEVATIONS. TAKE PROPER PRECAUTIONS
TO PROTECT WORK AND EQUIPMENT FROM DAMAGE.
12. PROVIDE CODE APPROVED FIRE STOPPING AT ALL CONDUIT PENETRATIONS
THROUGHOUT BUILDING CONSTRUCTION TO MAINTAIN FIRE, SMOKE AND SOUND
RATING. FIRE SEAL ALL PENETRATIONS. SEAL TELECOMMUNICATION SLEEVES AFTER
CABLES HAVE BEEN INSTALLED.
13. RACEWAYS AND FITTINGS: CONDUIT RUNS SHALL BE CONCEALED IN CEILING SPACES
AND WALL PARTITIONS. NO CONDUIT SHALL BE EXPOSED IN INTERIOR SPACES EXCEPT
FLEXIBLE CONNECTION TO WIRE MOLDS. CONCEALED CONDUITS ARE TO BE EMT.
SURFACE MOUNTED RACEWAYS (WIRE MOLD) ARE TO BE INSTALLED IN SOLID WALLS
ONLY. THE MINIMUM CONDUIT SIZE IS TO BE 1/2 ". ALL CONDUITS AND RACEWAYS
SHALL BE METAL.
14. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION WITH OTHERS AS
WELL AS PROVIDING TEMPORARY POWER.
15. VERIFY EQUIPMENT SIZES, VOLTAGE AND CURRENT CHARACTERISTICS, ETC., BEFORE
THE ORDERING OF ANY EQUIPMENT AND PRIOR TO ROUGHING -IN FOR EQUIPMENT TO
BE SUPPLIED TO OTHERS. NOTIFY ENGINEER OF ANY CONFLICT.
16. PROVIDE COMPLETE POWER CIRCUIT WIRING AND CONNECTIONS FOR EACH AND
EVERY ITEM OF PERMANENT MECHANICAL EQUIPMENT. PRIOR TO ANY ROUGH -IN,
COORDINATE WITH HVAC AND PLUMBING EQUIPMENT NAME PLATE TO OBTAIN
CORRECT WIRE SIZE AND OVERCURRENT PROTECTION RATING. IF THE NAME PLATE
LABEL REQUIRES THE OVERCURRENT PROTECTION DEVICE TO BE FUSES, PROVIDE A
FUSED SWITCH WITH PROPER SIZE FUSES AT THE EQUIPMENT LOCATION.
17. CONDUCTOR: ALL CONDUCTOR WIRE AND CABLE SHALL CONSIST OF 98%
CONDUCTIVITY COPPER. ALL CABLES SHALL BE SINGLE CONDUCTOR, 600 VOLT,
THERMOPLASTIC INSULATION, SUITABLE FOR CONTINUOUS OPERATION AT 75 DEGREES
C. CONDUCTOR TEMPERATURE IN BOTH WET AND DRY LOCATIONS. THESE CABLES
SHALL BE N.E.C. INSULATION CLASSIFICATION TYPE THWN/THHN. MINIMUM SIZE SHALL
BE #12. ALL CONDUCTOR INSULATION SHALL BE COLOR CODED MAINTAINING THE
INTEGRITY OF THE EXISTING INSTALLATION. COLORED INSULATION SHALL BE USED
FOR AWG SIZES #10 AND SMALLER AND APPROVED COLOR TAPES SHALL BE USED FOR
AWG SIZES #8 AND LARGER. ALL POWER AND CONTROL CIRCUITS SHALL CARRY
EQUIPMENT GROUNDING CONDUCTOR SIZED PER NEC 250 -122.
18. THE NATURE OF THIS TYPE OF CONSTRUCTION POSES SPECIAL PROBLEMS FOR THE
DESIGN ENGINEER AS WELL AS THE CONTRACTOR. EVERY EFFORT HAS BEEN MADE BY
THE ENGINEER TO SHOW AND VERIFY WHERE POSSIBLE THE LOCATION OF THE
EXISTING ELECTRICAL SYSTEM. THE MAJOR PORTION OF THE ELECTRICAL SYSTEMS
ARE AS SHOWN ON THE DRAWINGS. HOWEVER, MINOR DEVIATIONS MAY BECOME
EVIDENT AS THE JOB PROGRESSES. NO ADVANTAGE IS TO BE TAKEN BY THE
CONTRACTOR BECAUSE OF THESE MINOR DIFFERENCES.
19. CORRECTION OF ANY DEFECTS, REPAIRS OR DAMAGE DURING CONSTRUCTION AS
WELL AS ANY MINOR CHANGES IN OUTLET LOCATIONS SHALL BE MADE WITHOUT
ADDITIONAL COST.
20. GUTTERS, PULL BOXES, ETC., SHALL BE GALVANIZED STEEL SIZED PER NATIONAL
ELECTRICAL CODE, ARTICLE 312, MADE OF MATERIAL SUITABLE FOR THE
ENVIRONMENTAL CONDITIONS PRESENT.
21. ALL FLOORS, WALLS AND ROOF PENETRATIONS SHALL BE PROPERLY SEALED -OFF. IF
FIRE RATED, AN APPROVED FIRE RETARDANT SEAL SHALL BE USED.
22. ALL WIRING SHALL BE IN RACEWAY.
A. INDOORS - USE THE FOLLOWING WIRE METHODS:
• EXPOSED: EMT
• CONCEALED: EMT
• CONNECTION TO VIBRATION EQUIPMENT (INCLUDING TRANSFORMERS AND
HYDRAULIC, PNEUMATIC, ELECTRIC SOLENOID, OR MOTOR - DRIVEN EQUIPMENT):
FMC, EXCEPT IN WET OR DAMP LOCATIONS USE LFMC.
• DAMP OR WET LOCATIONS: RIGID STEEL CONDUIT.
• BOXES AND ENCLOSURES: NEMA 250, TYPE 1, EXCEPT AS FOLLOWS:
B. DAMP OR WET LOCATIONS: NEMA 250, TYPE 3R STEEL.
C. DAMP OR WET LOCATIONS: 250, TYPE 4, NONMETALLIC.
• UNDERGROUND RNC (SINGLE RUN OR GROUPED).
D. SEALING FITTINGS SHALL BE INSTALLED AT FOLLOWING POINTS, AND ELSEWHERE AS
SHOWN.
• WHERE REQUIRED BY THE NEC.
23. THESE DRAWINGS ARE A GUIDE FOR THE INSTALLATION OF THE RACEWAY SYSTEM AND
EQUIPMENT. THEY ARE INTENDED TO SHOW THE GENERAL ARRANGEMENT, DESIGN
AND EXTENT OF THE WORK AND ARE PARTLY DIAGRAMMATIC. THE CONTRACTOR IS
RESPONSIBLE FOR PROVIDING A COMPLETE AND FUNCTIONAL INSTALLATION.
24. CIRCUIT NUMBERS ARE FOR IDENTIFICATION PURPOSES ONLY. THE CONTRACTOR IS
RESPONSIBLE FOR CORRECTLY PHASING THE CIRCUITS IN THE PANEL AND SHALL
BALANCE THE LOAD ON THE PHASES UNDER NORMAL OPERATING CONDITIONS.
PROVIDE TYPE WRITTEN PANEL BOARD DIRECTORIES IN EXISTING PANEL BOARD
DIRECTORIES. UPDATE ALL DIRECTORIES IN EXISTING PANEL BOARDS AFFECTED BY
THIS PROJECT ELECTRONICALLY TRACING ALL CIRCUITS.
25. ANY DEVIATION FROM THESE DRAWINGS AND SPECIFICATIONS MUST BE AUTHORIZED
IN WRITING FROM THE ENGINEERS OFFICE. THE CONTRACTOR SHOULD BE HELD LIABLE
FOR ANY DEVIATIONS WITHOUT SUCH AUTHORIZATION.
26. ALL POWER AND LIGHTING CIRCUITS SHALL HAVE A GREEN EQUIPMENT GROUNDING
CONDUCTOR SIZED AS PER NEC 250 -122. NEUTRAL CONDUCTOR SHALL BE 10 AWG
(MINIMUM CU -THW) IN ALL MULTICIRCUIT BRANCH CIRCUITS.
27. PROVIDE NYLON PULL STRINGS IN ALL EMPTY CONDUITS FOR FUTURE USE.
28. COLOR CODING FOR CONDUCTORS: "
A. WIRING FOR 120/208 VOLT SYSTEM SHALL BE CODED AS FOLLOWS:
PHASE A - BLACK
PHASE B - RED
PHASE C - BLUE
NEUTRAL - WHITE
GROUND - GREEN
B. WIRING FOR 120/240 VOLT SYSTEM SHALL BE AS FOLLOWS:
PHASE A - BLACK
PHASE B (HIGH LEG) - ORANGE
PHASE C - RED
NEUTRAL - WHITE
GROUND - GREEN
C. WIRING FOR 277/480 VOLT SYSTEM SHALL BE CODED AS FOLLOWS:
PHASE A - BROWN
PHASE B - ORANGE
PHASE C - YELLOW
NEUTRAL - GRAY
GROUND - GREEN
D. COLORS ON CONDUCTOR 6 AWG AND SMALLER SHALL BE AN INTEGRAL PART OF
INSULATION. ON CONDUCTOR 4 AWG AND LARGER CONDUCTORS, EITHER COLOR
CODING TAPE OR PAINTED WITH TWO COATS OF CORRECT COLOR PAINT AT ALL
TERMINALS AND CONNECTION POINTS.
UNLESS OTHERWISE REQUIRED BY APPLICABLE CODE.
29. ANY WORK NOT SHOWN OR SPECIFICALLY MENTIONED ON THESE PLANS BUT
CONSIDERED NECESSARY FOR COMPLETION OF WORK IN THE PROPER MANNER SHALL
BE PROVIDED BY THE CONTRACTOR WITHOUT ADDITIONAL CHARGE.
30. CONTRACTOR SHALL VERIFY SPACE CONDITIONS AND DIMENSIONS AT JOB SITE PRIOR
TO FABRICATION AND INSTALLATION OF MATERIALS AND EQUIPMENT. ELECTRICAL
CONTRACTOR IS TO COORDINATE HIS WORK WITH THE ARCHITECT BEFORE ROUGH
INSTALLATION OF ALL OUTLETS (LIGHTS, RECEPTACLES, SWITCHES, PULL BOXES, ETC.)
FOR EXACT LOCATION.
31. ALL ELECTRICAL EQUIPMENT SUCH AS PANELS, PULUJ- BOXES, FEEDERS, ETC. SHALL
BE PROPERLY IDENTIFIED WITH A PERMANENT LABEL AFFIXED TO THE EQUIPMENT.
IDENTIFY CIRCUIT IN PANELS BY MEANS OF A TYPED, PLASTIC COVERED DIRECTORY.
32. SPOT PAINT CONDUITS AND BOXES. IDENTIFY CONDUITS WITHIN 6 INCHES (6 ") OF BOX
OR ENCLOSURE. USE ONLY COLOR CODE IN COMPLIANCE WITH USER REQUIREMENTS
UPON COMPLETION.
33. ALL SERVICE INTERRUPTIONS AND ALL REMOVAL AND DISPOSAL WORK SHALL BE
SCHEDULED AND COORDINATED WITH THE AUTHORIZED REPRESENTATIVE OF THE
OWNER.
34. CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS,
TESTS AND OTHER ITEMS AS REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC
LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK.
35. CONTRACTOR SHALL MAINTAIN A COMPLETE SET OF PRINTS FOR INDICATING ALL
CHANGES AS THE CONTRACTOR PROGRESSES. AT THE COMPLETION OF THE WORK,
THE CONTRACTOR SHALL DELIVER A SET OF AS -BUILT DRAWINGS TO THE OWNER IN
REPRODUCIBLE MATERIAL. CONTRACTOR SHALL STAMP AS -BUILT ON THE PLANS (EACH
SHEET), PRINT, DATE, AND SIGN WITH INK.
36. CONTRACTOR IS RESPONSIBLE FOR REPLACING ALL PARTITION, FLOOR CEILING,
CONDUIT PENETRATIONS, AND ANY OTHER EXISTING CONDITION AFFECTED BY THIS
PROJECT. UPON COMPLETION, RE -PAINT ALL AFFECTED SURFACES MATCHING
SURROUNDING COLOR.
37. TELECOM RACEWAYS, EMPTY BOXES AND PULL STRINGS TO BE INSTALLED BY
ELECTRICAL CONTRACTOR. WIRING AND WIRING DEVICES AND FINAL CONNECTION IS
TO BE BY OWNER.
38. NO MULTIWIRE CIRCUIT ALLOWED EACH CIRCUIT MUST HAVE ITS SEPARATE NEUTRAL
CONDUCTOR.
39. ELECTRICAL EQUIPMENT TO BE PROVIDED WITH A WARNING LABEL FOR ARC FLASH
HAZARDS IN COMPLIANCE WITH NEC 110.16.
40. PROJECT TO COMPLY WITH THE REQUIREMENT OF CURRENT EDITION OF NFPA 241
STANDARDS FOR SAFE GUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION
OPERATIONS.
41. CONTRACTOR SHALL PROVIDE THE REQUIRED MEASURES FOR THE SAFEGUARDING OF
THE EXISTING FACILITY AND SYSTEMS THEREIN DURING THE PERFORMANCE OF THE
CONSTRUCTION, DEMOLITION AND ALTERATION OPERATIONS UNDER THIS PROJECT IN
ACCORDANCE WITH NFPA 241 2009 EDITION.
42. CONTRACTOR SHALL MAINTAIN THE FUNCTIONING AND INTEGRITY OF THE FACILITY
FIRE ALARM SYSTEM DURING ALL PHASES OF CONSTRUCTION.
43. ALL LAMPS SPECIFIED AND PURCHASED PER BUILDING NOT TO EXCEED AN OVERAGE
OVERALL MERCURY - CONTENT OF 90 PICOGRAMS OF MERCURY PER LUMEN -HOUR.
CONTRACTOR TO SUBMIT LAMP DATA SHEETS TO LEED CONSULTANT SHOWING
COMPLIANCE PRIOR TO PURCHASE AND INSTALLATION, AND SHALL TRACK MERCURY
CONTENT OF ALL LAMP TYPES.
44. ALL ELECTRICAL EQUIPMENT, FIXTURE, CAMERAS, DEVICES AND CABLES / WIRING
SHALL BEAR (NRTL) THIRD PARTY APPROVALS AND BE LISTED FOR ENVIRONMENT IN
WHICH THEY ARE INSTALLED (NEC 90.7, 110.3 (A) (B) AND 410.6)
ARCHITECT:
t
ba
BERMELLO AJAMIL & PARTNERS, INC.
M _ Architecture Engineering Planning
- - -p Interiod Deign Landscape Architecture
260,1 5icutn Bayshore Drive 10th Floor
Miami, Florida 33133
(305) 859 -2050 Fax (305) 860 -3700
LOUIS J. AGUIRRE & ASSOCIATES, P.A.
Consulting Engineers
9150 South Dodeland Blvd. ® Suite 900
Miami *Florida 33156 *CA 924
Telephone 305.670.0141
Facsimile 305.670.0144
www.ljaaoa.com
Project No.: 23069
CONSTRUCTION
DOCUMENTS
REVISIONS-
PROJECT NAME:
SMH - LOBBY FLOOR REPLACEMENT
& GIFT SHOP RENOVATION
PROJECT ADDRESS:
7400 S.V. 62nd Ave.
South Miami, Florida 33143
KEY PLAN
COMM. NO.
SCALE:
DATE:
DRAWN:
CHECKED:
CADD FILE:
40071.000
08-28 -2013
BH
MINSTITUTIONAL
DRAWING
SYMBOLLEGEND
AND GENERAL
ELECTRICAL
SHEET NO.