13-1288-004SYMBOL LEGEND
ONE HOUR FIRE RATED PARTITION
2= r mm
ONE HOUR FIRE RATED/ SMOKE PARTITION
TWO HOUR FIRE RATED PARTITION
MIM ") I 1 111110
TWO HOUR FIRE RATED/ SMOKE PARTITION
OEM
THREE HOUR FIRE RATED/ SMOKE PARTITION
FOUR HOUR RATED/ SMOKE PARTITION
EXIT LIGHT (CENTER ON DOOR(S))
NOTE: SHADED AREA INDICATES
LIGHTED FACE
EXIT LIGHT: DIRECTIONAL (CENTER ON DOOR(S)
AS REQUIRED)
NOTE: SHADED AREA INDICATES
LIGHTED FACE
LIFE SAFETY GENERAL N O-1 ES n.1
1. THIS SHEET SHOWS LIFE SAFETY EXITING DURING CONSTRUCTION OF THE PROJECT
DUE TO TEMPORARY WALL NO NEW WALLS OR DOORS ARE BEING CONSTRUCTED THAT
WILL ALTER EXITING ROUTES TO THE EXISTING HOSPITAL THEREFOR, A- FULL- pff- wzw
PLAN IS NOT PART OF THE PACKAGE OF THESE CONSTRUCTION DOCUMENTS.--
GENERAL LIFE SAFETY CRITERIA
A. CODES: APPLICABLE CODES:
• FLORIDA BUILDING CODE 2010
• FLORIDA ACCESSIBILITY CODE 2012
• FLORIDA TEST PROTOCOLS (HIGH VELOCITY HURRICANE ZONES) 2010
• FLORIDA MECHANICAL CODE 2010
• FLORIDA PLUMBING CODE 2010
• FLORIDA GAS CODE 2010
• AIA GUIDELINES FOR DESIGN AND CONSTRUCTION OF
HOSPITALS AND HEALTH CARE FACILITIES - 2010 EDITION
• FLORIDA FIRE PREVENTION CODE/NFPA 101 - 2009 CHAPTER 19, EXISTING HEALTH
CARE
OCCUPANCIES
• NFPA 70 - 2008
• NFPA 253 - 2006
• NFPA 13 - 2007 STANDARD FOR INSTALLATION OF SPRINKLER SYSTEM
• NFPA 14 - 2007 STANDARD FOR THE INSTALLATION OF STANDPIPE, PRIVATE
HYDRANTS, AND HOSE SYSTEMS.
• NFPA 72 - 2007 (NEC) NATIONAL FIRE ALARM CODE
B. OCCUPANCY:
OCCUPANCY TYPE:
• INSTITUTIONAL (FLORIDA BUILDING CODE 2010 - SECTION
308.3 GROUP 1-2)
C. CLASSIFICATION:
BUILDING CLASSIFICATION:
• TYPE [-A FULLY SPRINKLERED (FBC 2010) TABLE 601
• NFPA 220 - TYPE 1 (443)
D. BUILDING TYPE: (CLASSIFIED BY TYPE OF CONSTRUCTION)
FBC SEC. 5
CRITERIA OUTLINED BELOW IS TYPICAL FOR ALL OCCUPANCIES AND BASED UP
CRITERIA OF A FULLY
SPRINKLERED BUILDING.
1. TYPE OF CONSTRUC11ON: (TYPE I-A) FULLY SPRINKLERED IN ACCORDANCE WITH
903.3.1
2. STRUCTURE OF EXISTING (I-A) = FBC EXISTING BUILDINGS. CHAPTER 4 (407 AND
419)
3. ALLOWABLE HEIGHT=UNLIMITED (FBC TABLE 503)
4. MAX NO. OF STORIES = UNLIMITED (FBC TABLE 503)
5. ALLOWABLE BUILDING AREA = UNLIMITED (TABLE 503)
E. OCCUPANCY LOAD: FBC SEC. 10 (TABLE 1004.1.1)/NFPA
TABLE 7.3.1.2
1. PRIMARY OCCUPANCY (INSTITUTIONAL - INPATIENT TREATMENT): 240 SF GROSS
2. ACCESSORY OCCUPANCY (INSTITUTIONAL - OUTPATIENT AREAS): 100 SF GROSS
3. ACCESSORY OCCUPANCY (BUSINESS) 100 SF GROSS
4. ACCESSORY OCCUPANCY (ASSEMBLY - 2) 15 SF/P
G. TRAVEL DISTANCES / EXIT WIDTHS REQUIREMENTS:
(FBC SEC. 10)
THE REQUIREMENTS OUTLINED BELOW ARE BASED ON A FULLY SPRINKLERED
BUILDING AND APPLICABLE OCCUPANT TYPES.
1. ALLOWABLE TRAVEL DISTANCES BY OCCUPANCY(FBC 1016.1): INSTITUTIONAL (1-2)
a. MAX. TRAVEL DISTANCE TO EXIT- 200 FT. (FBC TABLE
1016.1).
b. MAX TRAVEL DISTANCE TO EAT FROM RM DOOR. 150 FT.
(NFPA 101)
c. MAX DEAD END CORRIDOR : 20 FT. (FBC 1018.4/20 NFPA
19.2.5.2
d. MAX COMMON PATH OF TRAVEL- 75 FT./50 NFPA 101
2. EGRESS WIDTHS:
a. LEVEL EAT. 0.2 IN. PER PERSON (FBC 1005.1)
b. STAIRS: 0.3 IN. PER PERSON (FBC 1005.1)
Q MIN. CORRIDOR WIDTH: 44 IN. (FBC 1018.2)
d. CLEAR OPENING DOOR EXIT- 32 IN. (FBC 1008.1.1)
e. MIN. STAIR WIDTH 44 IN. (FBC 1009.1)
3. VERTICAL EXIT ENCLOSURES
a.1 HR. CONNECTING 3 STORIES OR LESS / 2 HR.
CONNECTING 4 OR MORE STORIES. (FBC 1022.1)
4. EXIT PASSAGEWAYS
a. WIDTH = 44-IN. MIN. (FBC 1023.2)
b. CONSTRUCTION = I HR. MIN BUT NOT LESS THAN THAT
REQUIRED FOR ANY CONNECTING EAT ENCLOSURES (FBC
1023.3)
c. OPENINGS AND PENETRA11ONS = ONLY FROM EXIT ACCESS
FROM NORMALLY OCCUPIED SPACES. (1023.5) AS REQ. BY
FBC 715.
d. PENETRATIONS = NP EXCEPT MEN SERVING EXIT
PASSAGEWAY
H. INTERIOR FINISHES: (FBC SEC. 8)
THE REQUIREMENTS OUTLINED BELOW ARE BASED UPON A FULLY SPRINKLERED
BUILDING AND APPLICABLE OCCUPANT TYPES.
CLASS A - FLAME SPREAD - 00-25 SMOKE DEVELOPMENT - 0-450
CLASS B - FLAME SPREAD - 26-75 SMOKE DEVELOPMENT - 0-450
CLASS C - FLAME SPREAD - 76-200 / SMOKE DEVELOPMENT - 0-450
1. EAT ENCLOSURES AND EXIT PASSAGEWAYS
a. INSTITUTIONAL 1-2. CLASS B
2. CORRIDORS
a. INSTITUTIONAL 1-2: CLASS B
3. ROOMS AND ENCLOSED SPACES
a. INSTITUTIONAL 1-2 CLASS B
*CLASS C ON ADMINISTRATIVE SPACES
*CLASS C ON ROOMS WITH CAPACITY FOR FOUR PERSONS OR LESS.
AREA SMOKE COMPARTMENTS
S.F.
ARCHITECT:
BERMELLO AJAMIL & PARTNERS, INC.
Architecture Engineering Planning
inte6or DQsign Landscape Architecture
2601 9Q6th Bayshore Drive 10th Floor
Miami, Florida 33133
(305) 859-2050 Fax (305) 860-3700
LOUIS J. AGUIRRE & ASSOCIATES. PA
Consulting Engineers
9150 South Dodeland Blvd. • Suite 900
Miami • Florida 33156 • EB0000924
Telephone 305.670.0141
Facsimile 305.670.0144
www.iigaRo.com
x N1
Z4
6.5,7
PROJECT NAME:
SMH - LOBBY FLOOR REPLACEMENT
& GIFT SHOP RENOVATION
PROJECT ADDRESS:
7400 S.W. 62nd Ave.
South Miami, Florida 33143
COMM. NO. 40071.000
SCALE: AS SHOWN
DATE: 09-06-2013
DRAWN: JEC
CHECKED: BH
CADD FILE: KINSTITUTIONAL
DRAWING TITLE:
LIFE SAFETY
FIRST FLOOR
PLAN
SHEET NO.