13-1288-003TEMPORARY -
PARTITION SEE
DETAIL WALL
TYPE 71A3.1
0
[►LATH ICH2 R3 :T•7;7
F
TEMPORARY PARTITION WITH -
DOOR TO BE CONSTRUCTED
AFTER FLOOR IS INSTALLED.
PROVIDE TEMPORARY SIGN TO
READ: "CONSTRUCTION DO NOT
ENTER" ON PUBLIC SIDE. SEE
DETAIL WALL TYPE 71A3.1
b
<vi
PARTITION SEE
DETAIL WALL
TYPE 7/A3.1
I
GIs cr�
r
L_J
;0
z
TEMPORARY PARTITION WITH -
DOOR TO BE CONSTRUCTED
AFTER FLOOR IS INSTALLED.
PROVIDE TEMPORARY SIGN TO
READ: "CONSTRUCTION DO NOT
ENTER" ON PUBLIC SIDE. SEE
DETAIL WALL TYPE 71A3.1
GIFT •-
��- � _ f , f. :� fffffFFfflfff /ff /lfFI1Nf. % A %i'N.! ffflfffR
�11�11
e
t
r
r
t
i
U
r�
TEMPORARY -
PARTITION SEE
CORRIDOR DETAIL WALL
TYPE 7/A3.1
LIFE SAFETY GENERAL NOTES-
GENERAL LIFE SAFETY CRITERIA
A. CODES:
APPLICABLE CODES:
FLORIDA BUILDING CODE 2010
FLORIDA ACCESSIBILITY CODE 2012
• FLORIDA TEST PROTOCOLS (HIGH VELOCITY HURRICANE ZONES) 2010
• FLORIDA MECHANICAL CODE 2010
• FLORIDA PLUMBING CODE 2010
• FLORIDA GAS CODE 2010
• AIA GUIDELINES FOR DESIGN AND CONSTRUCTION OF
HOSPITALS AND HEALTH CARE FACILITIES - 2010 EDITION
• FLORIDA FIRE PREVENTION CODE/NFPA 101 - 2009 CHAPTER 19, EXISTING HEALTH
CARE
OCCUPANCIES
• NFPA 70 - 2008
NFPA 253 - 2006
NFPA 13 - 2007 STANDARD FOR INSTALLATION OF SPRINKLER SYSTEM
* NFPA 14 - 2007 STANDARD FOR THE INSTAWl71ON OF STANDPIPE. PRIVATE
HYDRANTS, AND HOSE SYSTEMS.
• NFPA 72 - 2007 (NEC) NATIONAL FIRE ALARM CODE.
B. OCCUPANCY:
OCCUPANCY TYPE:
• INSTITUTIONAL (FLORIDA BUILDING CODE 2010 - SECTION
308.3 GROUP 1 -2)
C. CLASSIFICATION:
BUILDING CLASSIFICATION:
• TYPE I -A FULLY SPRINKLERED (FBC 2010) TABLE 601
• NFPA 220 - TYPE 1 (443)
D. BUILDING TYPE: (CLASSIFIED BY TYPE OF CONSTRUCTION)
FBC SEC. 5
C F47EPJA OUTLINED BELOW IS TYPICAL FOR ALL OCCUPANCIES AND BASED UPON
CRITERIA OF A FULLY
SPRINKLERED BUILDING.
1. TYPE OF CONSTRUCTION: (TYPE I -A) FULLY SPRINKLERED IN ACCORDANCE WITH
903.3.1
2. STRUCTURE OF EXISTING (I -A) = FBC EXISTING BUILDINGS: CHAPTER 4 (407 AND
419)
3. ALLOWABLE HEIGHT- UNUMITED (FBC TABLE 503)
4. MAX NO. OF STORIES = UNLIMITED (FBC TABLE 503)
5. ALLOWABLE BUILDING AREA = UNLIMITED (TABLE 503)
E. OCCUPANCY LOAD: FBC SEC. 10 (TABLE 1004.1.1)/NFPA
TABLE 7.3.1.2
1. PRIMARY OCCUPANCY (INSTITUTIONAL - INPATIENT TREATMENI). 240 SF GROSS
2. ACCESSORY OCCUPANCY (INSTITUTIONAL - OUTPATIENT AREAS): 100 SF GROSS
3. ACCESSORY OCCUPANCY (BUSINESS) 100 SF GROSS
4. ACCESSORY OCCUPANCY (ASSEMBLY - 2) 15 SIR
G. TRAVEL DISTANCES / EXIT WIDTHS REQUIREMENTS:
(FBC SEC. 10)
THE REQUIREMENTS OUTLINED BELOW ARE BASED ON A FULLY SPRINKLERED
BUILDING AND APPLICABLE OCCUPANT TYPES.
1. ALLOWABLE TRAVEL DISTANCES BY OCCUPANCY(FBC 1016.1 INSTITUTIONAL (1 -2)
a MAX TRAVEL DISTANCE TO EXIT 200 FT. (FBC TABLE
1016.1).
b. MAX TRAVEL DISTANCE TO EXIT FROM RM DOOR. 150 FT.
(NFPA 101)
c. MAX DEAD END CORRIDOR : 20 FT. (FBC 1018.4/20 NFPA
19.25.2
d. MAX COMMON PATH OF TRAVEL- 75 FT./50 NFPA 101
2 EGRESS WIDTHS:
a LEVEL EXIT. 0.2 IN. PER PERSON (FBC 1005.1)
b. STAIRS: 0.3 IN. PER PERSON (FBC 1005.1)
c. MIN. CORRIDOR WIDTH: 44 IN. (FBC 1018.2)
d. CLEAR OPENING DOOR EXaT. 32 IN. (FBC 1008.1.1)
a MIN. STAIR WIDTH 44 IN. (FBC 1009.1)
3. VERTICAL EXIT ENCLOSURES
a 1 HR. CONNECTING 3 STORIES OR LESS / 2 HR.
CONNECTING 4 OR MORE STORIES. (FBC 10221)
4. EXIT PASSAGEWAYS
a WIDTH - 44-K MIN. (FBC 1023.2)
b. CONSTRUCTION = 1 HR. MIN BUT NOT LESS THAN THAT
REQUIRED FOR ANY CONNECTING EXIT ENCLOSURES (FBC
1023.3)
c. OPENINGS AND PENETRATIONS = ONLY FROM EXIT ACCESS
FROM NORMALLY OCCUPIED SPACES. (1023.5) AS REQ. BY
FBC 715.
d. PENETRATIONS - NP EXCEPT WHEN SERVING EXIT
PASSAGEWAY
H. INTERIOR FINISHES: (FBc SEC. 8)
THE REQUIREMENTS OUTLINED BELOW ARE BASED UPON A FULLY SPRINKLERED
BUILDING AND APPLICABLE OCCUPANT TYPES.
CLASS A - FLAME SPREAD - 00-25 / SMOKE DEVELOPMENT - 0-450
CLASS B - FLAME SPREAD - 26-75 / SMOKE DEVELOPMENT - 0-450
CLASS C - FLAME SPREAD - 76- 200 / SMOKE DEVELOPMENT - 0-450
1. EDIT ENCLOSURES AND EXIT PASSAGEWAYS
a INSTITUTIONAL 1 -2: CLASS B
2 CORRIDORS
a INSTITUTIONAL 1 -2 CLASS B
3. ROOMS AND ENCLOSED SPACES
a INSTITUTIONAL 1 -2: CLASS B
•CLASS C ON ADMINISTRATIVE SPACES
*(LASS C ON ROOMS WITH CAPACITY FOR FOUR PERSONS OR LESS.
SYMBOL LEGEND
EXTERIOR AREAS: NOT PART OF
SCOPE
INTERIOR AREAS: NOT PART OF
SCOPE
►A
11: EXTE
LIATIy Y -
ARCHITECT:
BERMELLO AJAMIL & PARTNERS, INC.
Architecture Engineering Planning
Interior De3ign .andscape Architecture
2041, Gout�_Bajrshore Drive 10th Floor
Miami, Florida 33133
(305) 859 -2050 Fax (305) 860 -3700
LO
LOUIS J. AGUIRRE & ASSOCIATES. P.A.
Consulting Engineers
9150 South Dadelond Blvd. * Suite 900
Mlami • Florida 33158 * EB0000924
Telephone 305.870.0141
Facedmle 305.870.0144
Vim.
�u
a
C
6 5 7f4�"
CONSTRUCTION
DOCUMENTS
REVISIONS:
PROJECT NAME:
SMH - LOBBY FLOOR REPLACEMENT
& GIFT SHOP RENOVATION
PROJECT ADDRESS:
7400 S.W. 62nd Ave.;'
South Miami, Florida 33143
KEY PLAN
COMM. NO. 40071.000
SCALE: AS SHOWN
DATE: 08 -28 -2013
DRAWN: JEC
CHECKED: BH
CADD FILE: H:INSTITUnONAL
DRAWING TITLE:
LIFE SAFETY 1ST
FLR CONSTRUCTION
O
& CORRIDOR AREAS
SHEET NO.