13-1221-02941000 SMH MAB FIRE ALARM PANEL 4100es FACP Standby Total Alarm Total Module Qty Description Current Standby Current Alarm Panel Equipment 4100 -9111 1 4100 CONFIG. DOMESTIC 120V * 0.3730 0,3730 0.4700 0.4700 4100 -3105 1 IDNET MODULE, UP TO 64 POINTS * 0.0750 0.0750 0.1150 0.1150 4100 -5111 2 SYSTEM POWER SUPPLY (SPS) - 120VAC 60HZ 0.1750 0.3500 0.1850 0.3700 4100 -6052 1 EVENT REPORTING DACT 0.0300 0.0300 0.0400 0.0400 4100 -0634 1 POWER DISTRIBUTION MODULE 120V 0.0000 0.0000 0,0000 0.0000 4100 -9620 1 BASIC AUDIO WITH MICROPHONE - ANALOG 0.2250 0.2250 0.2250 0.2250 4100 -1314 2 ANALOG 10OW AMP W/6 B NACS 120VAC 25V 0.0850 0.1700 3.8000 7.6000 4100 -1320 1 BACKUP 10OW AMP - 120VAC 25V 2 0.0850 0.0850 0.0000 0.0000 4100 -1240 1 AUXILIARY AUDIO INPUT BOARD 0.0100 0.0100 0.0100 0.0100 4100 -1252 1 1 CHANNEL AUDIO OPERATOR INTERFACE 0.0000 0.0000 1 0.0240 0.0240 4100 -1280 1 1 8 SWITCH, 8 RED LED MODULE 0.0000 0.0000 0.0240 0.0240 4100 -1288 1 64/64 LED /SWITCH CONTROLLER 0.0200 0.0200 0.0200 0.0200 4100 -96xx 14 REMOTE ANNUNCIATORS & MINIPLEX TRANSPONDERS RUI CURRENT DRAWS INCLUDED BELOW Panel Totals 1.3380 8.8980 IDNet Addressable Devices SLC 4099 -9001 51 IDNET SINGLE ACTION PULL STATION * 0.0000 0.0000 0.0000 0.0000 4090 -9001 59 IDNET SUPERVISED IAM * 0.0000 0.0000 0.0000 0.0000 4090 -9002 25 IDNET RELAY IAM * 0,0000 0,0000 0.0000 0.0000 4090 -9007 1 IDNET ADDRESSABLE SIGNAL ZAM * 0,0000 0.0000 0.0000 0.0000 4090 -9118 134 RELAY IDNET 2 IAM W/T SENSE * 0.0000 0.0000 0.0000 0.0000 4098 -9714 283 TRUEALARM PHOTO SMOKE SENSOR 0.0000 0,0000 0.0000 0.0000 4098 -9733 17 TRUEALARM HEAT SENSOR 0.0000 0.0000 0.0000 0.0000 4098 -9756 14 TRUEALARM DUCT SMOKE SENSOR W/ RELAY OUTPUT * 0.0000 0.0000 0.0000 0.0000 4009 -9201 17 4009 IDNET NAC EXTENDER, 120 VAC * 0.0000 0.0000 0.0000 0.0000 4098 -9791 2 TRUEALARM SENSOR BASE W/ RELAY DRIVER * 0.0000 0.0000 0.0000 0.0000 4098 -9792 298 TRUEALARM SENSOR BASE * 0.0000 0.0000 1 0.0000 1 0.0000 Miscellaneous Peripheral Devices That May Require System Power 4098 -9843 14 ENCAPSULATED RELAY PAM -SD 0.0000 0.0000 0.0150 0.2100 2098 -9737 2 RELAY DPDT 3 AMP 0.0000 0.0000 0.0240 0.0480 4098 -9756 14 TRUEALARM DUCT SMOKE SENSOR W/ RELAY OUTPUT 0.0030 0.0420 0.0150 0.2100 4098 -9791 2 TRUEALARM SENSOR BASE W/ RELAY DRIVER 0.0003 0.0005 0.0040 0.0080 4603 -9101 14 SERIAL LCD ANNUNCIATOR 0.0650 0.9100 0.1400 1.9600 Notification Appliances ' 4009 -9201 1 4009 IDNET NAC EXTENDER, 120 VAC * 0.0000 0.0000 0.0150 0.0150 4906 -9127 3 A/V MC NON- ADDRESS, RED, WALL 75 0.0000 0.0000 0.2210 0.6630 ELW 6 ELEVATOR WARNING A OR ARN NG LIGHT 0.0000 0.0000 0.0400 0.2400 EX -SIG10 1 EXISTING SIGNAL CIRCUIT 7 LOAD 0.0000 0.0000 0.5350 0.5350 EX -SIG11 1 EXISTING SIGNAL CIRCUIT 8 LOAD 0.0000 0.0000 0.5350 0.5350 Peripheral Totals 0.9525 4.4240 RUI Totals 28 0.0980 0.0980 Address Totals 602 Addresses 0.4791 0.5959 * Additional Current included under ''Device Addresses Used" (See below under "Additional Current Draws:") 1. 2 -wire detector alarm current is included in the alarm current of the Initiating Device Circuit. 2. Backup Amplifier assumes Main Amplifier alarm current on failure. Battery Set #1 (Cabinet /Charger #1) Select ALL Power Supplies on this battery set: SPS -1 SPS -2 SPS -3 Additional Current Draws: RUI Connected Peripheral Devices 28 MAPNET /IDNet Device Addresses ordered / used 602 Spare addressable point capacity 0% Total Standbyl 2.8676 Total Alarml 14.0159 Standby Standby Alarm Alarm Current Sub Total x 0.0035 x 0.000796 Sub Total 0 x 0.000796 Total Standby Time = 4 Hrs x 2.6976 Alarm Time = 15 Min 0.25 x 6.4159 Additional Spare Capacity = 20% Battery Discharge Factor = 20% Minimum Battery Required 2081 -9275 18AH (2x) Battery Supplied 2081 -9275 18AH (2x) Battery Set #2 (Cabinet /Charger #2) Select ALL Power Supplies on this battery set: AMP -1 AMP -2 Additional Current Draws: MAPNET /IDNet Device Addresses ordered / used 0 Spare addressable point capacity 0% Total Current Total 1.2505 2.4440 0.4350 1.8550 0.4350 1.4230 2.1205 5.7220 = 0.0980 x 0.0035 = 0.0980 = 0.4791 x 0.000990 = 0.5959 2.6976 6.4159 = 0.0000 x 0.00099 = 0.0000 2.6976 6.4159 10.7906 Standby Ah 1.6040 Alarm Ah 12.3945 + 2.9747 17.8481 Standby Standby Alarm Alarm Current Sub Total x 0.000796 Sub Total 0 x 0.000796 Standby Time = 4 Hrs x 0.1700 Alarm Time = 15 Min 0.25 x 7.6 Additional Spare Capacity = 20% PROVISIONS TO CONFORM TO NEC 760 POWER- LIMITED AND NON- DIRECTLY CONNECTED TO THE INPUT CIRCUIT. S Battery Discharge Factor = 20% OR FACP Minimum Battery Required 2081 -9272 6.2AH (2x) Battery Supplied 2081 -9272 6.2AH (2x) 6.81K (NORMAL), 16.9K (OPEN), 1.65K (CURRENT- LIMITED) % 845 OHMS (SHORTED). ® C SEE NOTES WIRING IF NON - POWER -LIMITED WIRING IS USED ON THE RELAY OUTPUT. CLOSED BEYOND A SERIES CONNECTED CURRENT F 10.7906 Standby Ah 1.6040 Alarm Ah 12.3945 + 2.9747 17.8481 Standby Standby Alarm Alarm Current Sub Total x 0.000796 Sub Total 0 x 0.000796 Standby Time = 4 Hrs x 0.1700 Alarm Time = 15 Min 0.25 x 7.6 Additional Spare Capacity = 20% PROVISIONS TO CONFORM TO NEC 760 POWER- LIMITED AND NON- DIRECTLY CONNECTED TO THE INPUT CIRCUIT. S Battery Discharge Factor = 20% OR FACP Minimum Battery Required 2081 -9272 6.2AH (2x) Battery Supplied 2081 -9272 6.2AH (2x) N Cl) w 'S Total + Total Current Total 0.085 3.8000 0.085 3.8000 0.1700 7.6000 = 0.0000 x 0.000990 = 0.0000 0.1700 7.6000 = 0.0000 x 0.00099 = 0.0000 0.1700 7.6000 0.6800 Standby Ah 1.9000 Alarm Ah 2.5800 + 0.6192 3.7152 @UGL p,SS1Fj� us FILL VOID On CAVITY MATERIALS CLASSIFIED BY VNDERWPITERS LABORATORIES, INC 0 FOR USE IN THROUGH -PENET RATIOI l FIRESTOP SYSTEMS p(HEZI. SEE CURRENT UL FIFE RESISTANCE DIRECTORY 6CL6, 900,0 System No.W -L -1228 June28,2010 F Rating - 1 and 2 Hr (See Item 1) T Rating - 0, 1/2 and 1 Hr (See Item 3) L Rating At Ambient - Less Than 1 CFM /sq ft L Rating At 400 F - 2 CFM /sq ft 1. Wall Assembly The 1 or 2 hr fire rated gypsum board /stud wall assembly shall be constructed of the materials and In the manner described In the individual U400 or V400 series Wall and Partition Design in the UL Fire Resistance Directory and shall Include the following construction features: A. Studs- Wall framing shall consist of min 3 -5/8 in. (92 mm) wide steel channel studs spaced max 24 in. (610 mm) OC. B. Gypsum Board• Thickness, type, number of layers and fasteners shall be as specified In the Individual U400 or V400 series Wall and Partition Design In the UL Fire Resistance Directory. Max area of opening Is 67 -1/2 sq. in. (435 sq cm) with max dimension of 22 -1/2 in. (572 mm). The hour) F Rating of he fir estop g t estop system Is equal to the hourly Dre rating of the wall assembly in which it is Installed. 2. Through Penetrant One or more nom 2 in 1 di am e . (5 mm) d am (or smaller) rigid steel conduit or electrical metallic tubing (EMT) Installed either concentrically or eccentrically within the Orestop system. The annular space between conduits or tubing a n d periphery ry of opening shall be nt;l 0 In. (0 mm, point contact) to max 1 -1/4 In. (32 mm). The space between conduits or tubing shall be min 1/4 In.(6 mm) to max 1 In. (25mm). Conduit or tubing rigidly g to be supported on both sides of wall assembly. 3. FIII,Void or Cavity Material* - Caulk or Seahlht 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall. Min 1/2 in. (13 mm) dlam bead of caulk applied to the penetrant /gypsum board Interface at the point contact location on both sides of wall. The hourly T Rating of the firestop system Is 0 Hr when used In 1 Hr rated assemblies. The T Rating for 2 Hr rated assemblies is 1/2 and 1 Hr for FireDam 150+ and IC 15WB and Is 1 Hr for CP- 25WB+ and FB -300 WT. 3M COMPANY - CP 25WB+ FireDam 150+ I 1 WB+ ' C 5 caulk or FB -3000 WT sealant. *Bearing the UL Classification Mark * NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2011 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. ' 0,1 @UL us FILL VOID OR CAVITY MATERIALS CLASSIFIED BY VNDERWHITEnS LABORATORIES, INCM THROUGH -PENS FIRESTOP SYSTEI SEE CURRENT RESISTANCE DIG 6OL6 DOC System No.W -L -3001 September 07, 2004 (Formerly System No. 149) F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 3/4, 1, 1 -1/2 and 2 Hr (See Item 2) L Rating At Ambient - 15 CFM /sq ft (See Item 3) L Rating At 400 F - less than 1 CFM /sq ft (See Item 3) SECTION A -A 1. Wall Assembly - The 1 or 2 hr nre-rated gypsum wallboard /stud wall assembly shall be constructed of the materials and In the manner described In the Individual U3DO or U400 Series Wall or Partition Designs In the UL Fire Resistance Directory and shall induce the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 In. lumber spaced 161n. OC with nom 2 by 4 In. lumber end plates and Goss braces. Steel studs to be min 3 -5/8 In. wide by 1- 3/81n. deep channels spaced max 24 In OC. B. Gypsum Board* .- Nom 1/2 or 5/8 In. thick, 4 R wide with square or tapered edges. The gypsum 1 wallboard type, thicknesse numbep of layers and sheet orientation shall be as specified In the Individual Wall or Partition Desl n. Diem of circular through opening o t be 3 e In, to 5 e In. larger than outside 9 9 P 9 / / e r9 dram of cable or cable bundle. C. Fasteners - When wood stud framing Is employed gypsum wallboard layers attached to studs with cement coated nails as specified In the individual Wall or Partition Design. When steel channel stud framing is employed, gypsum wallboard attached to studs with Type S self - drilling, self - tapping bugle -head steel screws as specified In the Individual Wall or Partition Design. The hourly F Rating of the flrestop system Is equal to the hourly fire rating of the wall assembly In which It Is Installed. 2. Cables - Individual cable or max 1 In. diem cable bundle Installed In through opening with an annular space of min O In. (point contact) to max 3/4 In. Cable to be rigidly supported on both sides of wall assembly. The following types and sizes of cables may be used: A. Max 150 pair No. 24 AWG copper conductor telephone cable with polyvinyl chloride (PVC Insulation and Jacket materials. When max 25 pair telephone cable Is used, T Rating Is 2 hr.When 50 to 150 pair telephone cable Is used In 1 hr nre rated wall, T Rating Is 314 hr When 50 to 150 pair telephone cable Is used In 2 hr fire rated wall, T Rating Is 1 hr. B. Max No. 10 AWG multiple copper conductor Type NM ( "Romex" ) nonmetallic sheathed cable with PVC Insulation and Jacket materials. When Type NM cable Is used, max T Rating Is 1 -1/2 hr. C. Multiple fiber optical communication cable Jacketed with PVC and having a max outside diem of 5/8 In. When fiber optic cable Is used, max T Rating Is 2 hr. D. Max 12 AWG multi conductor (max seven conductors) power /control cable with cross - linked polyethylene (XLPE) Insulation and XLPE or PVC Jacket materials. When multi conductor power /control cable Is used, max T Rating is 2 hr. • E. Max four conductor with ground No. 2 AWG (or smaller) aluminum SER cables with polyvinyl 1 • 61 1 1 1 chloride Insulation and Jacket in terlals. 3. FlII,Vold or Cavity Materials* - Caulk, Sealant or Putty - Caulk or putty fill material Installed to completely fill annular space between cable and gypsum wallboard on both sides of wall and with a min 1/4 in. clam bead of caulk or putty applied to perimeter of cable(s) at Its egress from each side of the wall. 3M COMPANY - MP+ Stlx putty, CP 25WB+ caulk, FB -3000 WT sealant or Cable Wrap putty (Note: L Ratings apply only when CP 25WB+ caulk or FB -3000 WT sealant Is used.) *Bearing the UL Classlncatlon Mark * NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2011 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. PRODUCT INFORMATION 4090-9118 RELAY IAM (INDIVIDUAL ADDRESSABLE MODULE) WITH T -SENSE INPUT FEATURES: • UL LISTED STANDARD 864 SPECIFICATIONS: • DUAL -POINT OPERATION PROVIDES A SUPERVISED • WIRE CONNECTIONS: SCREW TERMINALS FOR IN OUT WIRING MULTI -STATE INPUT AND A RELAY OUTPUT IN A FOR WIRE FROM 118 TO �14 AWG SINGLE PACKAGE USING ONLY ONE ADDRESS: 8 W X 1 3 H X 4 1 8 " 4 1 8 - TYPICAL APPLICATIONS ARE FOR DAMPER MOTOR • DIMENSIONS: / / / "D CONTROL WITH DUAL POSITION FEEDBACK • TEMPERATURE RANGE: 3Z'F TO 1207 (INDOOR OPERATION ONLY) MONITORING (OPEN AND CLOSED) • HUMIDITY: 10 TO 90% RH 0 90'F (32-C) #8/32 PANHEAD SCREW - FOR USE WITH 4100 PANELS WITH A REVISION •SUPERVISION RESISTOR: REFER TO INSTALLATION INSTRUCTIONS (NOT SUPPLIED) - 11 OR HIGHER AND PROVIDING IDNET 574 -874 FOR ADDITIONAL INFORMATION COMMUNICATIONS AND WIRING DETAIL COVER • INPUT REQUIREMENTS: • INPUT /OUTPUT DETAILS: - NORMALLY OPEN DRY CONTACTS ( NOT SUPPLIED) - INPUT OPERATION IS "T- SENSE" AND PROVIDES • HOUSING MATERIAL - SUPERVISED MONITORING OF NORMALLY - BLACK THERMOPLASTIC OPEN, DRY CONTACTS (a - TOTAL WIRING DISTANCE TO SUPERVISED DESCRIPTION: CONTACTS IS UP TO 50OFT (152M); FOR • SINGLE ADDRESS DUAL POINT MODULE: INDOOR WIRING APPLICATIONS - 4090 -9118 RELAY IAM WITH T -SENSE ALLOWS A - BOTH DATA AND POWER ARE PROVIDED BY THE 4100 IDNET COMMUNICATION CHANNEL TO MONITOR i 0 IDNET COMMUNICATION LINK OVER A SINGLE TWO INPUT CONTACT CLOSURES WITH ONE POINT WIRE PAIR AND CONTROL AN OUTPUT RELAY WITH THE OTHER - FORM C RELAY OUTPUT IS RATED 2A 0 3OVDC POINT, BOTH FROM A COMPACT MODULE AND 1/2A 0 120VAC (RESISTIVE RATINGS) REQUIRING A SINGLE ADDRESS. IDNET COMMUMCATIONSER IS ® ® 0 •COMPACT, SEALED CONSTRUCTION: CHANNEL ELIMINATING THE NEED FOR �f - MINIMIZES DUST FILTRATION SEPARATE POWER WIRING. - VISIBLE LED FLASHES TO INDICATE COMMUNICATION • MULTI -POINT DEVICE DESCRIPTION: (� 4090 -9118 WIRING NOTES: -THE INPUT CIRCUIT AND RELAY OPERATION ARE i RELAY IAM WITH T -SENSE 1. MAXIMUM ALLOWABLE RUN FROM FACP TO FARTHEST DEVICE IS CONTROLLED INDEPENDENTLY AND MAY BE NOT TO EXCEED 2,500 FEET (762M). MAXIMUM TOTAL WIRE DISABLED SEPARATELY. POINT ASSOCIATION IS DETERMINED AT THE 4100 HOST PANEL i (INCLUDING ALL T -TAPS) FROM FACP IS 10,000 FEET (3,048M). AT THE 4100 HOST DISPLAY, THE DEVICE Ra IDNET LINES ARE 18 AWG TWISTED PAIR (SHIELDED RECOMMENDED). ADDRESS IS DESIGNATED AS A SINGLE HARDWARE � i WHEN USING SHIELD, WIRE NUT, SPLICE, OR SOLDER THE LOCATION. THE INDIVIDUAL POINTS ARE SHIELD WIRES. ALSO INSULATE SHIELD FROM THE ELECTRICAL BOX. CONSIDERED "SUB - POINTS" AND ARE LAYERED 2. THE RELAY IAM WITH T -SENSE COUNTS AS A ONE -UNIT LOAD. UNDERNEATH. X6/32 FLATHEAD SCREW 3. IDNET WIRING IS SUPERVISED AND POWER- LIMITED. AN IDNET CIRCUIT + ' . r (NOT SUPPLIED) HAS A COMMUNICATIONS POWER RATING OF 36.25 VOLTS (MAXIMUM) AT .5A, 3333 BAUD. T- SENSING OPERATION: 4. CONTRACTOR WIRING TO RELAY CONTACTS IS UNSUPERVISED. WIRE TO • SUPERVISED INPUT: LOCAL CODE 14 AWG RECOMMENDED WITH 12 AWG MAXIMUM). RELAY - 4090 -9118 RELAY IAM WITH T -SENSE HAS A CONTACTS AR RATED FOR 2 A(1 A FOR INDUCTIVE LOAD), 30 VDC AND SUPERVISED INPUT THAT MONITORS FOR CONTINUITY .5 A (0.25 A FOR INDUCTIVE LOAD), 120 VAX (NON -POWER TO AN END -OF -LINE RESISTOR AND CAN DIFFERENTIATE LIMITED). FOR POWER- LIMITED OPERATION, POWER MUST BE PROVIDED BETWEEN A SHORT CIRCUIT CONTACT CLOSURE AND A FROM A POWER- LIMITED AUXILIARY POWER OUTPUT FROM THE FACP CURRENT LIMITED CONTACT CLOSURE. OR FROM A POWER- LIMTED OUTPUT OF A POWER SUPPLY LISTED FOR • FOUR STATE OPERATION: 1.8K 1/2W SEE NOTE 6 FIRE PROTECTIVE SIGNALING USE. WHEN BOTH POWER- LIMITED AND - NORMAL IS WHEN ALL CONTACTS ARE OPEN AND THERE (733 - 84) NON - POWER- LIMITED SOURCES ARE PRESENT, USE TYPE FPL, IS CONTINUITY TO THE END -OF -LINE RESISTOR. FPLR, OR FPLP POWER- LIMITED CABLE POWER FOR POWER- LIMITED - OPEN IS WHEN CONTINUITY DOES NOT EXIST TO THE END -OF -LINE 4.7K 1 2W CIRCUITS F T E RESISTOR CAUSING A TR LE NIT / U\p,SSlFjFo UL us FILL VOID OR CAVITY MATERIALS CLASSIFIED BY VNOEfi4TRITERS LABORATORIES, ]NCO FOR USE IN THROUGH - PENETRATION FIRESTOP SYSTEMS (XHEZI. SEE CURRENT UL FIRE RESSTANCE DIRECTOHf 60L6, 9004 UL-LISTED SQUARE BOX DEEP BACK BOX )T SUPPLIED) I H RELAY IS USED TO CONTROL A FIRE SAFETY FUNCTION, OUB CO D ION. IT MUST BE WIRED WITHIN 3 FEET OF THE CONTROLLED DEVICE. - SHORT, INDICATES THAT A CONTACT HAS CLOSED THAT IS 733 -886 ® ® ® NORMALLY OPEN (N /0) DRY CONTACTS ARE ALLOWED ON THE ® N N.C. PROVISIONS TO CONFORM TO NEC 760 POWER- LIMITED AND NON- DIRECTLY CONNECTED TO THE INPUT CIRCUIT. S ARE PULLED UP TO 5VDC B1( A 17AK RESISTOR, WHICHI CAN I OR FACP SOURCE UP TO 284 uA (SUPERVISED AND POWER - LIMITED). T- SENSE! 11 = 0.0000 x 0.00099 = 0.0000 0.1700 7.6000 0.6800 Standby Ah 1.9000 Alarm Ah 2.5800 + 0.6192 3.7152 @UGL p,SS1Fj� us FILL VOID On CAVITY MATERIALS CLASSIFIED BY VNDERWPITERS LABORATORIES, INC 0 FOR USE IN THROUGH -PENET RATIOI l FIRESTOP SYSTEMS p(HEZI. SEE CURRENT UL FIFE RESISTANCE DIRECTORY 6CL6, 900,0 System No.W -L -1228 June28,2010 F Rating - 1 and 2 Hr (See Item 1) T Rating - 0, 1/2 and 1 Hr (See Item 3) L Rating At Ambient - Less Than 1 CFM /sq ft L Rating At 400 F - 2 CFM /sq ft 1. Wall Assembly The 1 or 2 hr fire rated gypsum board /stud wall assembly shall be constructed of the materials and In the manner described In the individual U400 or V400 series Wall and Partition Design in the UL Fire Resistance Directory and shall Include the following construction features: A. Studs- Wall framing shall consist of min 3 -5/8 in. (92 mm) wide steel channel studs spaced max 24 in. (610 mm) OC. B. Gypsum Board• Thickness, type, number of layers and fasteners shall be as specified In the Individual U400 or V400 series Wall and Partition Design In the UL Fire Resistance Directory. Max area of opening Is 67 -1/2 sq. in. (435 sq cm) with max dimension of 22 -1/2 in. (572 mm). The hour) F Rating of he fir estop g t estop system Is equal to the hourly Dre rating of the wall assembly in which it is Installed. 2. Through Penetrant One or more nom 2 in 1 di am e . (5 mm) d am (or smaller) rigid steel conduit or electrical metallic tubing (EMT) Installed either concentrically or eccentrically within the Orestop system. The annular space between conduits or tubing a n d periphery ry of opening shall be nt;l 0 In. (0 mm, point contact) to max 1 -1/4 In. (32 mm). The space between conduits or tubing shall be min 1/4 In.(6 mm) to max 1 In. (25mm). Conduit or tubing rigidly g to be supported on both sides of wall assembly. 3. FIII,Void or Cavity Material* - Caulk or Seahlht 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of wall. Min 1/2 in. (13 mm) dlam bead of caulk applied to the penetrant /gypsum board Interface at the point contact location on both sides of wall. The hourly T Rating of the firestop system Is 0 Hr when used In 1 Hr rated assemblies. The T Rating for 2 Hr rated assemblies is 1/2 and 1 Hr for FireDam 150+ and IC 15WB and Is 1 Hr for CP- 25WB+ and FB -300 WT. 3M COMPANY - CP 25WB+ FireDam 150+ I 1 WB+ ' C 5 caulk or FB -3000 WT sealant. *Bearing the UL Classification Mark * NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2011 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. ' 0,1 @UL us FILL VOID OR CAVITY MATERIALS CLASSIFIED BY VNDERWHITEnS LABORATORIES, INCM THROUGH -PENS FIRESTOP SYSTEI SEE CURRENT RESISTANCE DIG 6OL6 DOC System No.W -L -3001 September 07, 2004 (Formerly System No. 149) F Ratings - 1 and 2 Hr (See Item 1) T Ratings - 3/4, 1, 1 -1/2 and 2 Hr (See Item 2) L Rating At Ambient - 15 CFM /sq ft (See Item 3) L Rating At 400 F - less than 1 CFM /sq ft (See Item 3) SECTION A -A 1. Wall Assembly - The 1 or 2 hr nre-rated gypsum wallboard /stud wall assembly shall be constructed of the materials and In the manner described In the Individual U3DO or U400 Series Wall or Partition Designs In the UL Fire Resistance Directory and shall induce the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 In. lumber spaced 161n. OC with nom 2 by 4 In. lumber end plates and Goss braces. Steel studs to be min 3 -5/8 In. wide by 1- 3/81n. deep channels spaced max 24 In OC. B. Gypsum Board* .- Nom 1/2 or 5/8 In. thick, 4 R wide with square or tapered edges. The gypsum 1 wallboard type, thicknesse numbep of layers and sheet orientation shall be as specified In the Individual Wall or Partition Desl n. Diem of circular through opening o t be 3 e In, to 5 e In. larger than outside 9 9 P 9 / / e r9 dram of cable or cable bundle. C. Fasteners - When wood stud framing Is employed gypsum wallboard layers attached to studs with cement coated nails as specified In the individual Wall or Partition Design. When steel channel stud framing is employed, gypsum wallboard attached to studs with Type S self - drilling, self - tapping bugle -head steel screws as specified In the Individual Wall or Partition Design. The hourly F Rating of the flrestop system Is equal to the hourly fire rating of the wall assembly In which It Is Installed. 2. Cables - Individual cable or max 1 In. diem cable bundle Installed In through opening with an annular space of min O In. (point contact) to max 3/4 In. Cable to be rigidly supported on both sides of wall assembly. The following types and sizes of cables may be used: A. Max 150 pair No. 24 AWG copper conductor telephone cable with polyvinyl chloride (PVC Insulation and Jacket materials. When max 25 pair telephone cable Is used, T Rating Is 2 hr.When 50 to 150 pair telephone cable Is used In 1 hr nre rated wall, T Rating Is 314 hr When 50 to 150 pair telephone cable Is used In 2 hr fire rated wall, T Rating Is 1 hr. B. Max No. 10 AWG multiple copper conductor Type NM ( "Romex" ) nonmetallic sheathed cable with PVC Insulation and Jacket materials. When Type NM cable Is used, max T Rating Is 1 -1/2 hr. C. Multiple fiber optical communication cable Jacketed with PVC and having a max outside diem of 5/8 In. When fiber optic cable Is used, max T Rating Is 2 hr. D. Max 12 AWG multi conductor (max seven conductors) power /control cable with cross - linked polyethylene (XLPE) Insulation and XLPE or PVC Jacket materials. When multi conductor power /control cable Is used, max T Rating is 2 hr. • E. Max four conductor with ground No. 2 AWG (or smaller) aluminum SER cables with polyvinyl 1 • 61 1 1 1 chloride Insulation and Jacket in terlals. 3. FlII,Vold or Cavity Materials* - Caulk, Sealant or Putty - Caulk or putty fill material Installed to completely fill annular space between cable and gypsum wallboard on both sides of wall and with a min 1/4 in. clam bead of caulk or putty applied to perimeter of cable(s) at Its egress from each side of the wall. 3M COMPANY - MP+ Stlx putty, CP 25WB+ caulk, FB -3000 WT sealant or Cable Wrap putty (Note: L Ratings apply only when CP 25WB+ caulk or FB -3000 WT sealant Is used.) *Bearing the UL Classlncatlon Mark * NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2011 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. PRODUCT INFORMATION 4090-9118 RELAY IAM (INDIVIDUAL ADDRESSABLE MODULE) WITH T -SENSE INPUT FEATURES: • UL LISTED STANDARD 864 SPECIFICATIONS: • DUAL -POINT OPERATION PROVIDES A SUPERVISED • WIRE CONNECTIONS: SCREW TERMINALS FOR IN OUT WIRING MULTI -STATE INPUT AND A RELAY OUTPUT IN A FOR WIRE FROM 118 TO �14 AWG SINGLE PACKAGE USING ONLY ONE ADDRESS: 8 W X 1 3 H X 4 1 8 " 4 1 8 - TYPICAL APPLICATIONS ARE FOR DAMPER MOTOR • DIMENSIONS: / / / "D CONTROL WITH DUAL POSITION FEEDBACK • TEMPERATURE RANGE: 3Z'F TO 1207 (INDOOR OPERATION ONLY) MONITORING (OPEN AND CLOSED) • HUMIDITY: 10 TO 90% RH 0 90'F (32-C) #8/32 PANHEAD SCREW - FOR USE WITH 4100 PANELS WITH A REVISION •SUPERVISION RESISTOR: REFER TO INSTALLATION INSTRUCTIONS (NOT SUPPLIED) - 11 OR HIGHER AND PROVIDING IDNET 574 -874 FOR ADDITIONAL INFORMATION COMMUNICATIONS AND WIRING DETAIL COVER • INPUT REQUIREMENTS: • INPUT /OUTPUT DETAILS: - NORMALLY OPEN DRY CONTACTS ( NOT SUPPLIED) - INPUT OPERATION IS "T- SENSE" AND PROVIDES • HOUSING MATERIAL - SUPERVISED MONITORING OF NORMALLY - BLACK THERMOPLASTIC OPEN, DRY CONTACTS (a - TOTAL WIRING DISTANCE TO SUPERVISED DESCRIPTION: CONTACTS IS UP TO 50OFT (152M); FOR • SINGLE ADDRESS DUAL POINT MODULE: INDOOR WIRING APPLICATIONS - 4090 -9118 RELAY IAM WITH T -SENSE ALLOWS A - BOTH DATA AND POWER ARE PROVIDED BY THE 4100 IDNET COMMUNICATION CHANNEL TO MONITOR i 0 IDNET COMMUNICATION LINK OVER A SINGLE TWO INPUT CONTACT CLOSURES WITH ONE POINT WIRE PAIR AND CONTROL AN OUTPUT RELAY WITH THE OTHER - FORM C RELAY OUTPUT IS RATED 2A 0 3OVDC POINT, BOTH FROM A COMPACT MODULE AND 1/2A 0 120VAC (RESISTIVE RATINGS) REQUIRING A SINGLE ADDRESS. IDNET COMMUMCATIONSER IS ® ® 0 •COMPACT, SEALED CONSTRUCTION: CHANNEL ELIMINATING THE NEED FOR �f - MINIMIZES DUST FILTRATION SEPARATE POWER WIRING. - VISIBLE LED FLASHES TO INDICATE COMMUNICATION • MULTI -POINT DEVICE DESCRIPTION: (� 4090 -9118 WIRING NOTES: -THE INPUT CIRCUIT AND RELAY OPERATION ARE i RELAY IAM WITH T -SENSE 1. MAXIMUM ALLOWABLE RUN FROM FACP TO FARTHEST DEVICE IS CONTROLLED INDEPENDENTLY AND MAY BE NOT TO EXCEED 2,500 FEET (762M). MAXIMUM TOTAL WIRE DISABLED SEPARATELY. POINT ASSOCIATION IS DETERMINED AT THE 4100 HOST PANEL i (INCLUDING ALL T -TAPS) FROM FACP IS 10,000 FEET (3,048M). AT THE 4100 HOST DISPLAY, THE DEVICE Ra IDNET LINES ARE 18 AWG TWISTED PAIR (SHIELDED RECOMMENDED). ADDRESS IS DESIGNATED AS A SINGLE HARDWARE � i WHEN USING SHIELD, WIRE NUT, SPLICE, OR SOLDER THE LOCATION. THE INDIVIDUAL POINTS ARE SHIELD WIRES. ALSO INSULATE SHIELD FROM THE ELECTRICAL BOX. CONSIDERED "SUB - POINTS" AND ARE LAYERED 2. THE RELAY IAM WITH T -SENSE COUNTS AS A ONE -UNIT LOAD. UNDERNEATH. X6/32 FLATHEAD SCREW 3. IDNET WIRING IS SUPERVISED AND POWER- LIMITED. AN IDNET CIRCUIT + ' . r (NOT SUPPLIED) HAS A COMMUNICATIONS POWER RATING OF 36.25 VOLTS (MAXIMUM) AT .5A, 3333 BAUD. T- SENSING OPERATION: 4. CONTRACTOR WIRING TO RELAY CONTACTS IS UNSUPERVISED. WIRE TO • SUPERVISED INPUT: LOCAL CODE 14 AWG RECOMMENDED WITH 12 AWG MAXIMUM). RELAY - 4090 -9118 RELAY IAM WITH T -SENSE HAS A CONTACTS AR RATED FOR 2 A(1 A FOR INDUCTIVE LOAD), 30 VDC AND SUPERVISED INPUT THAT MONITORS FOR CONTINUITY .5 A (0.25 A FOR INDUCTIVE LOAD), 120 VAX (NON -POWER TO AN END -OF -LINE RESISTOR AND CAN DIFFERENTIATE LIMITED). FOR POWER- LIMITED OPERATION, POWER MUST BE PROVIDED BETWEEN A SHORT CIRCUIT CONTACT CLOSURE AND A FROM A POWER- LIMITED AUXILIARY POWER OUTPUT FROM THE FACP CURRENT LIMITED CONTACT CLOSURE. OR FROM A POWER- LIMTED OUTPUT OF A POWER SUPPLY LISTED FOR • FOUR STATE OPERATION: 1.8K 1/2W SEE NOTE 6 FIRE PROTECTIVE SIGNALING USE. WHEN BOTH POWER- LIMITED AND - NORMAL IS WHEN ALL CONTACTS ARE OPEN AND THERE (733 - 84) NON - POWER- LIMITED SOURCES ARE PRESENT, USE TYPE FPL, IS CONTINUITY TO THE END -OF -LINE RESISTOR. FPLR, OR FPLP POWER- LIMITED CABLE POWER FOR POWER- LIMITED - OPEN IS WHEN CONTINUITY DOES NOT EXIST TO THE END -OF -LINE 4.7K 1 2W CIRCUITS F T E RESISTOR CAUSING A TR LE NIT / U\p,SSlFjFo UL us FILL VOID OR CAVITY MATERIALS CLASSIFIED BY VNOEfi4TRITERS LABORATORIES, ]NCO FOR USE IN THROUGH - PENETRATION FIRESTOP SYSTEMS (XHEZI. SEE CURRENT UL FIRE RESSTANCE DIRECTOHf 60L6, 9004 UL-LISTED SQUARE BOX DEEP BACK BOX )T SUPPLIED) I H RELAY IS USED TO CONTROL A FIRE SAFETY FUNCTION, OUB CO D ION. IT MUST BE WIRED WITHIN 3 FEET OF THE CONTROLLED DEVICE. - SHORT, INDICATES THAT A CONTACT HAS CLOSED THAT IS 733 -886 ® ® ® NORMALLY OPEN (N /0) DRY CONTACTS ARE ALLOWED ON THE ® N N.C. PROVISIONS TO CONFORM TO NEC 760 POWER- LIMITED AND NON- DIRECTLY CONNECTED TO THE INPUT CIRCUIT. S ARE PULLED UP TO 5VDC B1( A 17AK RESISTOR, WHICHI CAN I OR FACP SOURCE UP TO 284 uA (SUPERVISED AND POWER - LIMITED). T- SENSE! 11 POWER- LIMITED WIRING SEPARATION MUST BE MADE IN THE FIELD - CURRENT LIMITED INDICATES THAT A CONTACT HAS ® ® ® 6.81K (NORMAL), 16.9K (OPEN), 1.65K (CURRENT- LIMITED) % 845 OHMS (SHORTED). ® C SEE NOTES WIRING IF NON - POWER -LIMITED WIRING IS USED ON THE RELAY OUTPUT. CLOSED BEYOND A SERIES CONNECTED CURRENT F 4 E FROM PREVIOUS LIMITING RESISTOR. THIS OPERATION ALLOWS IDNET + -R 5. IF AC IS USED ON RELAY TERMINALS, YOU MUST ADD LABEL 526 -631 DEVICE OR FACP IDNET - -B ® ® - ® N N.O. -==k =t ® TO ELECTRICAL BOX COVER TO INDICATE HIGH VOLTAGE, GROUND DIFFERENTIATION BETWEEN TWO DIFFERENT CONTACT ELECTRICAL BOX AND BRACKET TO SAFETY GROUND, AND WIRE TYPES DUE TO THEIR WIRING LOCATION, AND REPORTING INPUT CIRCUIT WITH TWISTED- SHIELDED WIRE SHIELD CONNECTED AS A SINGLE IDNET ADDRESSABLE POINT TO A OPTIONAL ® ® ® ® N NOT USED SHIELD TO GROUNDED BRACKET). TO NE D U\p,SSlFjFo UL us FILL VOID OR CAVITY MATERIALS CLASSIFIED BY VNOEfi4TRITERS LABORATORIES, ]NCO FOR USE IN THROUGH - PENETRATION FIRESTOP SYSTEMS (XHEZI. SEE CURRENT UL FIRE RESSTANCE DIRECTOHf 60L6, 9004 UL-LISTED SQUARE BOX DEEP BACK BOX )T SUPPLIED) I H RELAY IS USED TO CONTROL A FIRE SAFETY FUNCTION, OUB CO D ION. IT MUST BE WIRED WITHIN 3 FEET OF THE CONTROLLED DEVICE. - SHORT, INDICATES THAT A CONTACT HAS CLOSED THAT IS 733 -886 ® ® ® NORMALLY OPEN (N /0) DRY CONTACTS ARE ALLOWED ON THE ® N N.C. PROVISIONS TO CONFORM TO NEC 760 POWER- LIMITED AND NON- DIRECTLY CONNECTED TO THE INPUT CIRCUIT. S ARE PULLED UP TO 5VDC B1( A 17AK RESISTOR, WHICHI CAN I OR FACP SOURCE UP TO 284 uA (SUPERVISED AND POWER - LIMITED). T- SENSE! 11 POWER- LIMITED WIRING SEPARATION MUST BE MADE IN THE FIELD - CURRENT LIMITED INDICATES THAT A CONTACT HAS ® ® ® 6.81K (NORMAL), 16.9K (OPEN), 1.65K (CURRENT- LIMITED) % 845 OHMS (SHORTED). ® C SEE NOTES WIRING IF NON - POWER -LIMITED WIRING IS USED ON THE RELAY OUTPUT. CLOSED BEYOND A SERIES CONNECTED CURRENT F 4 E FROM PREVIOUS LIMITING RESISTOR. THIS OPERATION ALLOWS IDNET + -R 5. IF AC IS USED ON RELAY TERMINALS, YOU MUST ADD LABEL 526 -631 DEVICE OR FACP IDNET - -B ® ® - ® N N.O. -==k =t ® TO ELECTRICAL BOX COVER TO INDICATE HIGH VOLTAGE, GROUND DIFFERENTIATION BETWEEN TWO DIFFERENT CONTACT ELECTRICAL BOX AND BRACKET TO SAFETY GROUND, AND WIRE TYPES DUE TO THEIR WIRING LOCATION, AND REPORTING INPUT CIRCUIT WITH TWISTED- SHIELDED WIRE SHIELD CONNECTED AS A SINGLE IDNET ADDRESSABLE POINT TO A OPTIONAL ® ® ® ® N NOT USED SHIELD TO GROUNDED BRACKET). TO NE D 6. T -SENSE INPUT CIRCUITS ARE NOT TO EXCEED 500 FEET. ONLY (IF USED f ,DNET + -R NORMALLY OPEN (N /0) DRY CONTACTS ARE ALLOWED ON THE IF STYLE 6: l IONEf - -B INPUT CIRCUITS. T -SENSE LINES ARE 18 AWG WIRE. T -SENSE INPUTS TO NEXT DEVICE SEE NOTES 1,2 !c 3 ARE PULLED UP TO 5VDC B1( A 17AK RESISTOR, WHICHI CAN I OR FACP SOURCE UP TO 284 uA (SUPERVISED AND POWER - LIMITED). T- SENSE! 11 INPUTS MAY BE TESTED USING 1/4 WATT, 1% RESISTORS AS FOLLOWS: 6.81K (NORMAL), 16.9K (OPEN), 1.65K (CURRENT- LIMITED) % 845 OHMS (SHORTED). System No. C -AJ -1044 March 15, 2007 F Ratings - 2, 3, and 4 Hr (See Items 2A and 4) T Rating - 0 Hr L Rating At Ambient - 2 CFM /sq ft L Rating At 400 F - less than 1 CFM /sq ft W Rating - Class I (See Item 4) SECTION A -A 1. Floor or Wall Assembly- Ughtwelght or normal weight (100 -150 Pd or 1600 -2400 k91m3) co crate. Except as noted In table under Item 4, min thickness of wild concrete Poor or wall assembly k 4- 1/21n. (114 mm) Floor may also be constructed ciliary min 61n. (152 mm) thick UL Classin' hollow mrlrecast Concrete UnItsSYhen Poor Is constructed ,f hollow mm premst concrete units, packing material (Item 3) and caulk fill materiel (Item 4) to be Install. "t c any on both aides of floor, Push with floor surface. Wan assembly may also ba constructed o/ any UL GassI00lncrele Blocks- Max clam of opening Is In wild lightweight or normal might concrete. Floor 1132 In. (813 mm) Max clam of opening In floor constructed of hollow -mm precast concrete units Is 7 In (178 mm). See concrete Blocks(CAZT) andPrecast concrete UnitQCFTV) categories in the Fire Resistance Directory for names of manufacturers. IA. Steel Sleeve(Opdonal, not shown) - Max IS In. (381 mm) ID (or smaller) Schedule 10 (or heavier) steel sleeve castor grouted Into floor or wall assembly. Sleeve may extend a max of 2 In. (51 mm) above top of floor or beyond either wrfam of wall. Max 16 In. (406 mm) ID (or smaller) min 0 028 (0.71 mm) well thickness (or heavier) galvanlzed steel sleeve cast or grouted Into fbpr or well assembly. Sleeve may extend a max of 1/2 In. (13 mm) beyond either surface of floor or wan. 2. Through Penetrants One metallic pipe, conduit or tubing 0 be Installed either concentrically eccentrically within the fimsto stem Max annular between et par I conduit or P system, spew pipe, tubing and edge a through opening or sleeve Is dependent r the parameters shown m Item 4. (p Min annular space between pipe or conduit and edge of through opening Is O o (0 m ll (point contact). llo conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and size of meGlll< pipes, conduits or tubing may be used: A. Steel Pipe- Nom 301n. (762 mm) diem (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe- Nom 301n (762 mm) diem (or smaller) cast or ductile Icon pipe. C. Conduit- Nom 61n. (152 mm) diem (or smaller) rigid steel conduit D. Conduit- Nom 4 In. (102 mm) diem (or smaller) steel electrical metallic tubing. E. copper- Tubing Nom 61n (152 mm) diem (or smaller) Type L (or heavier) copper tube. F. Copper Pipe - Nom 61n. (152 mm) diem (or smaller) Regular (or heavier) copper pipe. 3 Packing Material Polyethylene barker rod or nom 1 In. (25 mm) thickness of lightly- packed mineral wool belt or glass flber Insulation firmly packed Into opening as a permanent form. Packing materiel to be recessed from top surface of floor or from both surfaces of wan as a uired to a=mmodate there required thickness f I 1 rq q sso caulk materiel (Item 4). 4. FlII,Vold or Cavity Material- -Caulk or SealAPplled to fin the annular space flush with top rface of Poor. In well aswmNles, required caulk thickness to be installed symmetrically on both 'Idea of wan, nosh with wall surface. At point contact location between penetrant and sleeve or between penetrant and concrete, a min 1/4 In (6 mm) diem bead of caulk shall be applied at top wdam of floor and at both wrfacas of wan. The hourly F Ratings and the min required caulk thicknesses are dependent upon a number of parameters, as shown In the following table: �� ® ®© ®mpnFnrwz MIMMEOUMMI®IIIIIIIII' (a)Mm 2 m. (51 mm) Chic kness of mineral wool ban Insulation required In annular space (b)Mln 1 In (25 mm) thickness of mineral wool ban Insulation required In annular space on both sides of floor or well assembly. Min 1 In. (25 mm) thickness of caulk to be Installed flush with each surface of floor or wan assembly. 3M COMPANY -CP 25WB+ caulk or FB -3000 Wr sealant. (Note W Rating applies only when FB -3000 WT sealant Is used.) •Bearing the UL Gassiflcatlon Marking • NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2011 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. FIP%E ALARM SYSTEM TO BE INSTALLED IN ACCORDANCE WITH NRA 72; 70;101• %17 F. AHAM[ -DADE COUNTY DIRE DEPAR NT BLDG. PERMIT FIRE ALARM FIRE SUPPRESSION__,____ WATER MAIN EXTa__"_ DATE:4z Lwf?11�5 BY' y 0 p� W e 1` U a Y Q � N N'T T M -Jv N � U_ aG -i V3 o -W W W laaaaaaaas C/ `�rI se� Q W Q W �- r n w /Lu C _ / vJ O U W M C 0- C LU Q Q W f- O �p 2InU_ laaaaaaaas C � M 2 U) OQ 2° � 2 0 ND O � �z W Z 0 0 Z O P= LL D_ o U CL o U) Q W to Ur D N O °O J U DRAWN BY: jJ.SERRANO CHECKED BY: J.SERRANO ISSUE DATE: 8/19/13 JOB #: PROJECT #: 263:972023611 SIMPLEXGRINNELL © 2013 SYSTEM: FIRE ALARM SYSTEM `,,1111111/1// "1 , SHEET: 41% CALCS & DETAILS Z.�. ,z- INGEMEL S. A. W = 2 ENGINEERING COMPANY �� : ��_�� Stage ofFlori a CA No. 9$13 •'•..��•�•�•�:•• 5���`` 20871 Johnson Street Street, Suite 115 FA -601 �,,p�O; �5,1��� Phone:Pembroke P flex, Florida533029 -7216 a 0 is iG (a)Mm 2 m. (51 mm) Chic kness of mineral wool ban Insulation required In annular space (b)Mln 1 In (25 mm) thickness of mineral wool ban Insulation required In annular space on both sides of floor or well assembly. Min 1 In. (25 mm) thickness of caulk to be Installed flush with each surface of floor or wan assembly. 3M COMPANY -CP 25WB+ caulk or FB -3000 Wr sealant. (Note W Rating applies only when FB -3000 WT sealant Is used.) •Bearing the UL Gassiflcatlon Marking • NOTE THIS MATERIAL WAS EXTRACTED BY 3M FIRE PROTECTION PRODUCTS FROM THE 2011 EDITION OF THE UL FIRE RESISTANCE DIRECTORY. FIP%E ALARM SYSTEM TO BE INSTALLED IN ACCORDANCE WITH NRA 72; 70;101• %17 F. AHAM[ -DADE COUNTY DIRE DEPAR NT BLDG. PERMIT FIRE ALARM FIRE SUPPRESSION__,____ WATER MAIN EXTa__"_ DATE:4z Lwf?11�5 BY' y 0 p� W e 1` U a Y Q � N N'T T M -Jv N � U_ aG -i V3 o -W W W laaaaaaaas C/ `�rI se� Q W Q W �- r n w /Lu C _ / vJ O U W M C 0- C LU Q Q W f- O �p 2InU_ laaaaaaaas C � M 2 U) OQ 2° � 2 0 ND O � �z W Z 0 0 Z O P= LL D_ o U CL o U) Q W to Ur D N O °O J U DRAWN BY: jJ.SERRANO CHECKED BY: J.SERRANO ISSUE DATE: 8/19/13 JOB #: PROJECT #: 263:972023611 SIMPLEXGRINNELL © 2013 SYSTEM: FIRE ALARM SYSTEM `,,1111111/1// "1 , SHEET: 41% CALCS & DETAILS Z.�. ,z- INGEMEL S. A. W = 2 ENGINEERING COMPANY �� : ��_�� Stage ofFlori a CA No. 9$13 •'•..��•�•�•�:•• 5���`` 20871 Johnson Street Street, Suite 115 FA -601 �,,p�O; �5,1��� Phone:Pembroke P flex, Florida533029 -7216 a 0 is iG a Y Q � N N'T T M -Jv N � U_ aG -i V3 o -W W W laaaaaaaas C/ `�rI se� Q W Q W �- r n w /Lu C _ / vJ O U W M C 0- C LU Q Q W f- O �p 2InU_ laaaaaaaas C � M 2 U) OQ 2° � 2 0 ND O � �z W Z 0 0 Z O P= LL D_ o U CL o U) Q W to Ur D N O °O J U DRAWN BY: jJ.SERRANO CHECKED BY: J.SERRANO ISSUE DATE: 8/19/13 JOB #: PROJECT #: 263:972023611 SIMPLEXGRINNELL © 2013 SYSTEM: FIRE ALARM SYSTEM `,,1111111/1// "1 , SHEET: 41% CALCS & DETAILS Z.�. ,z- INGEMEL S. A. W = 2 ENGINEERING COMPANY �� : ��_�� Stage ofFlori a CA No. 9$13 •'•..��•�•�•�:•• 5���`` 20871 Johnson Street Street, Suite 115 FA -601 �,,p�O; �5,1��� Phone:Pembroke P flex, Florida533029 -7216 a 0 is iG O � �z W Z 0 0 Z O P= LL D_ o U CL o U) Q W to Ur D N O °O J U DRAWN BY: jJ.SERRANO CHECKED BY: J.SERRANO ISSUE DATE: 8/19/13 JOB #: PROJECT #: 263:972023611 SIMPLEXGRINNELL © 2013 SYSTEM: FIRE ALARM SYSTEM `,,1111111/1// "1 , SHEET: 41% CALCS & DETAILS Z.�. ,z- INGEMEL S. A. W = 2 ENGINEERING COMPANY �� : ��_�� Stage ofFlori a CA No. 9$13 •'•..��•�•�•�:•• 5���`` 20871 Johnson Street Street, Suite 115 FA -601 �,,p�O; �5,1��� Phone:Pembroke P flex, Florida533029 -7216 a 0 is iG a 0 is iG