13-1221-016Miami -Dade Fire Rescue MIAM DADE
Fire Alarm Pre - Submittal Checklist
Desigoed by:
to n
YES
NO IN/Al
Signature:
LOCATION /COMMENTS
A location key is provided showing the area of proposed work with in the building. Also a site key with
X
26
north arrow for projects with multiple buildings showing locations of all buildings with addresses.
Floor plans are drawn to 1/8' scale or, if using another scale, all service coverage is diagrammed on the
X
27
plan and all room dimensions are included.
28
All rooms and spaces are labeled indicating their use. Also, for all assembly use rooms with an occupant
X
load of SO or greater the occupant load has been provided.
291
All new existing, relocated or replaced devices are indicated on the floor plan & riser.
X
30
Ceilin type /condition and height is provided for all ceiling mounted devices.
X
All devices in areas in which the voltage, temperature, and humidity variations exceed those conditions
X
31
stated in NFPA 72, are listed for conditions and all such areas are identified.
32
The FACP or remote annunciator is located at the main entrance/lobby.
X
33
The FACP and all sub panels in unoccupied rooms are protected with a smoke detector.
X
If complete automatically activated system, there is at least 1 pull station on each floor or 2 for large
X
34
buildings.
if a manually activated system, the travel distance to reach a pull station is less than 200' feet and within S'
X
35
feet of exits.
All automatic initiating devices arc shown and are located in accordance with NFPA 72, the
X
36
manufacturers specifications, and accepted engineering practices.
All visual notification appliances are placed per the tablet in NFPA 72 and each strobe has It's candela
X
37
rating listed on the floor plan and riser.
All corridor spaced strobes are placed a maximum of 100' feet apart and within 15' feet from ends of the
X
38
corridor.
39
All spaces meet the audible characteristics of NFPA 72 and NFPA 101.
X
Walls /partitions that do not extend to ceiling and racks, shelves and equipment, which may block
X
40
devices, are shown with their heights indicated.
Duct detectors or relays for duct detectors are shown on the floor plan and riser for all systems over 2000
X
41
•
cfrn. These devices are powered by fire alarm system.
421
A riser diagram is provided showing each floor ol'building with all zones and circuits labeled.
X
43
1 The wire size, type, and number of conductors are provided for each circuit of riser.
X
44
The fire pump is monitored -for run, phase reversal & phase loss to _X_ a continuously manned
X
location, or _ the supervised fire alarm system.
All relays for automatic extinguishing systems are shown on the floor plan and riser. (Hoods, booths, FM-
X
4S
200, sprinkler, etc.
The ampacity of each power supply and circuits is specified for each fire alarm control panel and NAC
X
46
panel. Also, individual device current is specified on plans.
The total footage to the last device is included with the voltage drop calculations for each notification
X
47
appliance circuit of each power supply.
48
1 The wattage tap is indicated for all speakers.
X
491
The wattage capacity and load calculation is provided for each amplifier.
X
All load values for stand -by and alarm used in calculations are highlighted on mfg. spec. sheets. Also,
X
SO
ampacity of equipmeut/components and circuits is highlighted on mfg. spec. sleet
This system includes Emergency Voice Evacuation and Is provided with 15 minutes of secondary alarm
X
51
power.
This system is being provided back cap power by an emergency generator and will provide 4 hours of
X
S2
standby power plus the appropriate secondary alarm power.
Battery calculations, detailed in chart form, showing all information required per NFPA 72 4.4.1.5.3.1
X
S3
are provided for each back-up power supply.
Desigoed by:
to n
IflevtoYr
Phone # : q Sl ` 9&2_5_z23
Signature:
Created by: ZGH 03 /07