13-1221-012Specifications
Electrical
Communications
41000 IDNet, one address
Power
Consumes one unit load, power supplied from 41000 IDNet communications
Input Requirements
Normally open dry contacts
Up to 500 ft (152 m) total distance from Relay IAM
For indoor wiring applications only
Input Supervision Resistors
Two required, refer to Installation Instructions 574 -874 for additional
information and wiring detail
Wire Connections
Screw terminals for input and output wiring, 18 to 14 AWG wire
(0.82 mm to 2.08 mm )
Relay Contact Ratings, Power - Limited
Form C (SPDT) Nonpower- Limited
2 A resistive, 1 A inductive @ 30 VDC
1/2 A resistive, 1/4 A inductive @ 120 VAC
IDNet Wiring Distance Reference
Up to 2500 ft (762 m) from the fire alarm control panel
Up to 10,000 ft (3048 m) total Class B wiring distance including T -Taps
Compatible with 2081 -9044 Overvoltage Protectors
Mechanical
. a
Dimensions 4 -1/8" H x 4 -1/8" W x 1 -3/8" D (105 mm x 105 mm x 35 mm)
Package Black thermoplastic housing on metal mounting plate
Temperature 32° to 120° F (0° to 49° C) indoor operation only
Humidity Range 10 to 90% RH at 90° F (32° C)
Tyco, Simplex, the Simplex logo, and IDNet are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other countries.
15®Simplex Tyco Safety Products Westminster • Westminster, MA • 01441 -0001 • USA S4090- 0007 -2 3/2004
www.tycosafetyproducts-usa-wm.com
02004 Tyro Safety Products Westminster. All nghts reserved All specifications and other nfonnation showvi N ere current as ofdocument revision date and are subject to change without notice.