Loading...
13-1221-012Specifications Electrical Communications 41000 IDNet, one address Power Consumes one unit load, power supplied from 41000 IDNet communications Input Requirements Normally open dry contacts Up to 500 ft (152 m) total distance from Relay IAM For indoor wiring applications only Input Supervision Resistors Two required, refer to Installation Instructions 574 -874 for additional information and wiring detail Wire Connections Screw terminals for input and output wiring, 18 to 14 AWG wire (0.82 mm to 2.08 mm ) Relay Contact Ratings, Power - Limited Form C (SPDT) Nonpower- Limited 2 A resistive, 1 A inductive @ 30 VDC 1/2 A resistive, 1/4 A inductive @ 120 VAC IDNet Wiring Distance Reference Up to 2500 ft (762 m) from the fire alarm control panel Up to 10,000 ft (3048 m) total Class B wiring distance including T -Taps Compatible with 2081 -9044 Overvoltage Protectors Mechanical . a Dimensions 4 -1/8" H x 4 -1/8" W x 1 -3/8" D (105 mm x 105 mm x 35 mm) Package Black thermoplastic housing on metal mounting plate Temperature 32° to 120° F (0° to 49° C) indoor operation only Humidity Range 10 to 90% RH at 90° F (32° C) Tyco, Simplex, the Simplex logo, and IDNet are trademarks of Tyco International Services AG or its affiliates in the U.S. and/or other countries. 15®Simplex Tyco Safety Products Westminster • Westminster, MA • 01441 -0001 • USA S4090- 0007 -2 3/2004 www.tycosafetyproducts-usa-wm.com 02004 Tyro Safety Products Westminster. All nghts reserved All specifications and other nfonnation showvi N ere current as ofdocument revision date and are subject to change without notice.