13-1221-0108..�M
(152 m) (input is for indoor wiring only)
Model
Description
4090 -9118
Relay IAM with T -Sense
4090 -9801
Optional trim plate with LED viewing window,
includes mounting screws; galvanized steel
For semi -flush mounted box
4090 -9802
For surface mounted box
••-
..-
N. 0.
Common Circuit Status Modes
Circuit Status
Device Status
Panel Display
Normal
Switches open
Normal
Open circuit
11,1N. om
Wiring discontinuity
Trouble
Damper Position Monitoring Status Modes
Circuit Status
Device Status
Typi' at Panel Display
Short
Switch A closed
Damper Closed
Current Limited
Switch B closed
Damper Open
Waterflow and Tamper Switch Monitoring Status Modes
+ 4090 -9118
Circuit Status
Device Status
Panel Display '
Short
Waterflow switch closed
Fire Alarm
Current Limited
with T -Sense
Tamper switch closed
Supervisory
Wiring Reference
Maximum distance to contacts is 500 it
(152 m) (input is for indoor wiring only)
1.8 kit, 1/2 W
- 4.7 kit, 1/2 W
For Fire Alarm applications, locate
End -of -line T -Sense Input
loads within 3 it (1 m) of contacts
resistor
N. 0.
Current limited Shorting
Power Limited Contact Ratings:
contact contact
Output
11,1N. om
2 A @ 30 VDC, resistive loads
1 A @ 30 VDC, inductive loads
C.
Non -Power Limited Contact
Ratings:
IDNet communications +
+ 4090 -9118
1/2 A @ 120 VAC, resistive loads
from host 41000 _ - --'
_ Relay IAM
1/4 A @ 120 VAC, inductive loads
control panel �-
with T -Sense
T T
To next device
IDNet Wiring Distances:
1. Up to 2500 ft (762 m) from host control panel.
2. Up to 10,000 it (3048 m) total wiring distance, including 'T' taps.
NOTE: Refer to Installation Instructions 574 -874 for detailed installation information.
S4090- 0007 -2 3/2004
2