Loading...
13-1221-0108..�M (152 m) (input is for indoor wiring only) Model Description 4090 -9118 Relay IAM with T -Sense 4090 -9801 Optional trim plate with LED viewing window, includes mounting screws; galvanized steel For semi -flush mounted box 4090 -9802 For surface mounted box ••- ..- N. 0. Common Circuit Status Modes Circuit Status Device Status Panel Display Normal Switches open Normal Open circuit 11,1N. om Wiring discontinuity Trouble Damper Position Monitoring Status Modes Circuit Status Device Status Typi' at Panel Display Short Switch A closed Damper Closed Current Limited Switch B closed Damper Open Waterflow and Tamper Switch Monitoring Status Modes + 4090 -9118 Circuit Status Device Status Panel Display ' Short Waterflow switch closed Fire Alarm Current Limited with T -Sense Tamper switch closed Supervisory Wiring Reference Maximum distance to contacts is 500 it (152 m) (input is for indoor wiring only) 1.8 kit, 1/2 W - 4.7 kit, 1/2 W For Fire Alarm applications, locate End -of -line T -Sense Input loads within 3 it (1 m) of contacts resistor N. 0. Current limited Shorting Power Limited Contact Ratings: contact contact Output 11,1N. om 2 A @ 30 VDC, resistive loads 1 A @ 30 VDC, inductive loads C. Non -Power Limited Contact Ratings: IDNet communications + + 4090 -9118 1/2 A @ 120 VAC, resistive loads from host 41000 _ - --' _ Relay IAM 1/4 A @ 120 VAC, inductive loads control panel �- with T -Sense T T To next device IDNet Wiring Distances: 1. Up to 2500 ft (762 m) from host control panel. 2. Up to 10,000 it (3048 m) total wiring distance, including 'T' taps. NOTE: Refer to Installation Instructions 574 -874 for detailed installation information. S4090- 0007 -2 3/2004 2