13-1221-009S.Simplex 410011L.J Multi -Point Peripherals
UL, ULC Listed, FM, CSFM 4090 -9118 Relay IAM (Individual
and MEA (NYC) Approved* Addressable Module) with T -Sense Input
M
Dual point operation provides a supervised
multi -state input and a relay output in a single
package using only one address:
• Typical applications are for damper motor control
with dual damper position feedback monitoring (open
and closed)
• For use with Simplex 4100U Fire Alarm Control
Panels operating with software revision 11 or higher
and providing IDNetTM communications **
Input/Output details:
• Input operation is "T- Sense" and provides supervised
monitoring of normally open, dry contacts
• Status conditions are Normal, Open Circuit (trouble
condition), Current Limited (position input 1), and
Short (position input 2)
• Total wiring distance to supervised contacts is up to
500 ft (152 m); for indoor wiring applications
• Both data and power are provided by the IDNet
communications link over a single wire pair
• Form C relay output is rated 2 A @ 30 VDC, and
1/2 A @ 120 VAC (resistive ratings)
Compact, sealed construction:
• Enclosed design minimizes dust infiltration
• Mounts in standard 4" square electrical box
• Visible LED flashes to indicate communications
• Screw terminals for wiring connections
• Optional covers are available to allow LED to be
viewed after installation
UL Listed to Standard 864
Descrintin
Single Address Dual Point Module. The 4090 -9118
Relay IAM with T -Sense allows a Simplex 410OU IDNet
communication channel to monitor two input contact
closures with one point and control an output relay with
the other point, both from a compact module requiring a
single address. Module power is supplied from the IDNet
communications channel eliminating the need for separate
power wiring.
Multi -Point Device Description. The input circuit and
relay operation are controlled independently and may be
disabled separately. Point association is determined at the
410OU host panel. At the 410OU host display, the device
address is designated as a single hardware location (such
as 1 -1). The individual points are considered "sub- points"
and are layered underneath (such as 1 -1 -1 and 1 -1 -2).
" IDNet addressable communications designs are protected by U.S. Patent No. 4,796,025.
4090 -9118 Relay IAM with T -Sense Input
(shown approximately 1/2 size)
Supervised Input. The 4090 -9118 Relay IAM with
T -Sense has a supervised input that monitors for
continuity to an end -of -line resistor and can differentiate
between a short circuit contact closure and a current
limited contact closure.
Four State Operation. Normal is when all contacts are
open and there is continuity to the end -of -line resistor;
Open is when continuity does not exist to the end -of -line
resistor, causing a Trouble condition; Short, indicates that
a contact has closed that is directly connected to the input
circuit; and Current Limited indicates that a contact has
closed beyond a series connected current limiting resistor.
This operation allows differentiation between two
different contact types due to their wiring location, and
reporting as a single IDNet addressable point to a 410OU
fire alarm control panel.
Efficient Package. For smoke control applications, this
module provides an efficient package for fan damper
control with position feedback. The monitor point can be
connected to two separate status indicator switches
allowing the host panel to track the fan damper status with
respect to the requested fan control operation.
General Applications. The monitor and control points
can be applied for a variety of associated or independent
operations. Flexible programming abilities at the host
panel can provide the association logic required for a
wide variety of fire or utility operations.
This product has been approved by the California State Fire Marshal (CSFM) pursuant to
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7300 - 0026:311
for allowable values and /or conditions concerning material presented in this document It is
subject to re- examination, revision, and possible cancellation. Accepted for use — City of New
York Department of Buildings — MEA35 -93E. Additional listings may be applicable; contact
your local Simpiex product supplier for the latest status Listings and approvals under
Simplex Time Recorder Co. are the property of Tyco Safety Products Westminster.
S4090- 0007 -2 3/2004