13-1037-003I i I . COORDINATION DRAWINGS 1. THE CONTRACTOR SHALL SUBMIT COORDINATION DRAWINGS TO ARCH. /ENG AND OWNER'S PROJECT MANAGER FOR APPROVAL PRIOR TO ANY FABRICATION AND INSTALLATION. 2. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL NEW PIPING, DUCTWORK, CONDUITS, ECT. WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL AND ELECTRICAL SYSTEMS OF THE BUILDING. VERIFY ALL SPACE CONDITIONS AND DIMENSIONS AT JOBSITE PRIOR TO FABRICATION AND INSTALLATION OF EQUIPMENT AND MATERIALS. ANY CONFLICTS SHALL BE REPORTED IMMEDIATELY TO THE ARCHITECT /ENGINEER PRIOR TO BEGINNING OF CONSTRUCTION. COORDINATION NOTE AS PART OF THIS CONTRACT, THE SUB - CONTRACTOR AND THE CONTRACTOR ARE RESPONSIBLE FOR COORDINATION AND VERIFICATION THAT ALL EQUIPMENT, SHOWN IN THE ARCHITECTURAL DRAWINGS PARTICULARLY, BUT NOT LIMITED TO THE ARCHITECTURAL EQUIPMENT PLAN, INCLUDE ALL SERVICE /UTILITY REQUIRED TO OPERATE THE EQUIPMENT SHOWN. ANY DISCREPANCIES ARE TO BE POINTED OUT DURING THE BIDDING PROCESS. DISCREPANCIES NOT POINTED OUT DURING THE BIDDING PROCESS WILL BE RESOLVED BY THE CONTRACTOR AS PER THE ARCHITECT DETAILS AT NO ADDITIONAL COST TO THE OWNER. BID NOTE THE DRAWINGS DO NOT INDICATE EXISTING INSTALLATIONS OTHER THAN TO IDENTIFY MODIFICATIONS OR EXTENSIONS THERETO, VISIT THE SITE AND ASCERTAIN THE EXISTING CONDITIONS. REVIEW CONSTRUCTION DETAILS OF THE EXISTING PORTION OF THE BUILDING DURING THE SITE INSPECTION. INCLUDE ALL WORK REQUIRED TO REMOVE OR MODIFY PORTIONS OF THE EXISTING INSTALLATION IN ORDER TO ACCOMMODATE THE NEW WORK. FAILURE TO COMPLY WITH THIS WILL NOT BE CONSIDERED GROUNDS FOR ADDITIONAL PAYMENT IN CONNECTION WITH REMOVING OR MODIFYING ANY PART OF THE EXISTING INSTALLATION OR INSTALLING ANY NEW OR TEMPORARY WORK, APPLICABLE CODES / STANDARDS APPLICABLE CODES AND STANDARDS SHALL INCLUDE ALL STATE LAWS, LOCAL ORDINANCES, UTILITY COMPANY REGULATIONS AND THE APPLICABLE REQUIREMENTS OF THE FOLLOWING ACCEPTED CODES AND STANDARDS, WITHOUT LIMITING THE NUMBER, AS FOLLOWS: 1. FLORIDA BUILDING CODE - 2010 2. GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH DEPARTMENT CARE FACILITIES 2010 3. AGENCY FOR HEALTH CARE ADMINISTRATION, AHCA, 59A -3. 4. NATIONAL ELECTRIC CODE (NEC 2008). 5. ENVIRONMENTAL PROTECTION AGENCY (EPA). 6. DEPARTMENT OF ENVIRONMENTAL REGULATION MANAGEMENT (DERM). 7. LOCAL ORDINANCES, REGULATIONS OF THE BUILDING DEPARTMENTS AND FIRE DEPARTMENTS. 8. NATIONAL ELECTRICAL SAFETY CODE 2002. 9. OCCUPATIONAL SAFETY AND HEALTH STANDARD. 10. RECOMMENDATION OF NFPA, IN GENERAL AND IN PARTICULAR: A. LIFE SAFETY, NFPA (2006) B. HAVC, NFPA 90A (2002) C. HVAC, NFPA 90B (2006) D. HVAC, NFPA 96 (2004) E. HOSPITALS, NFPA 99 (2002) F. SMOKE CONTROL, NFPA 92A (2000),92B (2000) G. MEDICAL GAS, NFPA 99 (2002), AND NFPA 50 (2001) H. STANDARD FOR INSTALLATION OF EXHAUST SYSTEMS, NFPA 91 (1999) I. STANDARD FOR INSTALLATION OF SPRINKLER SYSTEM, NFPA 13 (2007) 11. RECOMMENDATION OF ASHRAE (2001), INCLUDING ASHRAE 90 -75. 12, JOINT COMMISSIONS FIRE ALARM POLICY. 13. FLORIDA WITH DISABILITIES ACCESSIBILITY ACT (2004). 14.- SMACNA (2005). PLUMBING SPECIFICATIONS DOMESTIC COLD AND HOT WATER PIPING A. PROVIDE DIELECTRIC UNIONS WHERE DISSIMILAR METALS ARE JOINED. B. WATER PIPING (ABOVE GRADE): SHALL BE COPPER TYPE "L" ASTM B -88 WITH WROUGHT COPPER FITTINGS AND 95 -5 SOLDERED JOINTS OR VICTAULIC FITTINGS. C. WATER PIPING (BELOW GRADE): SHALL BE DUCTILE IRON PIPE WITH FLANGED FITTINGS. D. GATE VALVES: TO 2" - CLASS 150, BRONZE, UNION BONNET RISING STEM, INSIDE SCREW, SOLID WEDGE DISC, NON - ASBESTOS PACKING, SOLDERED ENDS OR VICTAULIC. E. GATE VALVES: 2 -1/2" AND ABOVE - CLASS 125, OUTSIDE SCREW AND YOKE, IRON BODY, BRONZE TRIM, (IBBM), RISING STEM, SOLID BRONZE WEDGE FACE RINGS IN LARGER SIZES, NON - ASBESTOS PACKING, FLANGED ENDS OR VICTAULIC. F. HANGERS: PROVIDE ADJUSTABLE HANGERS, INSERTS, BRACKETS, ROLLS, TRAPEZE, CLAMPS AND SUPPLEMENTARY STEEL AS REQUIRED FOR PROPER SUPPORT OF PIPE LINES. PLUMBING LEGEND PLUMBING GENERAL NOTES 1. EXAMINATION OF CONTRACT DOCUMENTS AND SITE OF WORK: 7. ALL PLUMBING SHALL BE IN ACCORDANCE WITH THE STATE AND DOMESTIC COLD WATER PIPE THE BIDDER IS REQUIRED, BEFORE SUBMITTING HIS PROPOSAL, DOMESTIC HOT WATER PIPE LOCAL CODES AND ORDINANCES. DOMESTIC HOT WATER RETURN PIPE TO VISIT THE SITE OF THE PROPOSED WORK AND FAMILIARIZE DIRECTION OF FLOW --- VALVE IN VERTICAL HIMSELF WITH THE NATURE, EXTENT OF THE WORK AND ANY 8. PLUMBING CONTRACTOR SHALL PAY ALL FEES, INSPECTION AND BALL VALVE LOCAL CONDITIONS THAT MAY IN ANY MANNER AFFECT THE CHECK VALVE CONNECTION CHARGES REQUIRED. HOSE BIBB WORK TO BE DONE AND EQUIPMENT, MATERIALS AND LABOR WATER HAMMER ARRESTOR CONNECT NEW TO EXISTING SYSTEMS REQUIRED THEREFORE. SINCE THE WORK INVOLVES EXISTING 9. PLUMBING CONTRACTOR SHALL VERIFY ALL SPACE CONDITIONS EXISTING LINE TO BE REMOVED BUILDING, SYSTEMS AND FACILITIES, SPECIAL CONSIDERATION AND DIMENSIONS AT JOB SITE PRIOR TO FABRICATION AND SHALL BE GIVEN TO EXAMINATION OF WORKING CONDITIONS, INSTALLATION OF MATERIALS AND EQUIPMENT. EXISTING FACILITIES AND ALL BUILDING STRUCTURES. HE IS TO FAMILIARIZE HIMSELF WITH ALL EXISTING CONDITIONS SLIGHT 10. COORDINATE NEW WORK WITH ALL TRADES. VARIATION OF ROUTING AND /OR CONSTRUCTIONS SHOULD BE ANTICIPATED BY THIS CONTRACTOR TO AVOID CONFLICTS WITH 11. SUBMIT SHOP DRAWINGS TO ENGINEER FOR APPROVAL OF ALL OTHER TRADES. THESE ARE EXPRESSLY INCLUDED AS PART OF EQUIPMENT, MATERIALS AND LAYOUTS PRIOR TO INSTALLATION. THE WORK WHENEVER REQUIRED AT NO ADDITIONAL COST TO OWNER. 12. FURNISH AND INSTALL CONNECTIONS TO EQUIPMENT PROVIDED BY THE OWNER UNDER THIS CONTRACT, COORDINATE 2. THE NATURE OF THE REMODEL TYPE CONSTRUCTION POSES INSTALLATION WITH MANUFACTURER'S RECOMMENDATION. SPECIAL PROBLEMS FOR THE DESIGN ENGINEER AS WELL AS THE PLUMBING CONTRACTOR. EVERY EFFORT HAS BEEN MADE 13. PLUMBING CONTRACTOR SHALL GURANTEE ALL WORK FREE OF BY THE ENGINEER TO SHOW AND VERIFY, WHERE POSSIBLE, DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF THE 'LOCATION OF THE EXISTING PLUMBING SYSTEMS. THE ONE YEAR FROM DATE OF ACCEPTANCES. MAJOR PORTION OF THE PLUMBING SYSTEMS ARE AS SHOWN ON THE DRAWINGS, HOWEVER, MINOR DEVIATIONS MAY BECOME 14. WHEREVER DISSIMILAR METALS ARE TO BE JOINED. A EVIDENT AS THE JOB PROGRESSES. NO ADVANTAGE IS TO BE DIELECTRIC FITTING SHALL BE PROVIDE TO CONNECT BOTH TAKEN BY THE PLUMBING CONTRACTOR BECAUSE THESE MINOR TYPES OF PIPES. DIFFERENCES. PLUMBING CONTRACTOR SHALL PERFORM FIELD VERIFICATION BEFORE BIDDING THIS PROJECT. 15. CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE ALL ROUGH INS WITH EQUIPMENT AND FIXTURES MANUFACTURER 3. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND BEFORE MAKING ANY INSTALLATION. EQUIPMENT NECESSARY FOR THE COMPLETE INSTALLATION OF THE FIRE PROTECTION SYSTEM, ALL IN ACCORDANCE WITH 16, CONTRACTOR SHALL PROTECT AND FIRE SEAL ALL OPENINGS THESE CONSTRUCTION DOCUMENTS. AND PIPE PENETRATIONS THROUGH FIRE RATED WALLS AND CEILINGS WITH ADEQUATE FIRESTOPPING MATERIALS TO 4. THE CONTRACTOR SHALL PAY ALL INSPECTION FEES, ALL COSTS MAINTAIN THE INDICATED FIRE RATINGS OF THE ASSEMBLIES OF PERMITS AND ALL OTHER COST INCIDENTAL TO THE BEING PENETRATED. COMPLETION AND TESTING OF THIS WORK UPON FINAL ACCEPTANCE, A CERTIFICATE FROM THE LOCAL INSPECTION 17. PROVIDE CEILING / WALL ACCESS PANELS WHERE INDICATED IN AUTHORITY SHALL BE FURNISHED TO THE OWNER. THE DRAWINGS AND WHERE REQUIRED TO ACCESS PLUMBING EQUIPMENT. PANELS SHALL BE RECESSED TYPE, FIRE RATED IF 5. ALL PIPING SHALL BE INSTALLED RECESSED IN WALLS, CHASES IN FIRE RATED WALLS OR CEILINGS. LOCATIONS OF PANELS OR PARTITIONS. SHALL BE COORDINATED WITH ALL THE OTHER TRADES. 6. EXISTING PIPES SERVING AREAS NOT COVER BY THIS CONTRACT BUT IN SERVICE AT THIS TIME SHALL NOT BE INTERRUPTED UNLESS IS A ,TEMPORARY INTERRUPTION COORDINATED WITH THE OWNER. COORDINATION DRAWINGS 1. THE CONTRACTOR SHALL SUBMIT COORDINATION DRAWINGS TO ARCH. /ENG AND OWNER'S PROJECT MANAGER FOR APPROVAL PRIOR TO ANY FABRICATION AND INSTALLATION. 2. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL NEW PIPING, DUCTWORK, CONDUITS, ECT. WITH ARCHITECTURAL, STRUCTURAL, MECHANICAL AND ELECTRICAL SYSTEMS OF THE BUILDING. VERIFY ALL SPACE CONDITIONS AND DIMENSIONS AT JOBSITE PRIOR TO FABRICATION AND INSTALLATION OF EQUIPMENT AND MATERIALS. ANY CONFLICTS SHALL BE REPORTED IMMEDIATELY TO THE ARCHITECT /ENGINEER PRIOR TO BEGINNING OF CONSTRUCTION. COORDINATION NOTE AS PART OF THIS CONTRACT, THE SUB - CONTRACTOR AND THE CONTRACTOR ARE RESPONSIBLE FOR COORDINATION AND VERIFICATION THAT ALL EQUIPMENT, SHOWN IN THE ARCHITECTURAL DRAWINGS PARTICULARLY, BUT NOT LIMITED TO THE ARCHITECTURAL EQUIPMENT PLAN, INCLUDE ALL SERVICE /UTILITY REQUIRED TO OPERATE THE EQUIPMENT SHOWN. ANY DISCREPANCIES ARE TO BE POINTED OUT DURING THE BIDDING PROCESS. DISCREPANCIES NOT POINTED OUT DURING THE BIDDING PROCESS WILL BE RESOLVED BY THE CONTRACTOR AS PER THE ARCHITECT DETAILS AT NO ADDITIONAL COST TO THE OWNER. BID NOTE THE DRAWINGS DO NOT INDICATE EXISTING INSTALLATIONS OTHER THAN TO IDENTIFY MODIFICATIONS OR EXTENSIONS THERETO, VISIT THE SITE AND ASCERTAIN THE EXISTING CONDITIONS. REVIEW CONSTRUCTION DETAILS OF THE EXISTING PORTION OF THE BUILDING DURING THE SITE INSPECTION. INCLUDE ALL WORK REQUIRED TO REMOVE OR MODIFY PORTIONS OF THE EXISTING INSTALLATION IN ORDER TO ACCOMMODATE THE NEW WORK. FAILURE TO COMPLY WITH THIS WILL NOT BE CONSIDERED GROUNDS FOR ADDITIONAL PAYMENT IN CONNECTION WITH REMOVING OR MODIFYING ANY PART OF THE EXISTING INSTALLATION OR INSTALLING ANY NEW OR TEMPORARY WORK, APPLICABLE CODES / STANDARDS APPLICABLE CODES AND STANDARDS SHALL INCLUDE ALL STATE LAWS, LOCAL ORDINANCES, UTILITY COMPANY REGULATIONS AND THE APPLICABLE REQUIREMENTS OF THE FOLLOWING ACCEPTED CODES AND STANDARDS, WITHOUT LIMITING THE NUMBER, AS FOLLOWS: 1. FLORIDA BUILDING CODE - 2010 2. GUIDELINES FOR DESIGN AND CONSTRUCTION OF HEALTH DEPARTMENT CARE FACILITIES 2010 3. AGENCY FOR HEALTH CARE ADMINISTRATION, AHCA, 59A -3. 4. NATIONAL ELECTRIC CODE (NEC 2008). 5. ENVIRONMENTAL PROTECTION AGENCY (EPA). 6. DEPARTMENT OF ENVIRONMENTAL REGULATION MANAGEMENT (DERM). 7. LOCAL ORDINANCES, REGULATIONS OF THE BUILDING DEPARTMENTS AND FIRE DEPARTMENTS. 8. NATIONAL ELECTRICAL SAFETY CODE 2002. 9. OCCUPATIONAL SAFETY AND HEALTH STANDARD. 10. RECOMMENDATION OF NFPA, IN GENERAL AND IN PARTICULAR: A. LIFE SAFETY, NFPA (2006) B. HAVC, NFPA 90A (2002) C. HVAC, NFPA 90B (2006) D. HVAC, NFPA 96 (2004) E. HOSPITALS, NFPA 99 (2002) F. SMOKE CONTROL, NFPA 92A (2000),92B (2000) G. MEDICAL GAS, NFPA 99 (2002), AND NFPA 50 (2001) H. STANDARD FOR INSTALLATION OF EXHAUST SYSTEMS, NFPA 91 (1999) I. STANDARD FOR INSTALLATION OF SPRINKLER SYSTEM, NFPA 13 (2007) 11. RECOMMENDATION OF ASHRAE (2001), INCLUDING ASHRAE 90 -75. 12, JOINT COMMISSIONS FIRE ALARM POLICY. 13. FLORIDA WITH DISABILITIES ACCESSIBILITY ACT (2004). 14.- SMACNA (2005). PLUMBING SPECIFICATIONS DOMESTIC COLD AND HOT WATER PIPING A. PROVIDE DIELECTRIC UNIONS WHERE DISSIMILAR METALS ARE JOINED. B. WATER PIPING (ABOVE GRADE): SHALL BE COPPER TYPE "L" ASTM B -88 WITH WROUGHT COPPER FITTINGS AND 95 -5 SOLDERED JOINTS OR VICTAULIC FITTINGS. C. WATER PIPING (BELOW GRADE): SHALL BE DUCTILE IRON PIPE WITH FLANGED FITTINGS. D. GATE VALVES: TO 2" - CLASS 150, BRONZE, UNION BONNET RISING STEM, INSIDE SCREW, SOLID WEDGE DISC, NON - ASBESTOS PACKING, SOLDERED ENDS OR VICTAULIC. E. GATE VALVES: 2 -1/2" AND ABOVE - CLASS 125, OUTSIDE SCREW AND YOKE, IRON BODY, BRONZE TRIM, (IBBM), RISING STEM, SOLID BRONZE WEDGE FACE RINGS IN LARGER SIZES, NON - ASBESTOS PACKING, FLANGED ENDS OR VICTAULIC. F. HANGERS: PROVIDE ADJUSTABLE HANGERS, INSERTS, BRACKETS, ROLLS, TRAPEZE, CLAMPS AND SUPPLEMENTARY STEEL AS REQUIRED FOR PROPER SUPPORT OF PIPE LINES. PLUMBING LEGEND SYMBOL DESCRIPTION Date: SANITARY PIPE - - DOMESTIC COLD WATER PIPE -- -- - -- DOMESTIC HOT WATER PIPE - -- DOMESTIC HOT WATER RETURN PIPE DIRECTION OF FLOW --- VALVE IN VERTICAL GATE VALVE BALL VALVE --� CHECK VALVE -C+ HOSE BIBB WATER HAMMER ARRESTOR CONNECT NEW TO EXISTING SYSTEMS E TEMPORARY OR PERMANENT CAP EXISTING LINE TO BE REMOVED INFECTION CONTROL NOTE CONTRACTOR SHALL OBTAIN A COPY OF THE INFECTION CONTROL RISK ASSESMENT FOR THIS PROJECT. ALL WORK SHALL BE IN COMPLIANCE WITH THE REPORT. ALL WORK OUTSIDE THE SCOPE OF WORK AREA REQUIRED FOR THIS PROJECT, SHALL BE COORDINATED WITH OWNER AND BE IN COMPLIANCE WITH THE ICRA REPORT AND BE SUPERVISED BY THE OWNER'S REPRESENTATIVE. ICRA TYPE " B " CLASS - II GROUP NEW I" CW I CONNECT NEW 3/4" CW TO EXISTING NEW 4" CW IN ,, � 3/4" RISEN SERVING 2ND FLOOR. CAFE CLG SPACE EXIST. RISER FROM BELOW. NEW 3/4" WB W/ VACUUM BREAKER `. COORDINATE AND OFFSET AS REQUIRED TO CLEAR EXIST. UTILITIES. EXIST. 1/2" CW. ABOVE CLG. NOTE: CONTRACTOR SHALL � NEW 4" CW �� DEMOLISH EXIST. CW PIPE BACK TO NEW 4" CW UNDERGOUND. J �, COORDINTATE NEW PIPING OVERHEAD SOURCE AND CAP, RECONNECT TO WITH EXISITNG EQUIPMENT 1 >, �_ FUTURE EQUIPMENT PRIOR TO �� NEW 4 "CW MAIN. \ INSTALLATION. CONNECT NEW 2" CW TO DISCONNECT EXISTING 4" CW EXIST. 2" RISER SERVING 2ND LINE AND RECONNECT AS �f NEW 1 114" CW�, AND 3RD FLOOR. CAP EXIST. \ SHOWN. EXISTING PIPING TO BE RISER FROM BELOW. COORDINATED WITH NEW 2" CW \'\rNEW 1 114" CW NEW 3%4" HB W/ FUTURE AHU. , b` „A" ` \`\ VACUUM BREAKER I ,� TO REPLACE EXIST. I NEW 3" CW/ - NEW 4" CW \ "B° NEW 2 1/2" CW A" EXIST. d EXIST 2" COPPER TO �� NEW I/2" CW 3/4" HW DOCTORS LOUNGE. NEW 4" CW RECONNECT WITH "� � I �� - -�ji CONNECT EXIST. ELF30W AS IN NEW 4" BYPASS SQECONNECT EXIST EXISTING BACK NOT WATER BRANCH � " TO EXISTING HOT VALVE. NORMALLY `� TO BACK TOILET CLOSED. QM AND SCURB WATER MAIN. CONNECT NEW 4" CW TO SINK TO NEW EXIST. I/2" NW EXISTING 4" RISER SERVING COPPER LINE LINE EXTEND 4" CW AND CONNECT 4TH 5TH, 6TH E 7TH FLOOR. COPPER NEW 4" CW UNDERGOUND. TO EXISTING 3" MANIFOLD AT CAP EXIST. RISER FROM NEW 2 1/2 CW � IN IST FLOOR 2 I/2" BELOW. EXISTING ELBOW WITH A TEE. '�� CLG. EXTEND 4" CW DOWN NEW WITH VALVE AND 21/2" CW RECONNECT MANIFOLD EXISTING (2) `� W1 NEW CU > 2" CW LINES FROM PUMP ELBOW INLET. PROVIDE BALL NEW 3/4" CW TYPE ISOLATION VALVES `� EXIST. 4" STORM AT PUMP INLET. `�. REMO O TEMP. D AND REINSTALLED. CONNECT NEW 3/4" CW TO EXISTING OFFSET EXIST. 4" - � �1 SERVING CAI' STORM LINE TO EXIST. RISER ROM BELOW UNDERGOUND CLEAR EXIST. CW �� VALVE. BELOW EXIST. NEW 314" CW STORM LINE. NEW 3/4" CW NEW 3/4" NB W1 VACUUM BREAKER N SOUTH MIAMI HOSPITAL MAIN BLDG LEVEL 1 - DOMESTIC WATER ISOMETRIC - PLUMBING SCALE: N.T.S. _ 1 1 1•• y, i• Y I • • W w • •mil •i••r LOUIS J. AGUIRRE & ASSOCIATES, P.A. Consulting Engineers 9150 South Dadeland Blvd. • Suite 900 Miami • Florida 33156 CA 924 Telephone 305.670.0141 Facsimile 305.670.0144 WWW.ljoapa.com Project No.: 22019 Client b South Miami Hospital B.H.S.F. 6200 S.W. 73 RD. Street Miami, FL. 33143 Q L1J z LIJ ...J 2 ((n< L1J z -0-J UJ 2= LU 2 C%i Z U v L H W W 11� co U M p M ct� J M LL ti Ua ca a cv to d.� aS 0 0 LL KEY PLAN S.W. 73RD STREET PROJECT LOCATION - o 5 W. 74TH ST 3 i 0 m Z s- m Seal NIEC4ANIC' I.. EDUAF' IJO A. SUAREZ P E • LICENSE #� 64759. ' li j Sheet Title: GENERAL NOTES, SYMBOL LEGEND AND ISOMETRIC PLUMBING W �4 MCI Project No.: Date: Scale: Drawn by: Checked by: Sheet Number: 16630 -1234 j 06.12.2013 AS NOTED) E. A. S. E.A.S. f P0000 1-