DRY TYPE TRANSFORMER SCHEDULE
FEEDER
SYMBOL
CONDUCTORS (3 PHASE,
3 WIRE) WITH GROUND
PRIMARY
SECONDARY
480 VOLT
208 VOLT
VERCURRENT
480V FEEDER
120 /208V FEEDER
GROUNDING
SIZE
KVA
AMPS
AMPS
OVERCURRENT
SEE NOTE *I
,�
SEE NOTE 2
SEE NOTE 2
SEE NOTE 3
T9
9
II
25
20A, 3P
30A, 31a
3 *12 is 1 *12G - )4'C.
4 *10 is I *IOG - Y4'C.
1 *8 - Y4'C
TI5
15
18
42
30A. 3P
50A, 3P
3010 L. I *IOG - )4'C.
408 A I *IOG - VC.
1 *8 - Y4'C
T30
30
36
13
60A, 3P
IOOA, 3P
3 *6 is I *IOG - Y4'C.
403 is I *IG - I I /4 "C.
1 *8 - Y4'C
T45
45
54
125
BOA, 3P
150A, 3P
3 *4 B I *IG - I'C.
4 *1 /0 & 106G - 2'C.
1 *6 - Y4'C
T75
75
RO
208
150A, 31D
250A. 3P
3 *1 /0 A 1 *6G - I %21C.
4 *250' KCMIL is I *4G
1 *2 - 74'C
7
3 *4/0 is 1 *4G.
2"
225
4 *4/0 is 1 *4G.
2 %2'
i
9
3 *250 KCMIL is 1 *4G.
T112
112.5
135
313
200A, 3P
400A, 3P
3 *3/0 is I*GG - 2'C.
4 *600 KCMIL is 1 *3G
1 *1 /0 - Y4'C.
4 *350 KCMIL A 1*4G.
3"
22
23
3 *500 KCMIL & I *3G.
3 V2'
350
4 *500 KCMIL is 1 *3G.
3 %2'
T150
150
181
417
300A. 3P
500A, 3P
3 *350 KCMIL B 104G
9*250 KCMIL & 2 *2G
1 *1 /0 - Y4'C
6 *250 KCMIL A 2 *2G.
2-2 %2"
500
8 *250 KCMIL is 2 *2G.
2 -2 %2"
i
- 3 1C.
2- 2%21C.
2 -3'
T225
225
271
625
400A. 3P
IOOA, 3P
3 *600 KCMIL A I *3G
B *600 KCMIL t. 2 *1 /OG
1 *3/0 - Y4'C
2 -3 %2"
2
3
6*600 KCMIL & 2 *1 /OG.
2-3 y2"
800
- 3 %'C.
2 -41C.
9 4
T300
300
361
833
600A, 3P
IOOOA. 3P
6 *350 KCMIL is 2 *IG
12 *400 KCMIL it 3 *2 /00
1 *3/0 - Y4 "C
3 -3 Y2"
1200
12 *600 KCMIL tc 3 *3 /OG.
3 -4'
B
9
2 -31C.
3 -31C.
1600
T500
1 500
602
1385
900A, 3P
IGOOA, 3P
9*350 KCMIL & 3x2 /OG
16 *600 KCMIL is 4 *4 /OG
1 *350KCMIL -I'C.
42
43
18 *600 KCMIL is 6*350G.
6-3 %2'
2500
240600 KCMIL is 6*350G.
3 -3'C.
4 -4 1C.
45
TRANSFORMER NOTES,
I. SECONDARY OVERCURRENT PROTECTION SHALL BE LOCATED WITHIN TEN (10) FEET OF THE TRANSFORMER
SECONDARY TERMINALS EITHER IN A PANELBOARD (MAIN BREAKER) OR A INDIVIDUALLY MOUNTED CIRCUIT BREAKER.
2. ALL CONDUCTOR SIZES ARE BASED ON N.E.C. TABLE 310 -IG FOR COPPER CONDUCTORS.
3. TRANSFORMER BONDING JUMPER AND GROUNDING ELECTRODE CONDUCTOR (COPPER CONDUCTORS).
BOND THE NEUTRAL OF THE TRANSFORMER SECONDARY TO THE TRANSFORMER CASE, WITH BONDING JUMPER.
GROUND THE CASE OF THE TRANSFORMER WITH THE GROUNDING ELECTRODE CONDUCTOR TO THE NEAREST
AVAILABLE EFFECTIVELY GROUNDED STRUCTURAL METAL MEMBER OF THE STRUCTURE, OR THE NEAREST
AVAILABLE EFFECTIVELY GROUNDED METAL WATER PIPE OR OTHER ELECTRODES AS SPECIFIED IN N.E.C. SECTIONS
250 -50 AND 250 -52 WHERE THE PRECEDING ELECTRODES ARE NOT AVAILABLE.
4. 600 KCMIL CONDUCTORS SHALL BE COORDINATED WITH PROPER TERMINATION LUGS OR PROVIDED WITH MAC ADAPTERS
AS REQUIRED TO COORDINATE WITH STANDARD BREAKER LUG SIZES.
FEEDER SCHEDULE
BASED ON N.E.C. TABLE 310 -16 FOR COPPER CONDUCTORS
FEEDER
SYMBOL
CONDUCTORS (3 PHASE,
3 WIRE) WITH GROUND
RACEWAY
SIZE
CONDUIT
NOMINAL
AMPERE
RATING
CONDUCTORS (3 PHASE,
4 WIRE) WITH GROUND
RACEWAY
SIZE
CONDUIT
FEEDER
SYMBOL
I
3 *8 A I *10G.
Y4'
50
4 *8 & 1 *10G.
1"
2
3
306 is 1 *10G.
74'
GO
4 *6 A l *TOG.
1"
4
5
3 *4 is I *8G.
1'
70
4 *4 is I *IG.
1 1/4'
G
7
303 A I08G.
1 1/4'
100
4 *3 is I *8G.
1 1/4'
8
9
3 *1 is I *6G.
1 1/2'
125
4 *1 i 1 *6G.
2"
0
II
3 *1 /0 A I" GG.
I V2'
150
4 *1 /0 & 106G.
2"
2
13
3 *2/0 & I*GG.
2'
175
402/0 is 1 *6G.
2"
4
15
3 *3/0 A IOGG.
2'
200
4 *3/0 A I *GG.
2"
G
7
3 *4/0 is 1 *4G.
2"
225
4 *4/0 is 1 *4G.
2 %2'
i
9
3 *250 KCMIL is 1 *4G.
2 1/2'
250
4 *250 KCMIL is 1 *4G.
2 %2"
0
21
3 *350 KCMIL A 1*4G.
3-
300
4 *350 KCMIL A 1*4G.
3"
22
23
3 *500 KCMIL & I *3G.
3 V2'
350
4 *500 KCMIL is 1 *3G.
3 %2'
4
25
3 *600 KCMIL & 1 *3G.
3 1/2'
400
4 *600 KCMIL is 1 *3G.
All
G
27
6 *250 KCMIL A 2 *2G.
2-2 %2"
500
8 *250 KCMIL is 2 *2G.
2 -2 %2"
i
9
6 *350 KCMIL & 2 *IG.
2 -3'
600
8 *350 KCMIL & 2"IG.
2 -3"
0
31
6 *500 KCMIL t. 2 *1 /OG.
2 -3'
700
8 *500 KCMIL A 2 *1 /OG.
2 -3 %2"
2
3
6*600 KCMIL & 2 *1 /OG.
2-3 y2"
800
8 *600 KCMIL A 2 *1 /OG.
2 -4"
9 4
35
9 *400 KCMIL is 3 *2 /0G.
3 -3'
1000
12 *400 KCMIL A 3 *2 /OG.
3 -3"
G
37
9 *600 KCMIL is 3 *3 /OG.
3 -3 Y2"
1200
12 *600 KCMIL tc 3 *3 /OG.
3 -4'
B
9
12 *600 KCMIL A 404/OG.
4 -3 %2"
1600
I6*600 KCMIL A 4 *4 /OG.
4 -4'
40
41
15 *600 KCMIL & 5 *250G.
5 -3 %2"
2000
20 *600 KCMIL II 50250G.
5 -4'
42
43
18 *600 KCMIL is 6*350G.
6-3 %2'
2500
240600 KCMIL is 6*350G.
6-4"
44
45
21- 50 KCMIL is 70400G.
7-4"
3000
280750 KCMIL is 7 *400G.
7 -5'
46
47
27 *750 KCMIL is 905006.
1 9 -4'
4000
360750 KCMIL & 90500G.
9 -5'
48
NOTES:
I. 600 KCMIL AND 750 KCMIL FEEDERS SHALL BE COORDINATED WITH PROPER TERMINATION LUGS OR PROVIDED
WITH MAC ADAPTERS AS REQUIRED TO COORDINATE WITH STANDARD BREAKER LUG SIZES.
2. SEE SPECIFICATIONS FOR ACCEPTABLE CONDUCTOR TYPES.
PROVIDE JUMPERS TO CONNECT to
ACROSS SEPARATE SECTIONS ""\L
TO ENSURE CONTINUOUS BOND.
PROVIDE INSULATED *6 GROUNDING
CONDUCTOR TO BOND ALL RACKS,
CABINETS AND CABLE TRAY, ETC.
EQUIP. *4AWG IN 1'C
RACK
z
0.25'x4'x12' GROUND
BUS WITH 20
`7p PRE -DRILL DINHOLES.
w
GENERAL NOTES:
A. ALL GROUND BUSES SHALL BE COPPER,
UL LISTED AND PRE- DRILLED WITH HOLES
FOR USE WITH STANDARD SIZE LUGS.
B. MOUNT ALL GROUND BUSES IN ACCESSIBLE
LOCATIONS WITH ISOLATORS.
C. ALL CONNECTIONS SHALL BE MADE WITH
LISTED CONNECTORS OR BY EXOTHERMIC
WELDING TO COMPLY WITH NEC ART 250.64(C).
D. LABEL EACH TERMINATION TO IDENTIFY
THE DESTINATION OF THE CONDUCTOR.
E. USE EMT FOR ALL GROUNDING CONDUCTORS
INDICATED TO BE INSTALLED IN CONDUIT
WITHIN THE BUILDING. BOND EACH END OF
THE CONDUIT TO THE GROUNDING CONDUCTOR
USING GROUNDING BUSHINGS.
TO OTHER
GROUNDING
BUS BARS
TO STEP DOWN
TRANSFORMER
SECONDARIES
3:
EAST TOWER
60OKW
120 /208V
NAQP1 3PH, 4W
7
; 01
TO OTHER
GROUNDING
BUS BARS
EXISTING GROUNDING
BUS IN EXISTING
IT CLOSET
SEVENTH FLOOR
EXISTING TELECOMMUNICATIONS
MAIN GROUNDING BUS BAR IN
THE DATA CENTER.
SECOND FLOOR
STRUCTURAL
STEEL
EXISTING MAIN ELECTRICAL
GROUNDING BUS IN CENTRAL PLANT
CONNECTION TO LIGHTNING
PROTECTION SYSTEM
GROUND I NG DETAIL
N.T.S.
FIRST FLOOR
COLD WATER PIPE
4
5
PAV IL ION
1000 BOOKW ROOKW 100KW
0
i•••
•••
•
*
••••• •i•
07 -03 -12
NO.
DESCRIPTION
DATE
REVISIONS /ISSUES
• •
r •
r
u
• •
Architect of Record:
•
.
• • •
•
r
r •
•
•
•
.•
..r
•`•
A
R
R
A
Y
••••
•••••
••
Arch
itects
P.C.
IhUKVA
2 SETS OF
4 *300, 1 *I /OG AL.
IN 3.5" C. EACH
2DLE
500
CRITICAL
BRANCH
4 *300, I*2G AL. 4 *3/0, 1''4G AL.
IN 3.S" C IN 3.5" C.
5E1 5E2 4E2
225 225 I 50
CRITICAL CRITICAL CRITICAL
BRANCH BRANCH BRANCH
L_
4 *300, 1 *2G AL. 01
IN 3.5" C.
01
GE1 6E2
225 I 225
CRITICAL I CRITICAL
BRANCH L BRANCH Q
4 *300, 1 #2G AL. 01
IN 3.5" C
711 782 �7E2B�
225 225 I 225
CRITICAL CRITICAL I CRITICAL
BRANCH BRANCH BRANCH
L_ -:�j
PARTIAL ELECTRICAL RISER
N.T.S.
KEYED NO TES :
01 EXISTING PANEL MODIFIED UNDER THE SCOPE OF THIS PROJECT.
CONTRACTOR SHALL PROVIDE NEW TYPED DIRECTORY.
61_5
225
NORMAL
BRANCH
71_5
225
NORMAL
BRANCH
L_
01
4 *300, 1 *2G AL.
IN 3.5" C.
4 *300, 1 *20 AL.
IN 3.5" C.
healthcare facilities solutions
6800 Broken Sound Boulevard NW
Suite 125
150172 Raton, FL 33487
t: 561.995.1700
f: 561.995.1701 firm license number
www.arrayhfs.com AA2600830
SEAL:
r1141'S, 0 %,�q''�,
•••�OEN
No, 5851
• ��
0NAIL�
CONSULTANTS:
Smith
W"%L Sec an
Reid, Inc.
600 West Hillsboro, Suite 300
Deerfield Beach, FL 33441
(954) 421 -1260
FAX: (954) 421 -1466
www.ssr- ine.com
Firm Certification - EB- 0000857
Dennis O. Davis PE - 58598
John E. Moulder PE - 33200
SSR JOB # 1232010.0
OWNER:
BAPTIST HEALTH SOUTH
FLORIDA
HOSPITAL:
SOUTH MIAMI HOSPITAL
PROJECT:
INTERIOR
RENOVATIONS FOR
.CENTRAL MONITORING
ADDRESS:
6200 . Southwest 73rd Street
j South Miami, FL 33143
AH CA:
CLIENT CODE /FILE NUMBER: 23/100154
PROJECT ID /SUBMISSION NUMBER: 187 -1
2
Bid and Permit Set
07 -18 -12
1
AHCA Stage III
07 -03 -12
NO.
DESCRIPTION
DATE
REVISIONS /ISSUES
SHEET TITLE:
ELECTRICAL RISERS
DRAWN: CHECKED:
CON /REF No. 0000
PROJECT No. 3606
DATE: 07 -03 -12 SCALE: As lndicQted
SHEET NO.
E40