12-984-044
1_ 2 E. C cla u O , I' II 0o r: CSC 0 91 SLEEVES AND THROUGH PENETRATIONS SECTION 15103 SLEEVES AND THROUGH PENETRATIONS PART 1 - GENERAL 1.01 WORK INCLUDED A. Provide sleeves for piping installed under this Division as specified herein. B. Seal pipe penetration as specified herein. 1.02 COORDINATION f A. Coordinate requirements of through penetration firestopping with Division 7. 1.03 RELATED WORK i A. Division 7: Firestopping 1.04 REFERENCES A. UL Fire Resistance Directory, latest edition. B. ASTM - E814 -88: Standard Test Method for Fire Tests of Through -Penetration Firestops. PART 2 - PRODUCTS 2.01 SLEEVES A. Materials 1. Concrete floors, concrete and masonry walls: 18 gauge galvanized sheetmetal. 2. Drywall partitions: 18 gauge galvanized steel sheet metal. B. Sleeves shall be sized such that the annular space between outside surface of pipe or pipe Insulation and the inside surface of the sleeve is not less than 1/2 ". Provide larger annular space if required by firestopping product Installation Instructions. C. Sleeves supporting riser piping 4" and larger shall have three 6" long reinforcing reds welded radically at 120 degree spacing to the sleeve and shall be installed with the rods embedded In the concrete slab. i 2.02ESCUTCHEON PLATES A. Provide S & C No. 10 or equal chrome plated escutcheon plates where pipes penetrate partitions or ceilings in finished areas. PART 3 - EXECUTION 3.01 INSTALLATION A. Sleeves: 1. Floors: sleeve all pipe penetrations. Extend sleeve 1 -1/2" above finished floor, except piping within pipe chases. sleeve shall be flush with underside of floor, 2. Masonry or concrete walls: sleeve all pipe penetrations. Sleeves shall be flush on both sides of wall. 3. Drywall partitions: sleeve all penetrations of piping in systems over 160 F. 4. Seal voids between outside surface of sleeve and wall, partition or floor. Seals shall be airtight. 5. Install piping, Insulation and sleeves in strict accordance with applicable U.L. floor or partition assembly instructions. Coordinate with Division 7 firestop manufacturer's installation Instructions. B. Penetrations not sleeved or firestopped: 1. Seal voids between pipe and partition. Seals shall be airtight. C. Escutcheon Plates 1. Provide chromium plated escutcheon plates for exposed uninsulated pipes projecting through floors or walls in I "finished" spaces. Mechanical rooms, storerooms, electric closets, and janitors closets are not considered "finished" spaces. I a. Clearance between sleeve and pipe: Minimum of 1/2 inch for hot piping and 1 Inch for cold piping or as otherwise dictated by UL Fire Resistance Directory. fI 1 PLUMBING SYSTEMS INSULATION I SECTION 15250 PLUMBING SYSTEMS INSULATION PART 1 - GENERAL 1.01 DEFINITIONS A. Exposed - Equipment, ducts and piping in areas which will be visible without removing ceilings or opening access panels. S. Concealed - Installed above ceiling, in walls or chases. C. Outdoors - Exposed to the weather or ambient conditions. D. Underground - Burled. 1.02 CERTIFICATION /QUALITY ASSURANCE A. Insulation, adhesives, coatings, sealers, tapes, shall have a flame spread rating of 25 or less and smoke development of 50 or less In accordance with ASTM E -84 and UL 723 B. Materials shall meet the requirements of NFRA 90 -A, i 1.03 SUBMITTALS A. Submit manufacturer's product data and installation procedures for review. PART 2 - PRODUCTS 2.01 PIPE AND EQUIPMENT INSULATION A. Materials for Pipe and Equipment: Provide factory premolded or shop or site mitered segment type insulation for pipe, pipe fittings, and valves. S. Fitting Insulation: Same thickness and material as adjoining pipe insulation. C. Flexible Tubular Elastomeric: 1. Provide fire- retardant closed -cell slip -on flexible type. Minimum "R" value of 2.57. 2. Acceptable manufacturers: LS manufactured by K -Flex USA. 3. Use on the following services: a. Moisture condensate drains - 1" thick, LS 3ft white seal seam. D. Fiberglass Pipe Insulation: 1. Acceptable manufacturers: Johns - Manville "Micro -Lok 850 "; CertainTeed; Knauf; Owens Corning. Fester Jacket: ASJ fiberglass reinforced kraft paper with aluminum foil and minimum R value of 3.6. 2. Use on the following services: a. Horizontal and vertical rain water leaders and overflow storm and reef drain bodies 1" thick. 2.02 MATERIALS FOR FITTINGS, VALVES, AND SPECIAL COVERINGS A. For all services, use premolded insulation for pipe fittings, elbows, tees, butterfly valves, and couplings 2 -1/2 and larger. Finish shall be as specified under Products above or as specified below. PVC fitting covers may be used I over the premolded insulation for: 1. Rainwater and Overflow Storm Piping B. For pipe fittings, valves, strainers, and other Irregular surfaces, when inside building or in equipment rooms, cover l insulation with white colored woven glass fabric embedded in white vapor barrier coating, Faster 30 -35 or equal. Provide removable section for pump, strainer, etc. service requirements. PART 3 - EXECUTION 3.01 INSTALLATION - GENERAL A. Deliver and store Insulation materials in manufacturers containers and kept free from dirt, water, chemical and mechanical damage. S. Complete piping pressure testing prior to applying insulation. C. Apply Insulation In workmanlike manner by experienced, qualified, workmen. D. Surfaces shall be clean and dry when covering Is applied. Covering to be dry when installed and before and during application of any finish, unless such finish requires specifically a wetted surface for application, E. Adhesives, cements and mastics shall be compatible with materials applied and shall not attack materials in either wet or dry state. F. Stop duct coverings, including jacket and insulation, at fire penetrations of fire or smoke rated partitions, floors above grade and reefs. "Fan -out" or extend jacketed Insulation at least 2" beyond angle frames of fire dampers and secure to wall. Maintain vapor barrier. 4 5. 3.02 INSTALLATION OF RIPE COVERING A. Where glass fiber or flexible tubular elastomeric insulation is used on piping sized 2" and larger, insert a section of foamglass or calcium silicate insulation, at hanger or support points, between pipe and metal shield for full length of shield, to prevent crushing of insulation. Where insulation passes through pipe hangers and across trapeze supports, 12" long metal saddles shall be used. Insulation thickness to be same as adjoining glass fiber insulation. On cold pipe, vapor barrier should be carried through the hanger and sealed. Saddles shall be used where rigid foamglass inserts are not acceptable. B. Apply flexible tubular elastomeric insulation to pipe and fittings with all joints tightly fitted and sealed with adhesive. PLUMBING SECTION 15400 PLUMBING PART 1 - GENERAL 1.01 WORK INCLUDED A. This section includes requirements for: 1. Cleanouts. 1.02 RELATED WORK A. Section 15010: Basic Mechanical Requirements B. Section 15050: Basic Materials and Methods C. Section 15060: Piping and Fittings D. Section 15061: Pipe Hangers E. Section 15250: Mechanical Systems Insulation 1.03 SUBMITTALS A. Submit product data for review. PART 2 - PRODUCTS 2.01 ACCEPTABLE MANUFACTURERS A. Acceptable manufacturers are indicated in subsequent paragraphs. 2.02 CLEANOUTS A. Acceptable manufacturers; 1. Wade. 2. Zurn. 3. Sioux Chief 4, Josam S. Jay R. Smith B. Zurn model numbers are used below. C. Finished concrete floor: ZB1400 -NL cast iron body with round adjustable polished nickel bronze top, ASS plug and carpet marker where required, D. Ceramic tile: Z51400 -TX series, cast iron body, polished nickel bronze top, 1/2" terrazzo recess and closure plug. E. Vinyl tile floor: ZN1400 -NL -X series, cast Iron body, round nickel bronze top, 1/8" the recess and closure plug. F. Carpet: ZN1400NL. Inside caulk round brass scoriated frame and cover and provide carpet marker. G, Wall: 1440 Cast iron caulking ferrule with stainless round access cover and screws. H. Access covers: Minimum size 12" x 12" located for access to valves, shock absorbers, trap primers, wall cleanouts, etc. I. Furnish cleanouts occurring in waterproof floors with clamping devices. J. Provide heavy duty floor cleanouts at exterior of building and within mechanical and pump rooms. PART 3 - EXECUTION 3.01 INSTALLATION AND TESTING A. Cleanouts 1. Provide line size cleanouts up to 4 "; 4" cleanout for lines larger than 4 ". 2. Locate cleanouts at all changes in direction greater than 45 degrees and in straight runs as shown 100 feet outside the building on drawing or spaced not greater than required by applicable Plumbing Code. 3. Extend inaccessible cleanouts up through floor and /or wall to provide easy accessibility. � 7 •••• ••• • • ••.•• •c• •rY•.fy Wr••y •yl.•Archl.ect of Record; .....• ARRAY • •• or• ••• 4..c Arch itects P.C. �taithcare facilities solutions 6800 Broken Sound Boulevard NW Suite 125 Boca Raton, FL 33487 t: 561.995.1700 f: 561.995.1701 firm license number www.2rrayhfs.com AA2600880 SEAL: / 1 \�ti�l'l1111ifJ >> r •M U :-10F Ile ONAL CONSULTANTS: SR Smith Seckman Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- ine.com Firm Certification - EB- 0000857 Dennis O. Davis PE - 58588 John E. Moulder PE - 33200 SSR JOB * 1232010.0 HOSPITAL: SOUTH MIAMI HOSPITAL PROJECT: NTERIOR RENOVATIONS FOR CENTRAL MONITORING ADDRESS: 6260 Southwest 73rd Street South Miami, FL 33143 AHCA: CLIENT CODE /FILE NUMBER: 23/100154 PROJECT ID /SUBMISSION NUMBER: 187 -1 2 Bid and Permit Set 07-18-12 1 AHCA Stage III 07 -03 -12 NO. DESCRIPTION DATE REVISIONS /ISSUES DRAWN: CHECKED: CON/REF No. 0000 PROJECT No. 3606 DATE: 07 -03 -12 SCALE: As Indicated SHEET NO. P0.3 hi;� 1c %urnpnt r n .oa,'iJ- Fr !ecte� inetruma'- r,' ?ni. , ;:'cier� ct AzF,A° ■nd licen3e l `ar ,a (, in 11 , 4tI,i pro, : � d). : I;n wiho�t writ-.?n pe n -rsior of AP�A' i legal a0 will be; ;2c.itetl n�nr -f- law. ©COPYRIGHT - 2012 ARRAY HFS