COMPUTER nTER ROOM A�R COND�T�ON�NQ
U w n T SCHEDULE LE
�
UNITS SHALL If PROVIDED WITH THE FOLLOWING:
G FOR MONITORING /CONTROL.
EFFICIENCY MOTORS G. COCT {� FRACI
MFGR R MODEL
CFM RANGE
FACE SIZE /
MODULE SIZE
2.
2. INTELLISLOT WEB /415 CARD
C INA S
REMARKS
A
06660 **Ova
r goose
0-100
4
2 "♦
tx1 / W ♦
23:
• •
......
4. SMOKE DETECTOR
101-200
-
210
'.Y•v Y•9 '
.... ..
5. 2 WAY MODULATING CONTROL VALVE
C
TITUS TMS-AA
201-325
�4rchiteC,� of�ccdrd:: .
COMPUTER nTER ROOM A�R COND�T�ON�NQ
U w n T SCHEDULE LE
�
UNITS SHALL If PROVIDED WITH THE FOLLOWING:
G FOR MONITORING /CONTROL.
EFFICIENCY MOTORS G. COCT {� FRACI
MFGR R MODEL
CFM RANGE
FACE SIZE /
MODULE SIZE
NECK SIZE
2. INTELLISLOT WEB /415 CARD
C INA S
REMARKS
A
TITUS TMS -AA
0-100
3. NON- LOCKING DISCONNECT SWITCH
2 "♦
tx1 / W ♦
23:
B
4. SMOKE DETECTOR
101-200
24x24 / 24x24
210
10x6/8" •
3-5-5
5. 2 WAY MODULATING CONTROL VALVE
C
TITUS TMS-AA
201-325
24x24 / 24x24
10 "♦
12x8/ 10" ♦
4-'i-13
FAN
FAN MOTOR
COOLING COIL - 72F 507 RH
(HI04 FAN
SPEED)
12 "0
ELECTRIC (W1 3.6 KW REHEAT)
OPERATING
DIMENSIONS
E
(DENT.
AREA SERVED
TYRE
MANUFACTURER
MODEL NO.
WEIGHT
INCHES
REMARKS
CFM
ES'
WATT
ELECTRIC
TOTAL
SENSIBLE
GPM E.W.T. 'F
L.W.T. 'F
I
MAX W.R.D.
BRANCH
KW
FLA
WSA
ORD
H
TITUS 300FL
301.550
11x10/20x12
19x10
11x101-
LL
1
TITUS 50F
0-180
ixt / 10x10
8x9
LSS.
LxWxH
CRAC -7 -1
110. MED CLOSET =701
CEILING MOUNTED
LIESERT
MM023C
750
0.3
0.2
201 /150
13100
13000
2.6
45
56
2
3.1
-
3.6
26.4
33.0
35.0
220
56X22XI9
1 -6
5
TITUS 50F
651 -850
16x1tl24x24
16x16
22x10/18" •
6
TITUS 50F
451-1000
18x18 / 24x24
12x12
28x10 / 19"
7
TITUS 5OF
1001.1900
itx11 /24x24
22x22
-/-
-
AIR DEVICE SCHEDULE
1. AIR DEVICE SIZES L SCHEDULED AIRFLOW ARE BY THIS SCHEDULE UNLESS OTHERWISE NOTED ON HVAC FLOOR PLANS.
2. BRANCH 9 OPTIONAL BRANCH DUCT SIZES ARE BY THIS SCHEDULE UNLESS OTHERWISE NOTED ON HVAC FLOOR PLANS.
3. ALL AIR DEVICES INSTALLED IN INACCESSIBLE AND /OR DRYWALL CEILINGS SHALL BE PROVIDED WITH MANUAL OPPOSED BLADE DAMPERS.
4. ALL AIR DEVICES INSTALLED IN ACCESSIBLE AND /OR LAY -IN CEILINGS SHALL HAVE A
MANUAL VOLUME DAMPER INSTALLED IN THE BRANCH TAKE -OFF. BRANCH
5. MAXIMUM PRESSURE DROP FOR ALL AIR DEVICES SHALL NOT EXCEED 0.10 IN, W.G. MAIN RUNOUT SQUARE TO
S. ALL AR DEVICES SHALL BE WHITE UNLESS OTHERWISE NOTED. MVD ROUND ADAPTER
7. MAXIMUM NC RATING FOR ALL AIR DEVICES SHALL NOT EXCEED 25,
8. ALL AIR DEVICES SHALL BE ALUMINUM CONSTRUCTION UNLESS OTHERWISE NOTED. DIFFUSER
Lil
t. THROW VALUES ARE GIVEN FOR TERMINAL VELOCITIES OF 150, 100 A 50 FPM RESPECTIVELY, OR GRILLE
MARK
MFGR R MODEL
CFM RANGE
FACE SIZE /
MODULE SIZE
NECK SIZE
BRANCH DUCT SIZE
THROW
REMARKS
A
TITUS TMS -AA
0-100
12x121 12xl2
2 "♦
tx1 / W ♦
23:
B
TITUS TMS -AA
101-200
24x24 / 24x24
210
10x6/8" •
3-5-5
C
TITUS TMS-AA
201-325
24x24 / 24x24
10 "♦
12x8/ 10" ♦
4-'i-13
D
TITUS TMS-AA
326-525
24x24 / 24x24
12 "0
14x10 / 12" ♦
541-16
E
TITUS TMS-AA
$25.700
24x24 / 24x24
14 "0
16x10114" ♦.
6- 10-119
F
TITUS 300FL
0 -125
SX61.lox$
8x9
8x61-
9 -11 -16
G
TITUS 300FL
126 -300
12x1 /14x10
12x8
12x8/-
12 -10 -25
H
TITUS 300FL
301.550
11x10/20x12
19x10
11x101-
16.23.34
1
TITUS 50F
0-180
ixt / 10x10
8x9
10x619" ♦
-
2
TITUS 5OF
191 -300
10xl0/24x24
1000
12x8/10" ♦
3
TITUS 50F
301.450
12xl2/24x24
12x12
14x10/12" •
4
TITUS 50F
451 -650
14xl4/24x24
14x14
16x10114"
5
TITUS 50F
651 -850
16x1tl24x24
16x16
22x10/18" •
6
TITUS 50F
451-1000
18x18 / 24x24
12x12
28x10 / 19"
7
TITUS 5OF
1001.1900
itx11 /24x24
22x22
-/-
-
9
TITUS 350FL
0-125
8x6 610x9
8x6
2xG / -
t
TITUS 350FL
126 -225
124 / 14x10
10x1
12x91-
10
TITUS 350FL
296 "440
18x10 /20x12
18xi0
12x10/ -
SCOPE OF WORK
ADDITION OF NEW SUPPLY AND RETURN AIR GRILLES.
ADDITION OF NEW FIRE DAMPERS.
ADDITION OF NEW COMPUTER ROOM AIR CONDITIONING UNIT.
AHU OPERATION DURING CONSTRUCTION
THE USE OF NEW OR EXISTING AIR HANDLING UNITS DURING CONSTRUCTION IS PROHIBITED
UNLESS APPROVED BY THE OWNER AND THE PROCEDURES OUTLINED IN THIS PARAGRAPH
ARE FOLLOWED RIGIDLY.
1. THE CONTRACTOR SHALL PROTECT THE INTERIOR OF ALL DUCTWORK AND AIR
HANDLING UNITS FROM THE ACCUMULATION OF DIRT AND DUST USUALLY
ASSOCIATED WITH THE FINISHING STAGES OF THECONSTRUCTION WORK.
2. DUCTWORK STORED ON SITE AWAITING INSTALLATION SHALL BE CAREFULLY
EXAMINED AND THOROUGHLY CLEANED BEFORE PLACEMENT IN ITS FINAL LOCATION.
THE ENDS OF DUCTWORK SHALL BE CLOSED DURING CONSTRUCTION.
3. THE AIR HANDLING UNITS WILL BE ALLOWED TO OPERATE DURING THE FINISHING
STAGES OF THE GENERAL WORK PROVIDED THE PRE- FILTERS ARE IN PLACE AND
THE ENDS OF ALL RETURN AIR INLETS ARE COVERED WITH ROLL -UP FILTER MATERIAL.
+4. WHEN THE SPACE IS TURNED OVER TO THE OWNER, THE CONTRACTOR SHALL REMOVE
ALL FILTERS USED DURING CONSTRUCTION AND REPLACE THEM WITH NEW FILTERS.
5. USE OF NEW AHU'S DURING CONSTRUCTION IS NOT ALLOWED.
G. FSD'S SHALL BE INTERLOCKED WITH ASSOCIATED AHU (AND /OR EF) AND SHALL
OPERATE PER CONTROL SEQUENCE.
MECHANICAL DEMOLITION NOTES
1. FOR EQUIPMENT AND SYSTEMS TO REMAIN IT SHALL BE THE CONTRACTOR'S
RESPONSIBILITY TO VERIFY THE CONDITION OF, EXACT SIZES AND LOCATION OF
EXISTING DUCT AND PIPING ETC. BEFORE DEMOLITION WORK IS BEGUN. REPORT
ANY DISCREPANCIES BETWEEN PLANS AND ACTUAL FIELD CONDITIONS TO THE
OWNER AND ENGINEER PRIOR TO THE COMMENCEMENT OF DEMOLITION WORK.
2. REMOVE THE INDICATED HVAC ITEMS AS SHOWN ON PLANS, THIS INCLUDES ALL
HANGERS, STRAPS AND RELATED MATERIAL. AS DIRECTED THIS MATERIAL
SHALL BE REMOVED FROM THE SITE OR TURNED OVER TO THE OWNER ( AS
DIRECTED BY THE OWNER).
3. CAP AND SEAL AIR TIGHT ALL POINTS AT WHICH DUCTWORK IS REMOVED FROM
DUCTWORK THAT WILL REMAIN.
4. PATCH AND MATCH OPENINGS IN WALLS TO MAINTAIN THE INTEGRITY OF THE
WALL WHERE AIR DEVICES, DUCTS, PIPING, ETC. HAVE BEEN REMOVED.
(MAINTAIN THE EXISTING RATINGS).
5. CONTRACTOR SHALL VERIFY CLEARANCE REQUIREMENTS AND INDICATE
ROUTING OF NEW DUCTWORK BEFORE FABRICATION BEGINS AS RISES AND
DROPS MAY BE NECESSARY DUE TO EXISTING FIELD CONDITIONS.
G. ALL DEMOLITION WORK SHALL COMPLY WITH NFPA 241 AND THE REQUIREMENTS
OF THE OWNER.
OWNER) TEST & BALANCE NOTES
I. PRECONSTRUCTION:
PRIOR TO COMMENCEMENT OF ANY HVAC WORK AN INDEPENDENT AABC OR NEBB
CERTIFIED TAB CONTRACTOR SHALL MEASURE AND DOCUMENT, IN A TYPED REPORT
THE AIRFLOW QUANTITIES PROVIDED OR EXHAUSTED BY ALL EXISTING
EQUIPMENT AND DUCTS TO REMAIN THAT SERVE OR ARE SERVED FROM THE
RENOVATED AREA. SUBMIT TYPE WRITTEN DATA TO ENGINEER FOR REVIEW.
THE FOLLOWING INFORMATION IS REQUIRED:
- AIR FLOW OF ALL AIR DEVICES IN RENOVATED AREA(S).
- AIR FLOW (TRAVERSE) AT MAINS AND BRANCH DUCTS SERVING THE RENOVATED
AREA(S).
AIR FLOW AT UNITS (TRAVERSE) AT MAINS AND BRANCH DUCTS SERVING THE
RENOVATED AREA(S).
- SUCTION AND DISCHARGE STATIC AT UNITS SERVING THE RENOVATED AREA(S).
- MEASURED FAN RPM, MOTOR AMPERAGE FOR ALL UNITS SERVING THE RENOVATED
AREA(S).
- PROVIDE EXISTING UNIT AND MOTOR NAME PLATE DATE.
2. FINAL CONSTRUCTION:
UPON COMPLETION OF THE HVAC RENOVATION WORK, THE SAME CONTRACTOR SHALL
REBALANCE THE NEW AND EXISTING EQUIPMENT AND DUCTS TO PROVIDE INDICATED
AIR QUANTITIES TO THE RENOVATED SPACE. ANY ADDITION OF DAMPERS.
ADJUSTMENTS, (FAN SPEED, CHANGE OUT OF PULLEYS, ETC.) REQUIRED FOR THIS SHALL
BE INCLUDED IN THIS CONTRACTORS PROPOSAL.
3. FINAL REPORT:
SUBMIT FINAL TEST AND BALANCE REPORT TO ENGINEER FOR REVIEW AND ACCEPTANCE
ONE WEEK PRIOR TO FINAL AHCA INSPECTION FOR EACH PHASE.
4. PRE -TEST A BALANCE:
IF PRE TEST AND BALANCE IS NOT COMPLETED IT IS THE SOLE RESPONSIBILITY OF
THE CONTRACTOR TO BALANCE ANY AND ALL SYSTEMS REQUIRED TO CREATE A
PROPERLY BALANCED SYSTEM.
HAZMDOUS MATERIAL NOTES
I. PORTIONS OF THE EXISTING SYSTEM MAY CONTAIN HAZARDOUS MATERIAL
(ASBESTOS). COORDINATE WITH THE OWNER TO DETERMINE THE LOCATION
AND TYPES OF HAZARDOUS MATERIALS.
2. THE OWNER IS RESPONSIBLE FOR THE IDENTIFICATION, REMOVAL AND
DISPOSAL OF HAZARDOUS MATERIAL AND IS NOT TO BE INCLUDED AS
PART OF THE WORK OF THIS CONTRACT UNLESS SPECIFICALLY IDENTIFIED
AS SUCH.
3. IF ANY MATERIAL APPEARS TO CONTAIN HAZARDOUS MATERIAL AND WAS
NOT PREVIOUSLY IDENTIFIED. THE CONTRACTOR IS TO INFORM THE OWNER
TO RECEIVE INSTRUCTIONS ON HOW TO PROCEED.
MECHANICAL AS- BUILTS NOTE
MECHANICAL CONTRACTOR IS REQUIRED TO SUBMIT MECHANICAL AS BUILT PLANS
UPON COMPLETION OF THE PROJECT. COMPLETION IS DEFINED AS THE OWNER
RECEIVING A 'CO' AND MECHANICAL INSPECTOR HAS FINALIZED AND APPROVED THE
INSTALLATION.
AS BUILTS SHALL BE SUBMITTED IN ELECTRONIC FASHION IN EITHER AUTOCAD FORMAT
OR SCANNED FILES IN PDF FORMAT.
AS BUILTS SHALL BE LEGIBLE AND NEAT. AS BUILTS WILL BE RETAINED BY
ARCHITECT AND ENGINEER FOR RECORD OF CHANGES TO THE SYSTEM. AS BUILTS WILL
BE SUBMITTED TO OWNER THROUGH ARCHITECT AND ENGINEER.
MECHANICAL DOS'T1NC3 FIELD CONDITIONS
MECHANICAL CONTRACTOR IS REQUIRED PRIOR TO FINAL INSPECTIONS TO LABEL ALL
NEW AND EXISTING PIPES, VALVES, BOXES, AHU'S, FAN COILS, ETC. WITH
PROPER TAGS AND LABELS. (SEE BOOK SPECIFICATIONS FOR LABELING).
CONTRACTOR SHALL WORK WITH OWNER /FACILITIES STAFF TO DETERMINE ALL
EXISTING SERVICES FUNCTIONS, SOURCES, NAMES, ETC FOR PROPER IDENTIFICATION.
ALL IDENTIFICATIONS SHALL BE CLEARLY NOTED ON AS BUILT CONDITIONS AND SHALL
BE TURNED OVER TO OWNER AND DESIGN TEAM FOR FINAL RECORDS.
CONTRACTOR IS REQUIRED TO HAVE LABELING AND IDENTIFICATION COMPLETED
PRIOR TO 757 INSPECTIONS AND /OR COMPLETION OF CONSTRUCTION.
u • lI
�y
u v
u�
i Y Y
R A Y
• '•rch itects P.C.
4
_,liealfh1carc• °facilities solutions
6200 Broken Sound Boulevard NW
Suite 125
BOU Raton, FL 33487
t: 561.995.1700
f: 561."5.1701 firm license number
wwwarrayhfs.com AA2600EE0
SEAL:
CONSULTANTS:
'ra ; �(• T�TE Of
/1,...,t %%
Smith
Seckman
Reid, Inc.
600 West Hillsboro, Suite 300
Deerfield Beach, FL 33441
(954) 421 -1260
FAX: (954) 421 -1466
www.ssr- inc.com
Firm Certification - EB- 0000857
Dennis O. Davis PE - 58588
John E. Moulder PE - 33200
SSR JOB # 123 20 10.0
OWNER:
BAPTIST HEALTH SOUTH
FLORIDA
HOSPITAL:
SOUTH MIAMI HOSPITAL
PROJECT:
INTERIOR
RENOVATIONS FOR
CENTRAL MONITORING
ADDRESS:
6200 Southwest 73rd Street
South Miami, FL 33143
AHCA:
CLIENT CODE /FILE NUMBER: 23/100154
PROJECT ID /SUQMISSION NUMBER: 187 -1
2
Bid and Permit Set
07 -15 -12
1
AHCA Stage III
07 -03 -12
NO.
DESCRIPTION
DATE
REVISIONS/ISSUES
DRAWN: CHECKED:
CON /REF No. 0000
PROJECT No. 3606