12-984-020. E ?I cr U C 0 c� i s 2 V") V) Q III M cri Ln cn 0- 0 +-d x N V v N V) V Ln v Un L 11 car , 0 l WE 17 co c� N c,a 0 cv -11 M co n N w IJ C 1 2 Design No. U419 May 09, 2012 Nonbearing Wall Ratings —1, 2,3 or 4 Hr (See Items 4 B 5) 3 4 1. Floor and Ceiling Runners — (Not shown) — For use with Item 2 - Channel shaped, fabricated from min 25 MSG corrosion- protected steel, min depth to accommodate stud size, with min 1 -114 in. long legs, attached to floor and ceiling with fasteners 24 in. OC max. 1A. Framing Members* - Floor and Ceiling Runners — Not shown - In lieu of Item 1— For use with Item 2A, proprietary channel shaped, min. 3-5/1 in. deep, fabricated from min. 0.015 in. (min bare metal thickness) galvanized steel, attached to floor and ceiling with fasteners 24 in. OC max. Effective thickness is 0.034 in. CLARKDIETRICH BUILDING SYSTEMS — UltraSTEEL& 1 B. Framing Members" - Floor and Ceiling Runners — (Not shown - In lieu of Item 1) — For use with item 2A, proprietary channel shaped, min. 2 -112 in. deep, fabricated from min. 0.015 in. (min bare metal thickness) galvanized steel, attached to floor and ceiling fasteners 24 in. OC. max. Effective thickness is 0.034 in. CLARKDIETRICH BUILDING SYSTEMS — UltraSTEELO. 1C. Framing Members* - Floor and Ceiling Runner — Not shown - In lieu of Item 1— For use with Item 2C, proprietary channel shaped runners, 3 -511 in. deep attached to floor and ceiling with fasteners 24 in. OC max, CALIFORNIA EXPANDED METAL PRODUCTS CO — Viper25'm Track CRACO MFG INC — SmartTrackT"I MARINOIWARE, DIV OF WARE INDUSTRIES INC — Viper25T"' Track PHILLIPS MFG CO L L C — Viper25T'" Track TELLING INDUSTRIES L L C — Viper25T1" Track * 1D. Framing embers - Floor and Ceiling Runner— Not shown - I — g g � n lieu of Item 1 For use with Item 2D, proprietary channel shaped runners,) -114 in. wide by 3-518 in. deep fabricated from min 0.020 in, thick ga[v steel, attached to floor and ceiling with fasteners spaced 24 in. OC max. CALIFORNIA EXPANDED METAL PRODUCTS CO — Viper20 Track MARINOIWARE, DiV OF WARE INDUSTRIES INC — Viper20T" Track PHILLIPS MFG CO L L C— Viper20TM Track TELLING INDUSTRIES L L C— Yper20T"' Track 1 E. Framing Members"— Floor and Ceiling Runners — (Not shown) — In lieu of Item 1- Channel shaped, attached to floor and ceiling with fasteners 24 in. OC. max. ALLSTEEL & GYPSUM PRODUCTS INC — Type SUPREME Framing System CONSOLIDATED FABRICATORS CORP, BUILDING PRODUCTS DIV — Type SUPREME Framing System QUAIL RUN BUILDING MATERIALS INC —Type SUPREME Framing Syste SCAFCO STEEL STUD MANUFACTURING CO —Type SUPREME Framing System STEEL CONSTRUCTION SYSTEMS INC —Type SUPREME Framing System UNITED METAL PRODUCTS INC —Type SUPREME Framing System 1 F. Floor and Ceiling Runners — (Not shown)- -For use with Item 26- Channel shaped, fabricated from min 20 MSG corrosion- protected or gals steel, min depth to accommodate stud size, with min 1 in. long logs, attached to floor and ceiling with fasteners spaced max 24 in. OC. 9 g 9 Pa 1 G. Framing Members * — Floor and Ceiling Runners — (Not shown, As an alternate to Item 1) — For use with items 2F, 5F or 5G or 51 only, channel shaped, fabricated from min. 0.015 in. (min bare metal thickness) galvanized steel, attached to floor and ceiling with fasteners 24 in. QC. max. CLARKDIETRICH BUILDING SYSTEMS —CD ProTRAK DMFCWIS L L C — ProTRAK MBA BUILDING SUPPLIES — ProTRAK SOUTHEASTERN STUD I COMPONENTS INC — ProTRAK STEEL STRUCTURAL SYSTEMS L L C — Tri -S ProTRAK TELLING INDUSTRIES L L C— TRUE- TRACKTu 1 H. Framing Members* - Floor and Ceiling Runner --• Not shown - In lieu of item 1— For use with Item 2G, proprietary channel shaped runners, minimum width to accommodate stud size, with 1 -118 in. long legs fabricated from min 0.015 in. (min bare metal thickness) gale steel, attached to floor and ceiling with fasteners spaced 24 in. OC max. SUPER STUD BUILDING PRODUCTS — The Edge 11. Framing Members* - Floor and Ceiling Runner — For use with Item 2H, proprietary channel shaped runners, minimum width to accommodate stud size attached to floor and ceiling with fasteners 24 in. OC max. STUDCO BUILDING SYSTEMS— CROCSTUD Track 1J. Floor and Ceiling Runners — (Not shown) — Channel shaped, fabricated from min 0.02 in. gals steel, min width to accommodate stud size, with min 1 in, long legs, for use with studs specified below and fabricated from min 0.02 in. galy steel or thicker, attached to floor and ceiling with fasteners spaced max 24 in. OC. MARINOIWARE, DIV OF WARE INDUSTRIES INC — Viper20Tm Track VT100. 2. Steel Studs — Channel shaped, fabricated from min 25 MSG corrosion- protected steel, min depth as indicated under Item 5, spaced a max of 24 in. OC. Studs to be cut 3/8 to 3/4 in. less than assembly height. 2A. Framing Members* - Steel Studs — In lieu of Item 2 - Proprietary channel shaped studs, min. depth as indicated under Item 5, fabricated from min. 0.015 in. (min bare metal thickness) galvanized steel, spaced a max of 24 in. OC. Studs to be cut 3/4 in. less than assembly height. Allowable use of studs is shown in the table below. For direct attachment of gypsum board only. Effective thickness is 0.034 in. CLARKDIETRICH BUILDING SYSTEMS — UltraSTEEL @. 2B. Steel Studs — (As an alternate to Item 2, For use with Items 5th & 5E) Channel shaped, fabricated from min 20 MSG corrosion- protected or galy steel, 3 -112 in. min depth, spaced a max of 16 in. OC. Studs friction -fit into floor and ceiling runners. Studs to be cut 518 to 314 in. less than assembly height. 2C. Framing Members' - Steel Studs — (As an alternate to Item 2, For use with Items 5C or 51) - Proprietary channel shaped studs, 3 -518 in. deep spaced a max of 24 in. OC. Studs to be cut 314 in less than the assembly height and installed with a % in. gap between the end of the stud and track at the bottom of the wall. For direct attachment of gypsum board only. CALIFORNIA EXPANDED METAL PRODUCTS CO — Viper2511" CRACO MFG INC — SmartStudT"I MARINOIWARE, DIV OF WARE INDUSTRIES INC — V1per25T"' PHILLIPS MFG CO L L C — Viper251 TELLING INDUSTRIES L L C — Viper25T"' 2D. Framing Members* - Metal Studs — Not shown - In lieu of Item 2 — For use with Item 1 D, proprietary channel shaped steel studs, min depth as indicated under Item 5, spaced a max if 24 in. OC, fabricated from min 0.020 in, thick galv steel. Studs cut 318 in. to 314 in. less in lengths than assembly heights. CALIFORNIA EXPANDED METAL PRODUCTS CO — Viper2011' MARINOIWARE, DIV OF WARE INDUSTRIES INC -- Viper20T"' PHILLIPS MFG CO L L C — Viper20Tm TELLING INDUSTRIES L L C — Viper20TM 2E. Framing Members' — Steel Studs — In lieu of Item 2 - For Use with Item 1 E- Channel shaped studs, min depth as indicated under Item 5, spaced a max of 24 in. 00. Studs to be cut 314 in. less than assembly height. ALLSTEEL k GYPSUM PRODUCTS INC — Type SUPREME Framing System CONSOLIDATED FABRICATORS CORP, BUILDING PRODUCTS DIV — Type SUPREME Framing System QUAIL RUN BUILDING MATERIALS INC —Type SUPREME Framing System SCAFCO STEEL STUD MANUFACTURING CO —Type SUPREME Framing System STEEL CONSTRUCTION SYSTEMS INC — Type SUPREME Framing System UNITED METAL PRODUCTS INC — Type SUPREME Framing System 2F. Framing Members * — Steel Studs — (Not shown, As an alternate to Item 2) —For use with Items 1 G, 5F or 5G or 51 only, channel shaped studs, min depth as indicated under item 5F, 5G or 51, fabricated from min. 0.015 in. (min bare metal thickness) galvanized steel, spaced a max of 24 in. OC. Studs to be cut 314 in. less than assembly height. CLARKDIETRICH BUILDING SYSTEMS — CD ProSTUD DMFCWBS L L C — ProSTUD MIA BUILDING SUPPLIES — ProSTUD SOUTHEASTERN STUD & COMPONENTS INC — ProSTUD STEEL STRUCTURAL SYSTEMS L L C — Tri -S ProSTUD TELLING INDUSTRIES L L C — TRUE- STUDT" 2G. Framing Members* - Metal Studs — Not shown - In lieu of Item 2 — For use with Item 1 H, proprietary channel shaped steel studs, minimum width indicated under Item 5,1 -114 in. deep fabricated from min 0.015 in. (min bare metal thickness) galvanized steel. Studs 318 in. to 314 in. less in lengths than assembly heights. SUPER STUD BUILDING PRODUCTS —The Edge in Members* - Steel Studs — Not shown - In lieu of Item 2 - For use with Item 11. Proprietary 2H. Framing p ry channel shaped studs, minimum width indicated under Item 5, Studs to be cut 318 to 314 in less than the assembly height. STUDCO BUILDING SYSTEMS — CROCSTUD Panel Sheathing — (Optional, For use with Item 5 Only.)- 3. Wood Structural Pa Not Shawn - 4 it wide 7116 in. thick oriented strand board OSB or 15132 in. thick structural 1 sheathing (plywood) complying uvit D - g (p ( ) { ) g (p yw ) h OC P51 or PS2, or APA Standard PRP 108, manufactured with exterior glue, applied horizontally or vertically to the steel studs. Vertical joints centered on studs, and staggered one stud space from wallboard joints. Attached to studs with flat -head self - drilling tapping screws with a min. head diam. of 0.292 in. at maximum 6 in. OC. in the perimeter and 12 in. OC. in the field. When used, fastener lengths for gypsum panels increased by min. 112 in. 4. Batts and Glankets* — (Required as indicated under Item 5) — Mineral wool batts, friction fitted between studs and runners. Min nom thickness as indicated under Item 5. See Batts and Blankets BKNV or BZJZ Categories for names of Classified companies. * ( ) 9 P Blankets* — (Optional) — Placed in stud cavities an lass fiber or mineral 4A. Rafts and II (p ) y g wool insulation bearing the UL Classification Marking as to Surface Burning Characteristics and /or Fire Resistance, See Batts and Blankets (IKNV or BZJZ) Categories for names of Classified companies. 5. Gypsum Board' — G yp sum panels with beveled square or tapered edges, a pp lied vertically or horizontally. Vertical joints centered over studs and staggered one stud cavity an opposite sides of studs. Vertical joints in adjacent layers (multilayer systems) staggered one stud cavity. Horizontal joints need not be backed by steel framing. Horizontal edge joints and horizontal butt joints on opposite sides of studs need not be sta gg ere d. Horizontal edge joints and horizontal butt joints in adjacent layers (multilayer systems) staggered a min of 12 in. The thickness and number of layers for the 1 hr, 2 hr, 3 hr and 4 hr ratings are as follows: Gypsum Board Protection on Each Side of Will Gypsum board Protection on Each Side ,oi'll all 0 5 6 7 Design No. U419 (CONT'D) May 01, 2012 Nonbearing Will Ratings ---1, 2, 3 or 4 Hr (See Items 4 B 5) CGC INC —112 in. thick Type C, IF-X2 or IPC -AR; WRC, 518 in. thick Type AR, C, IP -AR, IP -X1, IP -X2, IPC -AR, SCX, SHX, WRX or WRC; 314 in. thick Types IP -X3 or ULTRACODE UNITED STATES GYPSUM CO —112 in. thick Type C, IP -X2, IPC-AR or WRC; 518 in. thick Type SCX, SGX, SHX, WRX, IP -X1, AR, C, WRC, FRX -G, IP -AR, IP -X2, IPC -AR ; 314 in. thick Types I?-X3 or ULTRACODE USG MEXICO S A DE C V —112 in. thick Type C, I?-X2, IPC -AR or WRC; 511 in. thick Type AR, C, IP -AR, IP -X1, IP -X2, iPC -AR, SCX, SHX, WRX, WRC or; 314 in. thick Types IP -X3 or ULTRACODE When Item 71, Steel Framing Members *, is used, Nonbearing Wall Rating is limited to 1 Hr. Min. stud depth is 3 -1/2 in., min. thickness of insulation (Item 4) is 3 in., and two layers of gypsum board panels (112 in. or 511 in. thick) shall be attached to furring channels as described in Item 6. One layer of gypsum board panels (112 in. or 518 in. thick) attached to opposite side of stud without furring channels as described in Item 6. 5A. Gypsum Board* -- (As an alternate to Item 5) — 518 in. thick, 24 to 54 in. wide, applied horizontally as the outer layer to one side of the assembly. Secured as described in Item 6. CGC INC — Type SHX. UNITED STATES GYPSUM CO —Type FRX -G, SHX. USG MEXICO S A DE C V — Type SHX 58. Gypsum Board* — (Not Shown) - As an alternate to Item 5 when used as the base layer on one or both sides of wall when 518 in or Y44 in. thick products are specked. For direct attachment only to steel studs Item 26, (not to be used with Item 3) - Nom 511 in. or' /, in. may be used as alternate to all 518 in. or' /, in. shown in Item 5, Wallboard Protection on Each Side of Wall table. Nom 518 in. or 1/4 [n. thick lead backed gypsum panels with beveled, square or tapered edges, applied vertically. Vertical joints centered over studs and staggered min 1 stud cavity on opposite sides of studs. Gypsum board secured to 20 MSG steel studs Item 26 with 1 -114 in. long Type S -12 steel screws spaced I in. OC at perimeter and 12 in. OC in the field. To be used with Lead Batten Strips (see Item 11) or Lead Discs or Tabs (see Item 12) RAY -BAR ENGINEERING CORP —Type RB-LBG 5C. Gypsum Board* — (For Use With Item 2C) Rating Limited to 1 Hour. 518 in. thick, 48 in. wide, Gypsum panels with beveled, square or tapered edges, applied vertically or horizontally. (Vertical Application) - The gypsum board is to be installed on each side of the studs with 1 in. long Type S coated steel screws spaced I in. OC starting 4 in. from the edge of the board at the vertical edges and 12 in. OC starting 6 in. from the edge of the board at the center of each board. Gypsum boards are to be secured to the top and bottom track with screws spaced I in. OC starting 4 in. from the board edge. Fasteners shall not penetrate through both the stud and the track at the same time. Vertical joints are to be centered over studs and staggered one stud cavity on opposite sides of studs. (Horizontal Application) - The gypsum board is to be installed on each side of the studs with 1 in. long Type 5 coated steel screws spaced I in. OC starting 4 in. from the edge of the board at the vertical edges and 12 in. OC starting 6 in. from the edge of the board at the center of each board. Gypsum boards are to be secured to the top and bottom track with screws spaced 8 in. OC starting 4 in, from the board edge. Fasteners shall not penetrate through both the stud and the track at the same time. All horizontal joints are to be backed as outlined under section VI of Volume 1 in the Fire Resistive Directory. CGC INC — Type SCX. UNITED STATES GYPSUM CO — Type SCX, SGX. USG MEXICO S A DE C V— Type SCX 5D. Gypsum Board* — (As an alternate to Item 5) — 518 in. thick, 48 in. wide, applied vertically or horizontally. Secured as described in Item 6. For use with Items 1 and 2 only. UNITED STATES GYPSUM CO — Type USGX. 5E: Gypsum Board* — (Not Shown) - (As an alternate to Item 5 when used as the base layer on one or both sides of wall when 112 in. or 518 in thick products are specified, For direct attachment only to steel studs Item 28, not to be used with Item 3). Nominal 518 in. thick lead backed gypsum panels with beveled, square or tapered edges, applied vertically. Vertical joints centered over studs and staggered min 1 stud cavity on opposite sides of studs. Wallboard secured to studs with 1.114 in. long Type S -12 (or No. 6 by 1 -114 in. long bugle head tine driller) steel screws spaced 1 in. OC at perimeter and 12 in. OC in the field. NEW ENGLAND LEAD BURNING CO INC, DBA NELCO — Nelco 5F. Gypsum Board* — (As an alternate to Item 5) — For use with Items 1 G and 2F and limited to 1 Hour Rating only, Gypsum panels with beveled, square or tapered edges, applied vertically, and fastened to the steel studs with 1 in. long Type S screws spaced 8 in. OC along vertical and bottom edges and 12 in. OC in the field. Vertical joints centered over studs and staggered one stud cavity on opposite sides of studs. Steel stud depth shall be a minimum 3 -5/1 in. UNITED STATES GYPSUM CO -- 5/8 in. thick Type SCX, SGX. 5G. Gypsum Board* — (As an alternate to Item 5) — For use with Items 1G and 2F only, Gypsum panels with beveled, square or tapered edges, applied vertically or horizontally, as specified in the table below and fastened to the steel studs as described in Item 6. Vertical joints centered over studs and staggered one stud cavity on opposite sides of studs. Vertical joints in adjacent layers (multilayer systems) staggered one stud cavity. Horizontal joints need not be backed by steel framing. Horizontal edge joints and horizontal butt joints on opposite sides of studs need not be staggered. Horizontal edge joints and horizontal butt joints in adjacent layers (multilayer systems) staggered a min of 12 in. The thickness and number of layers for the 2 hr, 3 hr and 4 hr ratings are as follows: Gypsum Board Protection on Each Side of Will . I. ..Gypsum soars Protection on EA 1: ch Side +o11'''k all ••..yw.,•,r w�,- «.+,,.r,n.,- ...,rp.�++riK+,ry «wx::Wr+, vnwrwr ..,w^ ^rrr�wiiirfwnwwrwrwrrrhir mrw+-KK^ w�rcwm..,»wrc�w.m�.� .. ..41 N. �,.� ,{ ....,m .. .. [. .. . . . . . . . . I . . I r . . . . . . . . . . . . . . . . � . . . . . . I . I r r : : . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : . : . . . . . . . . . . , . . . . I . . . . . . . . CGC INC —112 in. thick Type C, IP -X2 or IPC -AR;, 518 in. thick Type AR, C, IF-AR, IP -X1, IPA2, IPC -AR, SCX, SHX, or; 314 in. thick Types IP -X3 or ULTRACODE UNITED STATES GYPSUM CO —112 in, thick Type C, IF-X2, IPC -AR or; 511 in. thick Type SCX, SGX, SHX, IP -X1, AR, C, , FRX -G, IF -AR, IF-X2, IPC -AR ; 314 in. thick Types IP -X3 or ULTRACODE USG MEXICO SA DE C V -112 in. thick Type C, IP -X2, IPC -AR or; 5/8 in. thick Type AR, C, IP -AR, IP -X1, IPA2, IPC -AR, SCX, SHX, or; 314 in. thick Types IPA3 or ULTRACODE 5H. Gypsum Board* — (Not Shown) - (As an alternate to Item 5 when used as the base layer on one or both sides of will when 518 or 3/4 in thick products are specified. For direct attachment only to steel studs Item 21, (not to be used with Item 3) - Nom 518 or 314 in. may be used as alternate to all 518 or 314 in. shown in Item 5, Wallboard Protection on Each Side of Wall table. Nom 5/8 or 314 in. thick lead backed gypsum panels with beveled, square or tapered edges, applied vertically. Vertical joints centered over 20 MSG steel studs and staggered min 1 stud cavity on opposite sides of studs. Wallboard secured to studs with 1 -1/4 in. long Type S -12 steel screws spaced 8 in. OC at perimeter and 12 in. OC in the field. Gypsum board secured to 20 MSG steel studs Item 2B with 1 -114 in. long Type S -12 steel screws spaced 8 in. OC at perimeter and 12 in. OC in the field. For Joint Compound see item 5. To be used with Lead Batten Strips (see Item 11A) or Lead Discs (see Item 12A). MAYCO INDUSTRIES INC —Type X -Ray Shielded Gypsum 51. Gypsum Board* — (As an alternate to Item 5) - Nom. 518 in. thick gypsum panels with beveled, square or tapered edges installed as described in Item 5. Steel stud minimum depth shall be as indicated in Item 5. CGC INC — Type ULX UNITED STATES GYPSUM CO —Type ULX USG MEXICO S A DE C V —Type ULX 5J. Gypsum Board* — (Not Shown) - (As an alternate to Item 5 when used as the base layer on one or both sides of wall when 112 in. or 518 in thick products are specified, For direct attachment only to steel studs Item 2R, not to be used with Item 3). Nom 518 in- thick lead backed gypsum panels with beveled, square or tapered edges, applied vertically. Vertical joints centered over studs and staggered min 1 stud cavity on opposite sides of studs. Wallboard secured to studs with 1 -114 in. long Type S -12 steel screws gypsum panel steel screws spaced 8 in. OC at perimeter and 12 in. OC in the field. Lead batten strips required behind vertical joints of lead backed gypsum wallbvard and optional at remaining stud locations. Lead batten strips, min 2 in. wide, max I it long with a max thickness of 0.14 in. placed on the face of studs and attached to the stud with construction adhesive and two 1 in. long Type S -12 pan head steel screws, one at the top of the strip and one at the bottom of the strip. Lead discs, nominal 3/8 in. diam by max 0.085 in. thick. Compression fitted or adhered over the screw heads. Lead batten strips and discs to have a purity of 99.9% meeting the Federal specification 00- L -201f, Grade "C ". RADIATION PROTECTION PRODUCTS INC —Type RPP -LBG 6. Fasteners — (Not shown) — For use with Items 2 and 2F - Type S or S -12 steel screws used to attach panels to studs (Item 2) or furring channels (Item 7). Single layer systems: l in, long for 112 and 518 in. thick panels or 1 -114 in. long for 314 in. thick panels, spaced 8 in. OC when panels are applied horizontally, or I in. OC along vertical and bottom edges and 12 in. OC in the field when panels are applied vertically. Two layer systems: First layer -1 in. long for 112 and 518 in, thick panels or 1 -114 in. long for 314 in. thick panels, spaced 16 in. OC. Second layer -1 -511 in. long for 112 in., 511 in. thick panels or 2 -114 in. long for 314 in. thick panels, spaced 16 in. OC with screws offset I in. from first Iayer.Three -layer systems: First layer -1 in. long for 112 in., 518 in, thick panels, spaced 24 in. OC. Second layer -1 -5/8 in. long for 112 in., 518 in. thick panels, spaced 24 in. OC. Third layer- 2 -1/4 in. long for 1/2 in., 518 in. thick panels or 2 -518 in. long for 518 in. thick panels, spaced 12 in. OC. Screws offset min 6 in. from layer below" Four -layer systems: First layer -1 in. long for 112 in., 5/1 in, thick panels, spaced 24 in, OC. Second layer -1 -518 in. long for 112 in., 518 in. thick panels, spaced 24 in. OC. Third layer- 2 -114 in. long for 112 in. thick panels or 2 -5/1 in, long for 5/8 in. thick panels, spaced 24 in. OC. Fourth layer- 2 -518 in. long for 1/2 in. thick panels or 3 in. long for 518 in. thick panels, spaced 12 in. OC. Screws offset min 6 in. from layer below. 6A. Fasteners — (Not shown) —For use with Item 2A - Type S or 5 -12 steel screws used to attach panels to studs (Rem 2A). Single layer systems :1 in. long for 112 and 51 in. thick panels or 1 -114 in. long for 314 in. thick panels, spaced 8 -112 in. OC with additional screws 1 in. and 2 -1/2 in. from edges of the board when panels are horizontally. or I in. OC along vertical and bottom edges and 12 in. OC in the field when panels are applied vertically. Two layer systems applied vertically: First layer -1 in. long for 112 and 518 in. thick panels or 1 -1/4 in. long for 314 in. thick panels, spaced 16 in. OC. Second layer -1 -511 in. long for 1/2 in., 511 in. thick panels or 2 -1/4 in. Ion for 314 in. thick panels, spaced 16 in. OC with screws offset 8 in. from first layer. Two layer systems applied horizontally: First layer- in. long for 112 and 5/2 in. thick panels or 1 -1/4 in. Ion for 314 in. thick panels, spaced 16 in. OC starting 8 in. from each edge of the board with an p p p P , 9 Y Y Y P Y Y 9 p g P Pa g 9 additional in na screw placed 1 114 .from each edge of the board. Second layer -1 -518 in. long for 112 in., 518 in. thick panels or 2 -114 in. long far 314 in. thick panels, spaced 16 in. OC starting 8 in. from each edge of the board with an additional screw placed 1 -114 in. from each edge of the board with screws offset 8 in. from first layer. Three -layer systems: First layer -1 in. long for 112 in., 519 in. thick panels, spaced 24 in. OC. Second Dyer -1 -5/1 in. long for 112 in., 511 in. thick panels, spaced 24 in. 00. Third layer- 2 -114 in, long for 112 in., 518 in. thick panels or 2 -518 in. long for 511 in. thick panels, spaced 12 in. OC. Screws offset min 6 in, from layer below. For all layers, an additional screw shall be placed 1 -114 in. from each edge of the board. Four -layer systems: First layer -1 in. long for 112 in., 518 in. thick panels, spaced 24 in. OC. Second layer -1 -518 in. long for 112 in., 518 in. thick panels, spaced 24 in. OC. Third layer- 2 -114 in. long for 1/2 in. thick panels or 2 -5/1 in. long for 518 in. thick panels, spaced 24 in. OC. Fourth layer- 2 -518 in. long for 112 in. thick panels or 3 in. long for 511 in. thick panels, spaced 12 in. OC. Screws offset min 6 in. from layer below. For all layers, an additional screw shall be placed 1 -114 in. from each edge of the board. 7. Furring hannels — (Optional, not shown for single or double layer systems) — Resilient furring channels fabricated from min 25 MSG corrosion -protected steels aced vertical) a f 4 in. OC. Flange ortion attached to each intersecting stud with 112 in. Ion Type S -12 steel screws. Not for use with Item 5A and 5E. g (p 9 Y Y ) 9 P P Y max o 2 P h 9 9 YP 7A. Framing Members* — (Not Shown) — (Optional on one or both sides, not shown, for single or double layer systems) — As an alternate to Item 7, furring channels and Steel Framing Members as described below: a. Furring Channels — Formed of No. 25 MSG gale steel. 2 -3/8 in, wide by 7/8 in. deep, spaced max. 24 in. OC perpendicular to studs. Channels secured to studs as described in Item b. Gypsum board attached to furring channels as described in Item 6. Not for use with Item 5A and 5E. b. Steel Framing Members* — Used to attach furring channels (Item 7Aa) to studs (Item 2). Clips spaced max. 48 in. OC. RSIC -1 clips secured to studs with No. I x 1 -112 in, minimum self - drilling, 5 -12 steel screw through the center grommet. RSIC -V clips secured to studs with No. I x 9116 in, minimum self - drilling, S -12 steel screw through the center hole. Furring channels are friction fitted into clips. PAC INTERNATIONAL INC — Types RSIC -1, RSIC -V. 75. Framing Members* — (Optional, Not Shown) - As an alternate to item 7, for single or double layer systems, furring channels and Steel Framing Members on only one side of studs as described below: a. Furring Channels — Formed of No. 25 MSG gals steel, spaced 24 in. OC perpendicular to studs. Channels secured to studs as described in Item b. Batts and Blankets placed in stud cavity as described in Item 5. Two layers of gypsum board attached to furring channels as described in Item 5. Not for use with Item 5A and 5E. b. Steel Framing Members* — Used to attach furring channels (Item 76a) to one side of studs (Item 2) only. Clips spaced 48 in. OC., and secured to studs with two No. 8 x 2 -112 in, coarse drywall screws, one through the hole at each end of the clip. Fung channels are friction fitted into clips. KINETICS NOISE CONTROL INC — Type Isomax 7C. Framing Members* — Optional - Not Shown - Used as an alternate method to attach resilient channels (Item 7). Clips attached at each intersection of the resilient channel and the steel studs (Item 2). Resilient channels are friction fitted into clips, and then clips are secured to the steel stud with min,1 in. long Type S- 12 steel screws through the center hole of the clip and the resilient channel flange. KEENE BUILDING PRODUCTS CO INC —Type RC Assurance, 7D. Framing Members* — (Not Shown) — (Optional on one or both sides, not shown, for single or double layer systems) — As an altemate to Item 7, furring channels and Steel Framing Members as described below: a. Furring Channels — Formed of No. 25 MSG gale steel. 2 -3/8 in. wide by 718 in. deep, spaced max. 24 in. OC perpendicular to studs. Channels secured to studs as described in Item b. Gypsum board attached to furring channels as described in Item 6. Not for use with Item 5A and 5E. b. Steel Framing Members* — Used to attach furring channels (Item 7Aa) to studs (Item 2). Clips spaced max. 48 in. 00. GEN] ECLIPS secured to studs with No. 8 x 1 -112 in. minimum self- drilling, S -12 steel screw through the center grommet. Furring channels are friction fitted into clips. PLITEQ INC —Type GENIECLIP 1. Joint Tape and Compound — Vinyl or casein, dry or premixed joint compound applied in two coats to joints and screw heads of outer layers. Paper tape, nom 2 in. wide, embedded in first layer of compound over all joints of outer layer panels. Paper tape and joint compound may be omitted when gypsum panels are supplied with a square edge. 9. Siding, Brick or Stucco — (Optional, not shown) — Aluminum, vinyl or steel siding, brick veneer or stucco, meeting the requirements of local code agencies, installed over gypsum panels. Brick veneer attached to studs with corrugated metal wall ties attached to each stud with steel screws, not more than each sixth course of brick. 10. Caulking and Sealants* — (Optional, not shown) — A bead of acoustical sealant applied around the partition perimeter for sound control. UNITED STATES GYPSUM CO — Type AS 11. Lead Batten Strips — (Not Shown, For Use With Item 59) - Lead batten strips, min 1 -1/2 in. wide, max 10 tt long with a max thickness of 0125 in. Strips placed on the interior face of studs and attached from the exterior face of the stud with two 1 in. long Type S-12 pan head steel screws, one at the top of the strip and one at the bottom of the strip. Lead batten strips to have a purity of 99.9% meeting the Federal specification QQ- L -201f, Grade "C ". Lead batten strips required behind vertical joints of lead backed gypsum wallboard (Item 56) and optional at remaining stud locations. Required behind vertical joints, 11A. lead Batten Strips — (Not Shown, For Use With Item 5H) Lead batten strips, 2 in. wide, max 10 It long with a max thickness of 0.140 in. Strips placed on the face of studs and attached to the stud with two min.1 in. long min. Type 6-8 pan head steel screws, one at the top of the strip and one at the bottom of the strip or with one min.1 in. long min. Type S -8 pan head steel screw at the top of the strip. Lead batten strips to have a purity of 69.9' meeting the Federal specification QQ- L -201f, Grades "A, B, C or D ". Lead batten strips required behind vertical joints of lead backed gypsum wallboard and optional at remaining stud locations. 12. Lead Discs or Tabs — (Not Shown, For Use With Item 5B) - Used in lieu of or in addition to the lead batten strips (Item 11) or optional at other locations - Max 314 in. diam by max 0.125 in. thick lead discs compression fitted or adhered over steel screw heads or max 112 in. by 1 -114 in. by max 0.125 in. thick lead tabs placed on gypsum boards (Item 51) undemeath screw locations prior to the installation of the screws. Lead discs or tabs to have a purity of 99.9% meeting the Federal specification QQ- L -201f, Grade "C ". 12A. Lead Discs — (Not Shown, for use with Item 5H) Max 5116 in. diam by max 0.140 in. thick lead discs compression felted or adhered over steel screw heads. Lead discs to have a purity of 99.9% meeting the Federal Specification QQ- L -201f, Grades "A, R, C or D ". 13. Lead Batten Strips — (Not Shown, For Use With Item 5E) Lead batten strips, 2 in. wide, Max 10 ft long with a max thickness of 0.142 in. Strips placed on the face of studs and attached to the stud with two min.1 in. long min. Type S-8 pan head steel screws, one at the top of the strip and one at the bottom of the strip or with one min.1 in. long min. Type S -8 pan head steel screw at the top of the strip. Lead batten strips to have a purity of 99.9% meeting the Federal specification QQ- L -201f, Grade "C ". Lead batten strips required behind vertical joints of lead backed gypsum wallboard (Item 5E) and optional at remaining stud locations. 14. Lead Tabs — (Not Shown, For Use With Item 5E) 2 in. wide, 5 in. long with a max thickness of 0.142 in. Tabs friction -fit around front face of stud, the stud folded back flange, and the back face of the stud. Tabs required at each location where a screw (that secures the gypsum boards, item 5E) will penetrate the steel stud. Lead tabs to have a purity of S9.9% meeting the Federal specification QQ- L -201f, Grade "C ". Lead tabs may be held in place with standard adhesive tape if necessary. *Bearing the UL Classification Mark • • i ••• • • u • • • . . •• • • • • • ♦ • •• •• • ♦ • • ♦ Y • V Y ♦ Y • ♦ ♦ • • • • • Y • ♦ i •Y•• • • • u; .try :ARR A Y !!!",-, iiii!!� �� r.. ,: 11, I r: V11 •♦•• •♦••r "4 • •;;., `ur.altbc�re facilities solutions 0000 6800 Broken Sound Boulev2rd NW Suite 125 Boca Raton, FL 33487 t: 561,995.1 700 f: 561.995.1701 www.arroyhfs.com firm license number AA26000880 SEAL: Bid and Permit Set 07 --18-12 1 AHCA Stage III �, , w r 1.� NO. I DESCRIPTION , N / REVISIONS /ISSUES %.; • 4 1. '. 4, � ' �� ,C� � + ,�, M ,� 'pt," 1 ;1 .., 1 �7 / , • , :; ,q l 1 MARK D. TAUDIEN * -) >• V, �' AR0011l21 , CONSULTANTS: 14 1 ' N Smith Seckman €t Reid, Inc. `, 600 West Hillsboro Blvd, Suite 300 Deerfield Beach FL 33441 Phone: 954.421 1260 Fax: 954.421.1466 OWNER: BAPTIST HEALTH SOUTH FLORIDA HOSPITAL: SOUTH MIAMI HOSPITAL PROJECT: INTERIOR RENOVATIONS FOR CENTRAL MONITORING ADDRESS: 6200 Southwest 73rd Street South Miami, FL 33143 AHCA: CLIENT CODE /FILE NUMBER: 23/100154 PROJECT ID /SUBMISSION NUMBER: 187 -1 2 Bid and Permit Set 07 --18-12 1 AHCA Stage III 07 -03 -12 NO. I DESCRIPTION I DATE REVISIONS /ISSUES SHEET TITLE: UL ASSEMBLIES DRAWN: EAS CHECKED: MDT CON /REF No. QQ000 PROJECT No. 3606 DATE: 07 -03 -12 SCALE: 1 112" = 1' -0" A -622A This d,%r rr r' is % cogtTight pro, ecPA instrument of senke, p'rvPp -rt f of .dRRi y anal licemsed for _ ir, tt tl r P-_ ' Only. R .,.,i_ctioe r Lse of '('s C - .,- ,ler,'r Mttlout wi<<_c permission or ARRA'T i, rL -y,01 •flC will b- r- C,'..ut�•f rc.1 ,ha cw- @COPYRIGHT - 2012 ARRAY HFS