12-965-010544 760A 544 811A TTE -1 ° 55/95 DEG F 0 /10 DRRMT DRRMH PCT RH 0 0 DETAIL MR DETAIL MF SENSORS LOCATED IN DATA ROOM DATA ROOM EXHAUST FANS The space served by the duct exhaust fan is controlled in Occupied and Unoccupied modes as follows: Occupied The DDC system turns on the exhaust fan when the respective AHU is running. Unoccupied The exhaust fan is off when the respective AHU has shut down. The DDC system uses a differential pressure switch or current sensor to monitor the exhaust fan status and shall provide and alarm if the fan fails during the occupied mode. Interlock all associated Fire /Smoke dampers with the exhaust fan. Dampers shall open when fan is running and close when fan is shut down manually, through the interlock or if the fan fails. TO CLOSEST PANEL 24 VAC CONDENSATE OVERFLOW SWITCH SWITCH PROVIDED BY I OTHERS DATA ROOM POINTS ONE CONDESATE SWITCH PER LIEBERT UNIT (PCU -1) TO UNIT SAFETY CIRCUIT TO CLOSEST PANEL DROVRF 0 DETAIL MC A temperature and humidity sensor will monitor room temp and humidity. If the humidity rises above a setpoint (60%), or drops below a setpoint (30%) (H1 /Low), an alarm will be generated. The condensate overflow switch will be monitored for each Liebert. The point will alarm if the overflow switch changes state signifying an overflow issue. C 9 C 1N 5. hi O E 0 c a� IN INSTALLATION NOTES: O1 RELAY LOCATED AT FAN STARTER. 2O TRANSFORMER LOCATED AT CONTROLLER. O3 INTERLOCK EXHAUST FAN WITH RESPECTIVE AHU STARTER X HWS L!!-jT HwR REHEAT COIL CONTROL SEQUENCE OF OPERATIONS REHEAT COILS: The space thermostat shall modulate the pump speed to maintain its setting Direct Acting (call for heat increases pump speed.) Pump to be set to "Equal Percentage" flow characteristic. Thermmostat to be 0 -10 vdc by Siemens. Wiring to pump from thermostat to be by Siemens. NOTE: EXISTING REHEAT COIL CONTROL DIAGRAM FOR REFERENCE ONLY. RELOCATE THERMOSTAT AS SHOWN PLANS. SRSmith Seckman Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- inc.com Firm Certification - EB- 0000857 Michael A. Steward PE - 65701 John E. Moulder PE - 33200 SSR JOB # 1232016.0 W M Drawn: Cl) o Revised: d' YI�Ohf��O V 06/21/12 � U p W =.00 ,H Q = L w IU CO _'ON'2� � oC V Q � z a X HWS L!!-jT HwR REHEAT COIL CONTROL SEQUENCE OF OPERATIONS REHEAT COILS: The space thermostat shall modulate the pump speed to maintain its setting Direct Acting (call for heat increases pump speed.) Pump to be set to "Equal Percentage" flow characteristic. Thermmostat to be 0 -10 vdc by Siemens. Wiring to pump from thermostat to be by Siemens. NOTE: EXISTING REHEAT COIL CONTROL DIAGRAM FOR REFERENCE ONLY. RELOCATE THERMOSTAT AS SHOWN PLANS. SRSmith Seckman Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- inc.com Firm Certification - EB- 0000857 Michael A. Steward PE - 65701 John E. Moulder PE - 33200 SSR JOB # 1232016.0 C) o o� ti M Drawn: Cl) o Revised: d' YI�Ohf��O V 06/21/12 M 05/08/13 � O N A (~D 'tt [-- O EXHAUST FAN WIRING DIAGRAM T d) c, (9 2) N L w IU CO _'ON'2� � M NOTE : ` Oco O C O O O , N REFER TO FAN INTERLOCK SCHEDULE O 0 /1 C O a (p . —' 6 _ 5- a E v .; co = .: m U- U-- 5OacnH = X HWS L!!-jT HwR REHEAT COIL CONTROL SEQUENCE OF OPERATIONS REHEAT COILS: The space thermostat shall modulate the pump speed to maintain its setting Direct Acting (call for heat increases pump speed.) Pump to be set to "Equal Percentage" flow characteristic. Thermmostat to be 0 -10 vdc by Siemens. Wiring to pump from thermostat to be by Siemens. NOTE: EXISTING REHEAT COIL CONTROL DIAGRAM FOR REFERENCE ONLY. RELOCATE THERMOSTAT AS SHOWN PLANS. SRSmith Seckman Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- inc.com Firm Certification - EB- 0000857 Michael A. Steward PE - 65701 John E. Moulder PE - 33200 SSR JOB # 1232016.0 Comm. No: 12007.00 Date: M Drawn: Revised: d' - Q 06/21/12 M 05/08/13 � M O L w LL. a_ Z Z W I— V = 02 OZ, C0 W L Q co W I— a o � t` M CD W 'r O C0 Z Q N O/� M W W �O V Comm. No: 12007.00 Date: 05/22/12 Drawn: Revised: QADDENDUM 2 06/21/12 A 05/08/13 THE I t Ly WIT No. 33200 ' T 4v AN1�L E����• c 0 AR`IIAlk JOLLY, INC M5.1 0