12-965-047LIMIT OF DEMOLITION DISCONNECT AND REMOVE ALL EXISTING ELECTRICAL FIXTURES, POWER AND SYSTEMS DEVICES, ETC. AND CONNECTIONS TO ALL EXISTING ELECTRICAL EQUIPMENT IN THESE AREAS UNLESS OTHERWISE NOTED HERE OR ON OTHER DRAWINGS. REFER TO ELECTRICAL SPECIFICATION SECTION 16010 FOR OTHER REQUIREMENTS. ALL EXISTING RACEWAYS PASSING THROUGH THIS AREA FEEDING OTHER AREAS SHALL REMAIN INTACT AND OPERATIONAL. PROVIDE SUPPORTS FOR ALL EXISTING RACEWAYS IF THEY ARE NOT PROPERLY SUPPORTED. AND OPERATIONAL, ALL OTHER RACEWAYS SHALL BE REMOVED. MIAI TENAN 1 28 r a I OFFICE " 116 ) TOILET 1 11 == = == WAITING I ' 1 11 — FIRST FLOOR PLAN — DEMOLITION — ELECTRICAL 4. y GENERAL NOTES: A. COORDINATE EXTENT OF DEMOLITION WITH ARCHITECTURAL AND ALL TRADES PRIOR TO START OF CONSTRUCTION. KEYED NOTES: `-' NEW TLOCATIONLAS SHOWN ON REMOVED AND REPLACED IIIT EXISTING NEW NOT WITHIN SCOPE OF WORK AREA TO EXISTING PANEL INL2 AS INDICATED PRIOR TO DEMOLITION OF EXISTING PANEL INL4. REFER TO KEYED NOTE 2. ( RE- CIRCUIT EXISTING RECEPTACLES CURRENTLY FED FROM PANEL INL4 TO EXISTING PANEL INL2 TO FACILITATE THE DEMOLITION OF PANEL INL4. PROVIDE ALL NEW ENGRAVED DEVICE PLATES WITH NEW CIRCUIT INFO FOR EACH DEVICE AFFECTED. RE -PULL NEW WIRING AS NECESSARY TO ENSURE NEW CIRCUITS HAVE DEDICATED NEUTRALS. COORDINATE DOWNTIME WITH FACILITY AT LEAST 2 WEEKS PRIOR TO WORK. 3 RE- CIRCUIT EXISTING LIGHTING CURRENTLY FED FROM PANEL INL4 TO EXISTING PANEL INL2 TO FACILITATE THE DEMOLITION OF PANEL INL4. PROVIDE ALL NEW ENGRAVED SWITCH PLATES WITH NEW CIRCUIT INFO FOR EACH LIGHT AFFECTED. RE -PULL NEW WIRING AS NECESSARY TO ENSURE NEW CIRCUIT HAS DEDICATED NEUTRALS. COORDINATE DOWNTIME WITH FACILITY AT LEAST 2 WEEKS PRIOR TO WORK. ORAGE , EXISTING PANELS TO REMAIN: PANEL 1EQL2 PANEL 1 LSL1 PANEL 1 NL2 PANEL 1 CL1 OFFICE 156 v� OFFICE 16 a N, CORRIDOR =6 RECREATION THERAPY y� ( 16c� F 0 dQ c9- CV ` 0 u Azy _ r \e ' d 05/22/12 Drawn: Noe 701 CV ` 0 u Azy _ r PER DRAWING BEFORE • Dade - Department. Approved for Buildirhgr Permit only! r 4e_1 Smith 14MSeGICi11Sn Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- inc.com Firm Certification - EB -0000857 Michael A. Steward PE - 65701 E1.1 John E. Moulder PE - 33200 SSR JOB # 1232016.0 Comm. No: 12007.00 Date: 05/22/12 Drawn: Noe 701 Revised: r T� •, FL RZ'-\�i © 2�YY, `' `.(pLLY, � INC GENERAL DEMOLITION NOTES = - I T SHALL BE THE RESPONSI BI LI TY OF THE CONTRACTOR TO REMOVE EXI STI NG EQ REQUI RED TO ACCOMPLI SH THE NEW WORK AS SHOWN OR REASONABLY I MPLI ED. T F-. CONTRACTOR SHALL REFER TO THE NEW ARCHITECTURAL, PLUMBING, FIRE PROTEC I 0 MECHANICAL AND ELECTRICAL WORK SHOWN ON THE OTHER DRAWINGS OF THIS SET TO DETERMINE THE EXTENT OF DEMOLITION REQUIRED. MMMMMN WHEN REMOVING ELECTRICAL EQUIPMENT AND SYSTEMS, ALL PRECAUTIONS SHALL EE ('1 TO PREVENT STRUCTURAL DAMAGE TO THE BUILDING. THE CONTRACTOR SHALL C00 DI �✓✓ INSTALLATION OF ANY STRUCTURAL SUPPORTS REQUIRED, TEMPORARY OR PERMANE T. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL DEMOLITION NO W CONSTRUCTION DEBRIS GENERATED FROM WORK ON ALL FLOORS. TAKING CARE TO PR EXCESSIVE LOADING OF FLOOR ASSEMBLIES. THE CONTRACTOR SHALL MAINTAIN CONTINUITY OF CIRCUITS WHERE EXISTING EQ I P TO BE REMOVED AND DOWN STREAM DEVICES MAY BE EFFECTED. THE CONTRACTOR SHALL COORDINATE ALL POWER INTERRUPTIONS WITH OWNER. SE E SPECIFICATIONS. WHEN EXISTING ELEMENTS OF ELECTRICAL EQUIPMENT AND SYSTEMS ARE REMOVED, A REMAINING OPENINGS IN THE SLAB AND WALLS SHALL BE FILLED IN BY THE CON SHALL BE MAINTAINED. RA THE FIRE RATING OF THE EXISTING STRUCTURE REMOVE ALL MISCELLANEOUS FIXTURES AND EQUIPMENT RETAINING ITEMS TO BE IDE FOR SALVAGE AND STORAGE AT THE DIRECTION OF THE OWNER. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION eNO CONSTRUCTI ON TO MAI NTAI N THE I NTEGRI TY AND OPERATI ON OF EXI STI NG LI FE AF EMERGENCY EGRESS EQUIPMENT. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITION ND CONSTRUCTION TO MAINTAIN ACCESS TO ALL MEANS OF EGRESS CORRIDORS, DOOR AY STAIRS. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS DURING DEMOLITIONe NO CONSTRUCTION TO PERMIT EFFECTED AREAS TO CONTINUE TO FUNCTION TO THE GF EA o r EXTENT POSSIBLE. THIS EFFORT SHALL INCLUDE SCHEDULED COORDINATION WIT 0 m o ELECTRICAL SHUTDOWNS. o :ram E THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL FLUORESCENT AN 3 N N TYPE LAMPS AND PROPER DI SPOSAL OF SAI D LAMPS AND SHALL PROVI DE VERI FI CAI �, ti r �- ti o OF LAMP DISPOSAL TO THE OWNER UPON REQUEST. m d, rn 4 ` °'N v REMOVE ALL LIGHTING FIXTURES, RECEPTACLES AND DEVICES IN THE AREA OFD M m E ? 'r o - t- .- AND PULL ALL CIRCUITS BACK TO NEXT ACTIVE DEVICE OR SOURCE OF POWER. m o -0 :? m o = ALL CONDUIT, JUNCTION BOXES AND WIRING DEVICES THAT ARE NOT INTENDED T U ° � a RE -USED MUST BE DEMOLI SHED BACK TO SOURCE. U. u.. 0 a U) PROVIDE PANEL SCHEDULES, TO THE ENGINEER INDICATING THE CIRCUITS MADE P DEMOLI TI ON AND THE EXI STI NG CI RCUI TS THAT REMAI N ACTI VE. I T SHALL BE THE RESPONSI BI LI TY OF THE CONSTRUCTI ON MANAGER ( CM) , GENERAL (GC) , AND THE SUB - CONTRACTORS (SC) TO STUDY ALL THE DRAWINGS AND DETAIL.S THE INSTALLATION OF ALL NEW WORK CAN BE FULLY COORDINATED. THE CM, GC A co VISIT THE SITE, INCLUDING DOING AN ABOVE CEILING INSPECTION, DURING BI DI q' HIM /HER SELF THAT ALL PROVISIONS HAVE BEEN MADE FOR ALL ASPECTS OF THISr IF DISCREPANCIES EXIST BETWEEN DRAWINGS AND /OR SITE CONDITIONS, THE CO NT Q NOTIFY THE ENGINEER /OWNER IN WRITING PRIOR TO BID DUE DATE. FAILURE TO D ELI MI NATE THE CONTRACTOR FROM BEI NG ABLE TO SEEK ADDI TI ONAL COMPENSATI I IN Q A DIFFICULTY OF DIFFERENCE FROM CONDITIONS INFERRED OR INDICATED ON THEJ DRAWINGS ARE DIAGRAMMATIC AND DO NOT INDICATE ALL DEVICES TO BE DEMOLI SHE CONTRACTOR SHALL VISIT JOB SITE PRIOR TO BID TO FIELD CONFIRM ALL REQU R .. J W U. = W Cl) 0 OZ _ F- W �z � _ W U J a: 0 Q 0 cn W ~ � � Q � � I— W U U) = �: R: F_ 0) F_ 0 Z Q O N m(j) co0 PER DRAWING BEFORE • Dade - Department. Approved for Buildirhgr Permit only! r 4e_1 Smith 14MSeGICi11Sn Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- inc.com Firm Certification - EB -0000857 Michael A. Steward PE - 65701 E1.1 John E. Moulder PE - 33200 SSR JOB # 1232016.0 Comm. No: 12007.00 Date: 05/22/12 Drawn: Noe 701 Revised: W THE 'eo TPE i i UM4v- Noe 701 T� •, FL RZ'-\�i © 2�YY, `' `.(pLLY, � INC