PLUMBING NEW CONSTRUCTION NOTES
1. PLUMBING INSTALLATION OF ALL FIXTURES, EQUIPMENT, AND PIPING
SHOWN ON THESE DRAWINGS SHALL BE INSTALLED IN ACCORDANCE
WITH ALL APPLICABLE STATE, LOCAL AND HEALTH CODES
REQUIREMENTS.
2. CONTRACTOR SHALL FIELD VERIFY EXISTING INVERT ELEVATIONS, SIZES AND
LOCATIONS OF EXISTING PLUMBING PRIOR TO BIDDING. IF DISCREPENCIES ARE
FOUND, THEY ARE TO NOTIFY ENGINEER.
3. ALL PLUMBING FIXTURES TO COMPLY WITH TABLE 604.3 OF THE FLORIDA
BUILDING CODE - 2010.
4. CONTRACTOR SHALL COORDINATE KITCHEN EQUIPMENT CONNECTIONS & MOUNTING
HEIGHTS WITH KITCHEN EQUIPMENT, EQUIPMENT AND ARCHITECTURAL DRAWINGS
AND SUPPLIER. INSTALL EQUIPMENT AND MAKE FINAL CONNECTIONS FURNISHING
CUTOFF VALVES, P- TRAPS, FITTINGS, P.R.V.'S, AND PIPING AS REQUIRED.
CONTRACTOR SHALL OBTAIN A SET OF THE KITCHEN EQUIPMENT DRAWINGS PRIOR
TO BIDDING IN ORDER TO DETERMINE ALL REQUIRED CONNECTIONS.
5. CONTRACTOR SHALL PROVIDE TRAP PRIMERS ON ALL FLOOR DRAINS, FLOOR SINKS
AND SHOWER DRAINS AND AS REQUIRED BY STATE AND LOCAL CODES.
6, PROVIDE 12 "X12" ACCESS PANELS FOR ALL VALVES LOCATED ABOVE HARD
CEILINGS. INSTALL VALVES SO AS TO BE WITHIN REACH OF ACCESS DOOR.
7. CONTRACTOR SHALL PROVIDE ROUGH -INS AND MAKE FINAL CONNECTIONS
FOR EACH PIECE OF EQUIPMENT REQUIRING PLUMBING CONNECTION,
INCLUDING TAILPIECES, TRAPS, LINE STRAINERS, STOP VALVES, GAUGES,
VACUUM BREAKERS, REDUCING VALVES, SPECIAL FITTINGS, THERMOMETERS,
INSULATION, AND ALL NECESSARY DEVICES FOR A COMPLETE AND OPERATIVE
SYSTEM. COORDINATE EXACT REQUIRED PLUMBING ROUGH -INS WITH VENDOR
SUPPLIER DRAWINGS.
8. THE CONTRACTOR SHALL INSTALL PLUMBING PIPING IN LOCATIONS INDICATED
ON THE CONTRACT DOCUMENTS. THE ONLY DEVIATION FROM THIS WOULD BE
IF ADDITIONAL OFFSETS ARE REQUIRED TO COORDINATE WITH OTHER TRADES.
IF THE THE CONTRACTOR DESIRES TO CHANGE THE PLUMBING ROUTING FOR
ANY OTHER REASON, HE SHALL COMPENSATE THE ENGINEER AT A RATE OF
DPE x 2.75 TO REVISE THE PLUMBING DRAWINGS, RISER DIAGRAMS AND FOR
THE TIME INVOLVED IN REISSUING DRAWINGS TO THE AUTHORITY HAVING
JURISDICTION. CONTRACTOR SHALL CONTACT ENGINEER FOR ESTIMATED TIME
REQUIRED AND SCHEDULE FOR PERFORMING WORK.
9. EXISTING UTILITIES, WHICH ARE NOT SHOWN, THAT ARE DISCOVERED
DURING EXCAVATION SHALL BE BROUGHT TO THE ATTENTION OF THE
OWNER'S REPRESENTATIVE BY THE CONTRACTOR FOR PROPER CO-
ORDINATION. CONTRACTOR SHALL REMOVE, REWORK AND /OR REROUTE
THE EXISTING UTILITIES AS DIRECTED BY THE OWNER'S REPRESENTATIVE.
10. ALL MATERIALS, EQUIPMENT, AND APPARATUS SHALL BE NEW, EXCEPT THAT
CALLED FOR AS BEING RE -USED OR FURNISHED BY OTHERS.
11. SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS IN ACCORDANCE
WITH U.L. FIRE RESISTANCE INDEX FOR THROUGH PENETRATION FIRE STOP
SYSTEMS. COORDINATE REQUIREMENTS WITH ARCHITECTURAL PLANS AND
SPECIFICATIONS.
12. CONTRACTOR SHALL FURNISH AND INSTALL SHOCK ABSORBERS ON FLUSH
VALVE FIXTURES AND ALL LINES SERVING QUICK CLOSING VALVES AND AS
INDICATED ON PLUMBING PLANS AND RECOMMENDED BY THE MANUFACTURER.
13. CLEANOUT COVERS SHALL NOT BE INSTALLED ON THE CORRIDOR SIDE OF
ANY WALL. IF DISCREPANCIES ARE FOUND ON PLANS CONTRACTOR SHALL
NOTIFY PLUMBING ENGINEER PRIOR TO INSTALLATION.
14. PIPING SHALL NOT BE RUN OVER ANY ELECTRICAL EQUIPMENT, PANELS AND
PHONE PANELS.
15, SEE ARCHITECTURAL DRAWINGS FOR FIXTURE LOCATIONS AND MOUNTING HEIGHTS.
16. ALL EXPOSED PIPE AND FITTINGS IN FINISHED AREAS SHALL BE CHROME PLATED.
17_ THE PLUMBING CONTRACTOR SHALL KEEP A SET OF MARKED UP DRAWINGS
AS THE JOB PROGRESSES. NO MAJOR CHANGE SHALL BE MADE TO PLUMBING
DESIGN ENGINEERING UNLESS IT HAS BEEN COORDINATED, DRAWN AND SUBMITTED
FOR APPROVAL.
18. MOUNT INTERIOR HOSE BIBBS AT 9" ABOVE FINISHED FLOOR UNLESS OTHERWISE
NOTED.
19. CONTRACTOR SHALL USE TEFLON TAPE AT THREADED FITTINGS EXPOSED OR ABOVE
CEILINGS, CONNECTIONS TO PRY'S AND BFP'S. PIPE DOPE IS ACCEPTABLE ONLY IN
THEADED DOMESTIC WATER PIPING WITHIN WALLS.
20, CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGES TO EXISTING PIPING
AND FIXTURES DUE TO NEW CONSTRUCTION AND SHALL RESTORE EXISTING
WORK DISTURBED TO IT'S ORIGINAL CONDITION AT NO COST TO THE OWNER.
21. CONTRACTOR SHALL COORDINATE WITH ALL DISCIPLINES INVOLVED SO AS
TO AVOID ANY PIPE ROUTING PROBLEMS.
22. PROVIDE OFFSETS AND FITTINGS AS REQUIRED.
23. ALL VENTS SHALL BE A MINIMUM OF 25' -0" AWAY FROM A/C INTAKES, AND
OPERABLE WINDOWS.
24, CONTRACTOR SHALL PROVIDE ALL LOW VOLTAGE WIRING AND CONDUIT FOR
SEWAGE LIFT STATION CONTROL SYSTEM, AND SHALL COORDINATE WITH DIVISION 16.
CONTRACTOR SHALL HOLD A LOW VOLTAGE WIRING LICENSE.
25, CONTRACTOR SHALL TEST WATER FROM DOMESTIC COLD AND HOT WATER SYSTEMS
WHICH WILL BE MODIFIED BY THE RENOVATION PRIOR TO COMMENCING
MODIFICATIONS AND AFTER MODIFICATIONS ARE COMPLETED FOR CONTAMINANTS.
PROVIDE COPY OF INITIAL TEST REPORT UPON COMPLETION. PROVIDE COPY OF FINAL
TEST REPORT ONE WEEK PRIOR TO THE FINAL INSPECTION.
26. WHEN BEAM SLEEVE PENETRATIONS ARE NECESSARY, NOTIFY AND COORDINATE
PENETRATIONS WITH ALL TRADES, THE ARCHITECT AND STRUCTURAL ENGINEER
PRIOR TO PENETRATING ANY BEAMS.
27, COORDINATE INSTALLATION OF PLUMBING SYSTEMS WITH ALL CASEWORK.
CONTRACTOR SHALL OBTAIN ARCHITECTURAL DRAWINGS AND REVIEW
PRIOR TO INSTALLATION.
28. CHANGES IN THE DIRECTION OF SANITARY PIPING SHALL NOT BE MADE WITH
FITTINGS WHICH WILL CAUSE EXCESSIVE REDUCTION IN THE VELOCITY OF FLOW
OR CREATE ANY OTHER ADVERSE EFFECT UNLESS PHYSICALLY IMPOSSIBLE
(IE: USE OF SANITARY TEE IN A HORIZONTAL CONNECTION, USE OF A DOUBLE
SANITARY TEE IN A VERTICAL STACK, IN GENERAL, USE OF SHORT - RADIUS
FITTING FOR BRANCH TO HOUSE DRAIN OR STACK CONNECTION).
29. WHERE SANITARY SEWER LINES CROSS UNDERGROUND WATER SUPPLY LINES
WITH LESS THAN 8" MINIMUM VERTICAL CLEARANCE, THE SANITARY SEWER
SHALL BE CONSTRUCTED OF DUCTILE IRON PIPE (10' EACH SIDE OF WATER
MAIN) OR THE WATER LINES SHOULD BE MODIFIED TO PROVIDE 8" MINIMUM
CLEARANCE.
30. COORDINATE EXACT LOCATION OF EQUIPMENT ROOM DRAINS FOR HVAC
EQUIPMENT. CONDENSATE PIPING SHALL NOT DISCHARGE INTO SANITARY SYSTEM.
31. THIS CONTRACTOR SHALL BASE HIS PROPOSAL UPON THE EQUIPMENT AS
SCHEDULED OR SPECIFIED, USING THE MANUFACTURERS AND MODEL NUMBERS
AS CALLED FOR IN THE SPECIFICATIONS AND SCHEDULED ON THE DRAWINGS.
IF MORE THAN ONE MANUFACTURER OF EQUIPMENT IS SPECIFIED, ANY ONE
OF THE MANUFACTURERS OF EQUIPMENT MAY BE USED IN THIS CONTRACTOR'S
PROPOSAL. IF THIS CONTRACTOR WISHES TO USE EQUIPMENT NOT SPECIFIED
HE MUST, AT THE TIME OF BIDDING, SUBMIT SEPARATELY ON LETTERHEAD
STATIONARY OF THE BIDDER, THE EQUIPMENT HE WOULD SUBSTITUTE AND
THE COST TO BE ADDED OR TO BE DEDUCTED FROM HIS PROPOSAL.
33. THE CONTRACTOR IS EXPECTED TO ORDER ALL MATERIALS IN SUFFICIENT TIME
TO AVOID DELAYING THE COMPLETION OF THE PROJECT. DELAY IN DELIVERIES
WILL NOT BE CONSIDERED A JUSTIFIABLE REASON FOR SUBMISSION OF
SUBSTITUTE MATERIALS.
0
34. WARRANTY /GUARANTEE
A. THE CONTRACTOR SHALL WARRANTY /GUARANTEE AND MAINTAIN THE STABILITY
OF WORK AND MATERIALS AND KEEP SAME IN PERFECT REPAIR AND CONDITION
FOR THE PERIOD OF ONE YEAR.
B. DEFECTS OF ANY KIND DUE TO FAULTY WORK OR MATERIALS, APPEARING
DURING THE ABOVE MENTIONED PERIOD, MUST BE IMMEDIATELY REPAIRED BY
THE CONTRACTOR AT HIS OWN EXPENSE TO THE ENTIRE SATISFACTION OF THE
OWNER AND ENGINEER, SUCH RECONSTRUCTION AND REPAIRS SHALL INCLUDE
DAMAGE TO THE FINISH OR FURNISHING OF THE BUILDING RESULTING FROM THE
ORIGINAL DEFECT OR REPAIR THERETO.
35. CONTINUITY OF SERVICE: INTERRUPTIONS OF EXISTING SERVICES OR FACILITIES SHALL BE
KEPT TO A MINIMUM AND THE CONTRACTOR SHALL FURNISH ALL MATERIALS AND LABOR
REQUIRED WHENEVER TEMPORARY CONNECTIONS ARE NECESSARY TO MAINTAIN
CONTINUITY OF SERVICE. INTERRUPTIONS OF THE EXISTING SERVICES, THE INSTALLATION
OF TEMPORARY FACILITIES, AND THE WORK OF MAKING FINAL CONNECTIONS TO NEW
WORK SHALL BE DONE ONLY AT SUCH TIMES AS PERMITTED AND SCHEDULED BY THE
OWNER. ALL SUCH CONNECTIONS AND TIE -INS SHALL BE COORDINATED THROUGH THE
OWNERS PROJECT MANAGER.
1. THE DURATION OF EACH SHUTDOWN SHALL BE LIMITED TO NIGHTS AND /OR
WEEKENDS WITH THE TIME FRAME FOR SHUTDOWNS AS SPECIFIED BY THE
OWNER. THE CONTRACTOR SHALL NOTIFY THE OWNER IN WRITING FORTY -EIGHT
(48) HOURS IN ADVANCE OF EACH REQUIRED INTERRUPTION
OF EXISTING SERVICE.
2. THE CONTRACTOR SHALL INCLUDE IN BID PRICE ALL PREMIUM TIME CHARGES FOR
LABOR AND EQUIPMENT REQUIRED FOR ALL NIGHT AND WEEKEND OVERTIME WORK,
AS NECESSARY, TO COMPLETE THE SCOPE OF THE CONTRACT.
36. ALL WATER PIPING INSTALLED BELOW SLAB SHALL BE SOFT COPPER TYPE "K ",
WITH NO FITTINGS BELOW SLAB AND RUN WITHIN PVC SLEEVE.
37. PROVIDE FOUNDATION PAD PENETRATION SLEEVES. ALLOW 1" MINIMUM
CLEARANCE BETWEEN SLEEVE INSIDE SURFACE AND PIPE EXTERIOR.
38. ALL STORM PIPING, AND CONDENSATE PIPING SHALL BE INSULATED
THROUGHOUT ENTIRE SYSTEM.
39. PROVIDE A MINIMUM OF 6 INCHES BETWEEN ALL PIPING AND FIRE RATED AND SMOKE
TIGHT PARTITIONS FOR REQUIRED INSPECTIONS. ANY PIPING WITHIN THIS 6 INCHES
SPACE SHALL BE REQUIRED TO BE MOVED AND REROUTED. ANY COST IMPACT TO
OTHER TRADES WILL BE THE RESPONSIBILITY OF THE CONTRACTOR.
40. THE MAXIMUM VERTICAL DISTANCE FROM THE FIXTURE OUTLET TO THE TRAP
WEIR SHALL NOT EXCEED 24- INCHES AND THE HORIZONTAL DISTANCE SHALL
NOT EXCEED 30- INCHES MEASURED FROM THE CENTER LINE OF FIXTURE OUTLET
TO THE CENTERLINE OF THE INLET OF THE TRAP AS PER SECTION 1002 OF THE
FLORIDA PLUMBING CODE 2010.
41. PROVIDE THE REQUIRED CLEARANCES AND SPACE FOR ALL PLUMBING FIXTURES,
PLUMBING CONTRACTOR SHALL VERIFY AND COORDINATE PRIOR TO THE START OF
CONSTRUCTION.
42, ALL FIXTURE STOPS, VALVES, ETC., ALL PIPING SHALL BE RIGIDLY
SECURED (NO MOVEMENT WHEN OPERATED). INSTALL PERMANENT STAMPED BRASS
VALVE TAG ON EACH VALVE, COORDINATE WITH OWNER'S IDENTIFICATION SYSTEM.
43. INSULATION, FITTINGS COVERS AND ALL FINISHES AND MATERIALS SHALL HAVE A
MAXIMUM FLAME SPREAD RATING OF 25 AND A MAXIMUM SMOKE DEVELOPED RATING
OF 50.
44. DRAWINGS ARE DIAGRAMMATIC. DO NOT SCALE FROM DRAWINGS, BUT FIT WORK TO
ACTUAL CONDITION AND SPACE REQUIREMENTS.
45. ALL WORK SHALL BE PERFORMED BY A LICENSED CONTRACTOR IN A FIRST CLASS
WORKMANLIKE MANNER. THE COMPLETE SYSTEM SHALL BE FULLY AND PROPERLY
OPERATIVE, AND IN COMPLIANCE WITH APPLICABLE CODES AND GOVERNING
AUTHORITIES AND SUBJECT TO ACCEPTANCE BY OWNER/ENGINEER.
46. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, FEES, INSPECTIONS
AND TESTS.
47, ALL REQUIRED INSURANCES SHALL BE PROVIDED AND MAINTAINED BY THE
CONTRACTOR FOR THE PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY
DAMAGE, AND OTHER INSURANCES REQUIRED BY THE OWNER, FOR THE DURATION OF
THE WORK.
48. SHORT SWEEPS AT BASE OF SANITARY, STORM AND CONDENSATE STACKS ARE
NOT PERMITTED.
49. REFER TO DIVISION 15 SPECIFICATIONS FOR MORE INFORMATION.
50. CONTRACTOR SHALL SAW CUT CONCRETE FLOOR SLAB TO INSTALL NEW
BELOW SLAB PIPING AND SHALL PATCH THE SLAB TO MATCH THE EXISTING
CONCRETE SLAB.
51. CONTRACTOR SHALL PROVIDE COPIES OF ALL TEST REPORTS WITH CLOSE
OUT DOCUMENTS AT THE COMPLETION OF THE PROJECT.
n
5
PLUMBING CONTRACTOR IS REQUIRED TO SUBMIT PLUMBING AS BUILT PLANS
UPON COMPLETION OF THE PROJECT. COMPLETION IS DEFINED AS THE OWNER
RECEIVING A "CO" AND PLUMBING INSPECTOR HAS FINALIZED AND APPROVED THE
INSTALLATION.
AS BUILTS SHALL BE SUBMITTED IN ELECTRONIC FASHION IN EITHER AUTOCAD
FORMAT OR SCANNED FILES IN PDF FORMAT.
AS GUILTS SHALL BE LEGIBLE AND NEAT. AS BUILTS WILL BE RETAINED BY
ARCHITECT AND ENGINEER FOR RECORDS OF CHANGES TO THE SYSTEM. AS BUILTS
WILL BE SUBMITTED TO OWNER THROUGH ARCHITECT AND ENGINEER.
N
PLUMBING DEMOLITION NOTES
I
1. EXISTING SERVICES INDICATED ON THESE DRAWINGS WERE DERIVED FROM EMS TING
DRAWINGS AND LIMITED FIELD OBSERVATIONS. THESE DRAWINGS MAY NOT BE ALL
INCLUSIVE OF SERVICES THAT EXIST IN THE PROJECT AREA. CONTRACTOR SHA' -1-
VERIFY SERVICES, LOCATION, TYPE, AND SIZE PRIOR TO ANY CONSTRUCTION. 4N >'
DEVIATIONS IMPACTING WORK SHOWN ON THESE DOCUMENTS SHALL BE REPORTED
TO THE ARCHITECT FOR COORDINATION PRIOR TO CONSTRUCTION.
2. EXISTING SERVICES, EQUIPMENT, AND FIXTURES, TO REMAIN OR TO BE RELOCATED,
SHALL BE REPAIRED TO ORIGINAL OPERATION OR REPLACED, SHOULD THEY BE
DAMAGED DURING CONSTRUCTION.
3. ALL EXISTING WORK NOT SHOWN ON THESE DRAWINGS (UNLESS NOTED OTHERWISE)
SHALL REMAIN AS IS.
4. ALL PENETRATIONS OR OPENINGS FROM REMOVED PIPES THROUGH EXISTING
BUILDING WALLS AND FLOORS SHALL BE SLEEVED AND /OR PATCHED TO MATCH
ORIGINAL. SEE ARCHITECTURAL DRAWINGS FOR FINAL FINISHES,
5. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO EXISTING PIPING AND
FIXTURES DUE TO NEW CONSTRUCTION AND SHALL RESTORE EXISTING WORK
TO ITS ORIGINAL CONDITION AT NO COST TO THE OWNER.
6. CONTINUITY OF SERVICES: EXISTING BUILDING WILL REMAIN IN USE DURING
CONSTRUCTION OPERATIONS. WHEN AN INTERRUPTION OF AN EXISTING SERVICE
IS NECESSARY, CONTRACTOR SHALL COORDINATE WITH AUTHORIZED MAINTENANCE
PERSONNEL BEFORE MAKING THE NECESSARY INTERRUPTION.
7. CONTRACTOR TO REMOVE EXISTING STACKS AND RISERS LOCATED IN EXISTING
WALLS TO BE DEMOLISHED AND PROVIDE NEW OFFSETS AT CEILING ABOVE AND
BELOW FLOOR SLAB. COORDINATE LOCATION FOR NEW STACK OR RISER DROP
THROUGH FLOOR.
8. CONTRACTOR TO FIELD VERIFY THAT ALL EXISTING PLUMBING
TO BE REMOVED DOES NOT AFFECT OTHER AREA'S OF THE BUILDING THAT
ARE NOT IN CONSTRUCTION AND MUST STAY OPERATIONAL. IF DISCREPENCIES
ARE FOUND THE CONTRACTOR IS TO NOTIFY THE ENGINEER.
9. CONTRACTOR SHALL REMOVE EXISTING PLUMBING TO FIXTURES
TO BE REMOVED AS SHOWN ON DRAWINGS OR AS REQUIRED. CONTRACTOR SHALL
CAP SERVICES NEXT TO SERVICE MAINS IN CEILINGS, WALLS OR BELOW FLOOR,
CONTRACTOR SHALL REROUTE ALL ACTIVE PLUMBING SERVICES IN CHASES OR
WALLS TO BE REMOVED, TO NEW CHASE AREAS OR NEW WALLS AS REQUIRED,
10. CONTRACTOR SHALL SUBMIT A COMPLETE LIST OF PLUMBING FIXTURES, THAT
ARE TO BE REMOVED TO THE LOCAL OWNER'S REPRESENTATIVE.
ALL ITEMS THAT THE LOCAL OWNER'S REPRESENTATIVE WISHES
TO RETAIN SHALL BE TURNED OVER TO THE OWNER AND THE REMAINDER
SHALL BE REMOVED FROM THE SITE AND LEGALLY DISPOSED.
PLUMBING ABBREVIATIONS
C.W
COLD WATER
OFCI
OWNER FURNISHED CONTRACTOR INSTALLED
H.W.
HOT WATER
R.D.
ROOF DRAIN
H.W.R.
HOT WATER RECIRC
F.D.
FLOOR DRAIN
V.T.R.
VENT THRU ROOF
P.R.V.
PRESSURE REDUCING VALVE
AN.T.R.
ACID VENT THRU ROOF
R.P.B.P,
REDUCED PRESSURE BACKFLOW PREVENTER
W.
WASTE (INTERIOR) _
A.F.F.
ABOVE FINISHED FLOOR
R.W.L.
RAIN WATER LEADER
A.F.G.
ABOVE FINISHED GRADE
S.W.
STORM WATER
G.W.
GREASE WASTE
I.E.
INVERT ELEVATION
A.P.
ACCESS PANEL
C.O.
CLEANOUT
W.C.O.
WALL CLEANOUT -
C.D.
CONDENSATE
S.S.
SANITARY SEWER
C.F.C.I.
CONTRACTOR FURNISHED CONTRACTOR INSTALLED_
V.I.V.
VALVE IN VERTICAL
A.H.0
AIR HANDLING UNIT
F.C.0
FAN COIL UNIT
PLUMBING LEGEND
SYMBOL DESCRIPTION
SYMBOL DESCRIPTION
-
COLD WATER
l
BALL VALVE
- --
HOT WATER
- - -vim
CHECKVALVE
- - - --
HOT WATER RECIRCULATION
Ill
UNION IN PIPE -�
W
WASTE LINE
04-
SECTIONAL CONTROL VALVE
- -V --
VENT PIPE (ABOVE OR BELOW GROUND)
P5.1
EXTERIOR CLEANOUT
RW6
RAIN WATER LEADER
P -1;ETC -
FIXTURE INDENTIFICATION
CLEANOUT (ABOVE CEILING)
CONNECTION TO EXISTING
BALANCING VALVE CIRCUIT SETTER
WITH CHECK VALVE
CAP ON LINE v
PIPE TURNED UP
n
SHOCK ARRESTOR
PIPE TURNED DOWN
NG-
NATURAL GAS
---- - - -
GAS SOLENOID
-GN-
GREASE WASTE LINE
PS
PUMPED SANITARY
DFMW0NU KDEX
SHEET
NUMBER
SHEET TITLE
POA
PLUMBING LEGENDS, NOTES AND DRAWING INDEX
PO.2
PLUMBING SCHEDULES
PO.3
PLUMBING SPECIFICATIONS
PO.4
PLUMBING SPECIFICATIONS
PO.5
PLUMBING SPECIFICATIONS
PO.6
PLUMBING SPECIFICATIONS
P2.0
UNDERGROUND PLAN - NEW CONSTRUCTION - PLUMBING
P2.1
FIRST FLOOR PLAN - NEW CONSTRUCTION - PLUMBING
P4.1
PLUMBING RISER DIAGRAMS
P5.1
PLUMBING DETAILS
j&1I ARRAY
hPUltheare facilities solutions
6800 Broken Sound Boulevard NW
Suite 125
Boca Raton, FL 33487
t:561.995.1700
f:561.995.1701 firm license number
www.arrayhfs.com AA26000880
SEAL:
P S OF
CONSULTANTS:
SRSmith
Seckman
Reid, Inc.
600 West Hillsboro, Suite 300
Deerfield Beach, FL 33441
(954) 421 -1260
FAX: (954) 421 -1466
www.ssr- inc.com
Firm Certification - EB- 0000857
Michael A. Steward PE - 65701
John E. Moulder PE - 33200
SSR JOB # 1232003.0
OWNER:
BAPTIST HEALTH
HOSPITAL:
SOUTH MIAMI
HOSPITAL
PROJECT:
Info Desk and Coffee
Shop
ADDRESS:
6200 Southwest 73rd Street
South Miami, FL 33143
1
BID AND PERMIT SET
07 -30 -12
NO.
DESCRIPTION
DATE
REVISIONS /ISSUES
SHEET TITLE:
PLUMBING LEGENDS,
NOTES AND
DRAWING INDEX
DRAWN: FL CHECKED:
CON /REF No. 00000
PROJECT No. 3601
DATE: 07/30/12 SCALE: As indicated
SHEET NO.
P0.1
T'nia do:nm�nl i} u C OpyIi.1nI �. to�aad h� ' �.ir��;n % .,e, I r;l PI AV and
i,.en,etl for its in the, titled j roject only . ol u,e of fhc, docum�,nt
ni'hotr wirmn fl AITV' ie III iml :rid „tll I< I ^I1,if .he I'i,,
COPYRIGHT -2012 ARRAY HFS