Loading...
12-939-030U_ 1 2 3 4 5 6 7 ARRAY FIRE PROTECTION SECTION 15300 d. Straps shall not be permitted. PART 3 - EXECUTION e. Flexible sprinkler drops shall not be approved or permitted. healthcare facilities solutions PART 1 - GENERAL f. Mechanical couplings shall be manufactured in two segments of cast ductile iron, conforming to ASTM A -536, Grade 3.01 COORDINATION 65- 45 -12, Gaskets shall be pressure responsive synthetic rubber, grade to suite the intended service, conforming to 1.01 WORK INCLUDED ASTM D -2000. Mechanical couplings bolts shall be zinc plated (ATSM B -6330) heat treated carbon steel track head A. Coordinate installation to avoid Interference with other systems. 6800 Broken Sound Boulevard NW conforming to physical properties of ASTM A -449, minimum tensile strength 110,000 psi as provided. Suite 125 E A. Provide materials and labor required to completely execute the sprinkler and fire protection work for this 1) Installation ready rigid joints shall be Victaulic Fire Lock EZ Style 009, in sizes 1 -1/4" through 4 ", which shall 3.02 PIPE INSTALLATION as indicated on the drawings and as herein specified. be designed for direct stab installation onto grooved Boca Raton, FL 33487 project, 9 P g g pipe without prior disassembly of the coupling. Housings shall be cast with offsetting, angle- pattern bolt pads. A. Install sprinkler pipe a minimum of 12" above top of ceiling to allow for removal of ceiling the and lighting B. Scope of work: 2) Standard rigid joints shall be Victualic Style 005 Firelock 005 or 07 (zero - flex), ins sizes 1 -1/4" through 8 ". fixtures and for access to equipment above the ceiling. t:561.995.1700 1. Shop drawings. Housing shall be cast with offsetting, angle- pattern bolt pads, to provide system rigidity and support and hanging In f :561,995.1701 firm license number 2. Interior pipe, fittings, and valves, accordance with NFPA 13. Provide with V[cplus flush sea[ gasket. B. Support vertical pipe risers at 12' maximum distance or at least once at each floor. www,arrayhfs.com AA26000880 3, Hangers, supports and sleeves, g. Mechanical coupling gaskets shall be pressure responsive, synthetic rubber listed for use with the housings. 4. Sprinkler heads and extra sprinkler cabinet. h. Flange adapters shall be for use with grooved end pipe and fittings, for mating to ANSI Class 125/150 flanges. C. Use hanger types as specified in Part 2 above. This shall overrule hanger types outlined in NFPA 13. S. Fire extinguishers cabinets. Victaulic Style 741 or 744. For mating to ANSI Class 300 Flanges use Victaulic Style 743. 6, Testing and flushing. I. Grooved end fittings shall be cast of ductile iron conforming to ASTM -A536, Grade 65 -45 -12 (fire lock), forged steel D. Hanger spacing shall be In accordance with NFPA 13. Maximum spacing of 12 " -0" on center per FM requirements. SEAL: conforming to ASTM A -234, Grade WPB 0,375" wall or fabricated from STD, wt carbon steel pipe conforming to ASTM A -53, 1.02 RELATED WORK Type F E or S Grade B. Fittings provided with an alkyd enamel finish or hot dipped galvanized to ASTM A -153 zinc 91®11 [ 11 f ®® YP � � g P y PP g � E. Provide hangers on all arm outs of 12" or more in all cases. ® � electroplated fittings and couplings shall conform to ASTM B633. g ®�'® � E. o A. Division 7; Through - Penetration Firestop Systems j. Hole cut branch outlets shall have bolted branch outlets with branch reductions on 2" through 8'" header piping, F. Seal penetrations of fire rated walls and floors in accordance with U.L. Fire Resistance Index for �„,` ®Oeya Bolted branch outlets shall be manufactured from ductile Iron conforming to ASTM A -536, Grade 65- 45 -12, with synthetic Through - Penetration Firestop Systems. Coordinate requirements with Division 7. 4 B. Section 09900: Painting rubber gasket and heat treated carbon steel zinc plated bolts and nuts conforming to physical properties of ASTM A -183, Victualic Style 920/920N. i C. Section 15010: General Requirements G. Provide trapeze type hangers where necessary to support pipe when structural steel is not directly above for B. Drain Piping: support. m - 7 D. Section 15050: Basic Materials and Methods 0 `a E OF A4' 1. Schedule 40, A53 grade B, galvanized pipe. H. Provide 8 -1/2" x 11" floor plan in color at each sprinkler control valve within stairwell on wall of area served «;* 2. Fittings: Class 250 cast Iron, screwed with galvanized coating. by sprinkler system. Coordinate with contract documents and Life Safety drawings for areas served. •, t'o° +w E. Division 16: Electrical ., R 1 o a � 2,03 HANGERS AND SUPPORTS I. Pipe ends shall be clean and free from indentations, projections and roll marks In the area from pipe end to 1.03 INSTALLER QUALIFICATIONS groove. A. Acceptable manufacturers: Grinnell, Bline, Viking, Reliable Empire, Fee and Mason. Grinnell model numbers are = �_ A. Comply with local and state licensure requirements for installation of fire protection systems. used to establish level of product quality. J. The gasket style and elastomeric material (grade) shall be verified as suitable for the Intended service as CONSULTANTS: specified. 1.04 SYSTEM DESIGN B. Provide U.L. Listed and F.M. approved hangers. All hangers, hanger rods, and nuts shall be galvanized. K. All grooved components (couplings, fittings, valves, gaskets and specialities) shall be of one manufacturer, 1.05 QUALITY ASSURANCE C. Hangers: 1. Grinnel #260 MSS, Type 1 for pipe 2" through 12" L. Grooved coupling manufacturer's factory trained field representative shall provide on site training for D A. Underwriters Laboratories (U.L.) listed and Factory Mutual (F.M.) approved material, 2. Grinnell Figure #104, Type 6, adjustable split ring for pipe less than 2 ". contractor's field personnel In the proper use of grooving tools, application of grooved, and Installation of grooved Smith 3. Grinnell #69 for pipe 1/2" through 2 ". piping products, Seckman B. Comply with local fire department standards for hose threads, operating nuts and accessories for hydrants and 1. Minimum excess pressure of 10 psi including required hose stream allowance and sprinkler requirements. siamese connections. D. Clamps; 2. Maximum pipe velocity of 20 feet /second or as limited by Insuring agent, Reid, Inc. 1. Riser Clamps: Grinnell #261, MSS Type 8, at floor slab penetrations to support risers. C. The automatic sprinkler system Installer shall provide a permanently attached nameplate located at the 2, C- Clamps: Grinnell #92 with retainer clip, MSS Type 23. M. Hose stream allowance based on occupancy classification of remote area in addition to sprinkler demand. In 600 West Hillsboro, Suite 300 controlling alarm, Indicating the location and the discharge densities over designed areas of discharge Including 3. Mailable Beam Clamps: Grinnell Figure #218, MSS Type 30. penthouses, design system for 150 GPM hose allowance in addition to sprinkler demand. Deerfield Beach, FL 33441 gallons per minute and residual pressure, and hose stream demand supplied by the sprinkler piping. 1. A minimum of 18 inches clearance between bottom of sprinkler deflector and top of storage shelving. (954) 421 -1260 E. Inserts: 1.06 SUBMITTALS AND SHOP DRAWINGS 1. Concrete insert: Grinnell Figure #281, MSS Type 18, universal concrete insert, adequately sized and correctly N. All piping, fittings and valves shall be rated for 300 psi. FAX: (954) 421 -1466 positioned to support full load. www.ssr- inc.com A. Prepare complete detailed working shop drawings for fire protection system based on the contract documents pipe 2. Lightweight concrete: Grinnell #285. 3.03SPRINKLERS Finn Certification - EB- 0000857 sizes, general routing, and hydraulic calculations. 3. Continuous Concrete Insert: Grinnell Powerstrut #PS -349, pregalvanized. 4. Power Insert: HILTI KWIK -Bolt, zinc plated HDI metal expansion anchor. Use in conjunction with all thread rods. Michael A. Steward PE - 65701 A. Install sprinkler heads and required piping in areas such as concealed spaces, kitchen hoods, lab hoods, dietary John E. Moulder PE - 33200 B. After receiving shop drawing approval from Engineer, Contractor shall submit approved shop drawings to State, To be used on existing construction only, freezer and chill boxes and other special areas and spaces as required by NFPA 13 and NFPA 101. Local Fire Marshal and Owner's Insuring Agent. Submit shop drawings to architect and engineer for review and approval 5. Power Inserts shall not be used In post tension construction unless approved by Structural Engineer. SSR JOB # 1232003.0 prior to purchasing material and submittal to Building Department and before the start of Installation. If 6. All hangers, including nuts, bolts, rods, trapeze hangers, clevis and swivel ring hangers shall be hot dipped B. Provide drain valves, pipes and test connections as required by NFPA 13. Pipe drain lines and test connections to discrepancies are found on shop drawings prior to approval, contractor shall fix plans and installation to match galvanized where used at exterior applications. outside building or as shown and detailed on Drawings. Originate test lines from most hydraulically remote point of engineer's contract drawings: each sprinkler zone. C. Include the following manufacturer's product data with shop drawings: 2.04 SPRINKLER HEADS C. Install sprinkler heads centerline of corridors and locate in the center of the ceiling tiles. Install sprinkler 1. Sprinkler Heads. A. Acceptable Manufacturers: Reliable Sprinkler Company, Viking, Victaulic. heads in other designated spaces in the center of the ceiling tiles and symmetrically locate with other heads within 2. Pipe and fittings, the ceiling. Do not install sprinkler heads in other locations any closer than six Inches to any ceiling grid or wall. 3. Hangers and hanging method. B. Slip -type escutcheons will not be accepted. D. Sprinklers shall be installed a minimum of 12" from any HVAC diffuser, D. Include the following information on sprinkler shop drawings: OWNER: 1, Complete fire sprinkler system layout. C. Extended coverage heads systems will not be acceptable. 2. Piping and sizes based on contract documents. D. Sprinkler heads shall be U.L. Listed and F.M. approved. Concealed type quick response sprinkler head may be U.L. BAPTIST HEALTH 3, Pipe elevation, listed only. 4. Sprinkler head type and locations fully coordinated with lights and diffusers. Provide head schedule. 5. Hanger locations. E. Concealed Viking Horizon Mirage VK404, bulb type, 1/2" orifice. Quick Response, 5.6 "K" Factor. 6. Valve locations and elevations. C 7, All required construction notes, details including details for hanging pipe. F. Provide quick response heads in all areas. 8. Sprinkler zone served. G. Provide the following sprinkler heads of the proper type, rating and spacing. Appropriate must be compatible E. Purpose of shop drawing Is to convey that contractor understands intent of Contract Documents and to facilitate with room finishes. Slip -type escutcheons will not be accepted. HOSPITAL: coordination of sprinkler system with HVAC ductwork and other trades. H. Provide one sprinkler cabinet with 6 extra sprinkler heads and sprinkler wrench for emergency use, Locate F. Submit shop drawing and submittals to Owner's Insuring Agency for cabinet in maintenance area. Provide a minimum of two extra sprinkler heads of each type sprinkler head used for the SOUTH MIAMI p g g g y approval. project. Add an extra sprinkler cabinet if necessary to house the spare heads. G. Sprinkler fabrication and installation shall not commence prior to approval by the listed authorities. HOSPITAL H. Contractor shall provide copy of MIC - Microbiological Influenced Corrosion Test. PART 2 - PRODUCTS 2.01 VALVES PROJECT: p A. Acceptable Manufacturers: Nibco, WIIkins,Vlctaulic, Grinnell. Nlbco model numbers are used to establish required Info Desk a 1 y� I d Coffee e level of product quality. 2.02 PIPE AND FITTINGS Shop A. Interior Pipe and Fittings: 1, Schedule 10 ASTM -135, electric- resistance welded steel pipe suitable for roll grooving for piping 3" and larger. Provide ABF coating on pipe. Piping shall be rated for 300 psi. 2. Thinwall, ASTM -A -795 Type E, Grade A, electric resistance welded by Allied -Dyna Thread with a CRR = 1.0 for threaded ADDRESS: pipe ends and Allied XL /BLT for unthreaded thinwall pipe. Provide ABF coating on piping. For piping up to 3 ". Piping shall be rated for 300 psi. 6200 Southwest 73rd Street 3. Schedule 5 piping shall not be approved or permitted. 4. Fittings: South Miami, FL 33143 a. Mechanical couplings: Roll groove rigid type by Victaulic, or Grinnell U.L. listed for 300 psi. [� b. Class 250 cast iron sprinkler fittings U.L. listed - screwed flanged. B C. All fittings shall be by the same manufacturer and shall be UL /FM approved. 1 BID AND PERMIT SET 07 -30 -12 NO. DESCRIPTION DATE REVISIONS /ISSUES SHEET TITLE: FIRE PROTECTION w, SPECIFICATIONS 0 1n SP lyK�tltf`'�S th DRAWN: FL CHECKED: CON /REF No. 00000 PROJECT No, 3601 A DATE: 07/30/12 SCALE: As indicated SHEET NO. FPO,3 'hi ui "art i a o:1) 1c,I f.F- .l p s ^.ir nl 3cr i L _crt of ARRA" I Ir:. n:J fo! u •: Ire th .i I P J pIc; t :)n I). R o l tim ^r I c fhl rl _v iii rnthal t 11,it[ r P� ml. °,ior A i I, 'Hl cal (Ind r,lll be jnd�r the laa. COPYRIGHT - 2012 ARRAY HFS