Loading...
12-939-018E Lam/ Cif no w 1 2 SECTION 017329 -CUTTING AND PATCHING 1.1 SUMMARY A. CUTTING AND PATCHING REQUIRED BY'f HE FOLLOWING: 1. INSTALLATION OF OTHER MATERIALS. 2. FINISHING. 3. ALTERATIONS. 4. TESTS AND INSPECTIONS. 1.2 QUALITY ASSURANCE A. LIMITATIONS ON CUTTING AND PATCHING: 1. STRUCTURAL ELEMENTS: DO NOT CUT AND PATCH STRUCTURAL ELEMENTS IN A MANNER THAT COULD CHANGE THEIR LOAD - CARRYING CAPACITY OR LOAD- DEFLECTION RATIO. 2. OPERATIONAL ELEMENTS: DO NOT CUT AND PATCH OPERATING ELEMENTS AND RELATED COMPONENTS IN A MANNER THAT RESULTS IN REDUCING THEIR CAPACITY TO PERFORM AS INTENDED OR THAT RESULTS IN INCREASED MAINTENANCE OR DECREASED OPERATIONAL LIFE OR SAFETY. 3. MISCELLANEOUS ELEMENTS: DO NOT CUT AND PATCH MISCELLANEOUS ELEMENTS OR RELATED COMPONENTS IN A MANNER THAT COULD CHANGE THEIR LOAD- CARRYING CAPACITY, THAT RESULTS IN REDUCING THEIR CAPACITY TO PERFORM AS INTENDED, OR THAT RESULTS IN INCREASED MAINTENANCE OR DECREASED OPERATIONAL LIFE OR SAFETY. 4. VISUAL REQUIREMENTS: DO NOT CUT AND PATCH CONSTRUCTION IN A MANNER THAT RESULTS IN VISUAL EVIDENCE OF CUTTING AND PATCHING. DO NOT CUT AND PATCH CONSTRUCTION EXPOSED ON THE EXTERIOR OR IN OCCUPIED SPACES IN A MANNER THAT WOULD, IN ARCHITECTS OPINION, REDUCE THE BUILDING'S AESTHETIC QUALITIES. REMOVE AND REPLACE CONSTRUCTION THAT HAS BEEN CUT AND PATCHED IN A VISUALLY UNSATISFACTORY MANNER. a. WHERE APPLICABLE - REMOVE AND REPLACE EXISTING WALL COVERING, EXISTING CORRIDOR HANDRAIL, GUARDRAILS, ACOUSTICAL CEILING PANELS AND GRID, AND EXISTING FLOORING. 1.3 WARRANTY A. EXISTING WARRANTIES: REMOVE, REPLACE, PATCH, AND REPAIR MATERIALS AND SURFACES CUT OR DAMAGED DURING CUTTING AND PATCHING OPERATIONS, BY METHODS AND WITH MATERIALS SO AS NOT TO VOID EXISTING WARRANTIES, INCLUDING ROOFING IF APPLICABLE. 1.4 MATERIALS A. GENERAL: COMPLY WITH REQUIREMENTS SPECIFIED IN OTHER SECTIONS. B. IN -PLACE MATERIALS: USE MATERIALS IDENTICAL TO IN -PLACE MATERIALS. FOR EXPOSED SURFACES, USE MATERIALS THATVISUALLY MATCH WPLACE ADJACENT SURFACES TO THE FULLEST EXTENT POSSIBLE. 1. IF IDENTICAL MATERIALS ARE UNAVAILABLE OR CANNOT BE USED, USE MATERIALS THAT, WHEN INSTALLED, WILL MATCH THE VISUAL AND FUNCTIONAL PERFORMANCE OF IN -PLACE MATERIALS. C. PROVIDE FIRE - RESISTIVE MATERIALS AND FIRESTOPPING MATERIALS THAT ARE COMPATIBLE WITH EXISTING AND SUBSTRATES AND ARE APPROVED BY UL OR ANOTHER TESTING AND INSPECTING AGENCY ACCEPTABLE TO AUTHORITIES HAVE JURISDICTION FOR USE IN FIRE - RESISTIVE DESIGNS INDICATED. D. CONCRETE WORK SHALL CONFORM TO AMERICAN CONCRETE INSTITUTE STANDARD 301 SPECIFICATION. USE PORTLAND CEMENT TYPE 1 PER ASTM C150 AND NORMAL WEIGHT AGGREGATES PER ASTM C33. DESIGN MINIMUM TO BE 3000 LBS. NORMAL WEIGHT CONCRETE. READY -MIX TO COMPLY WITH ASTM C94. E. ROOFING MATERIAL, FLASHING, AND ROOF SPECIALTIES MATERIAL: SELECTION SHOULD BE ON THE COMPATIBILITY WITH THE EXISTING ROOFING SYSTEM COMPONENTS AND APPROVED BY THE EXISTING ROOFING MANUFACTURER SO THEY ARE IN COMPLIANCE WITH THE EXISTING WARRANTY. 1.5 EXECUTION A. TEMPORARY SUPPORT OF WORK BEING CUT. B. PROTECTION: PROTECT IN -PLACE CONSTRUCTION DURING CUTTING AND PATCHING TO PREVENT DAMAGE. PROVIDE PROTECTION FROM ADVERSE= WEATHER CONDITIONS FOR PORTIONS OF PROJECT THAT MIGHT BE EXPOSED DURING CUTTING AND PATCHING OPERATIONS. C. ADJOINING AREAS: AVOID INTERFERENCE WITH USE OF ADJOINING AREAS OR INTERRUPTION OF FREE PASSAGE TO ADJOINING AREAS. D. EXISTING SERVICES: SERVICES BYPASSED BEFORE CUTTING TO AVOID INTERRUPTION TO OCCUPIED AREAS. E. EMPLOY SKILLED WORKERS TO PERFORM CUTTING AND PATCHING. PROCEED WITH CUTTING AND PATCHING AT THE EARLIEST FEASIBLE TIME, AND COMPLETE WITHOUT DELAY. 1. CUT IN -PLACE CONSTRUCTION TO PROVIDE FOR INSTALLATION OF OTHER COMPONENTS OR PERFORMANCE OF OTHER CONSTRUCTION, AND SUBSEQUENTLY PATCH AS REQUIRED TO RESTORE SURFACES TO THEIR ORIGINAL CONDITION. 2. ALL EXISTING WALLS WITHIN THE SCOPE OF THIS PROJECT SHALL BE PATCHED AND REPAIRED TO REMOVE ALL VISIBLE DEFECTS PRIOR TO PAINTING OR FINISHING OF THE WALL. 3. PATCHING AND REPAIR SHALL CONSIST OF REMOVING ALL LOOSE, CRACKED AND UNSOUND GYPSUM BOARD OR OTHER MATERIALS AND SUPPORTS, AND INSTALLING NEW MATERIAL TO MATCH THE EXISTING CONSTRUCTION, ACCORDING TO THE MANUFACTURERS RECOMMENDATIONS. REPAIRED AREAS SHALL NOT BE VISIBLY APPARENT FROM ADJACENT AREAS. 4. ALL HOLES SHALL BE FILLED AND VISIBLE JOINTS, CRACKS, CRAZES, TOOL MARKS, WAVES, STAINS OR OTHER DEFECTS SHALL NOT APPEAR ON THE FINISHED WORK. F. CUTTING: CUT IN -PLACE CONSTRUCTION BY SAWING, DRILLING, BREAKING, CHIPPING, GRINDING, AND SIMILAR OPERATIONS, INCLUDING EXCAVATION, USING METHODS LEAST LIKELY TO DAMAGE ELEMENTS RETAINED OR ADJOINING CONSTRUCTION. IF POSSIBLE, REVIEW PROPOSED PROCEDURES WTH ORIGINAL INSTALLER; COMPLY WITH ORIGINAL INSTALLER'S WRITTEN RECOMMENDATIONS. G. PATCHING: PATCH CONSTRUCTION BY FILLING, REPAIRING, REFINISHING, CLOSING UP, AND SIMILAR OPERATIONS FOLLOWING PERFORMANCE OF OTHER WORK. PATCH WITH DURABLE SEAMS THATARE AS INVISIBLE AS POSSIBLE. PROVIDE MATERIALS AND COMPLY WITH INSTALLATION REQUIREMENTS SPECIFIED IN OTHER SECTIONS. 1. PATCH VOIDS IN FLOOR AND WALLS AT REMOVED WALLS TO PROVIDE A SMOOTH SURFACE AS REQUIRED TO MATCH EXISTING AND FOR NEWFINISHES. 2. GRIND HIGH SPOTS AND FILL LOW AREAS IN FLOOR WITH LATEX CONCRETE TO PROVIDE A SURFACE FREE FROM RIDGES, DEPRESSIONS AND BLEMISHES WHICH CAN BE SEEN OR FELT AFTER NEW FLOOR COVERING IS INSTALLED. 3. WHERE WALLS ARE REMOVED THE CONTRACTOR SHALL VERIFY THAT THE EXISTING WALLS AND FLOORS ARE IN THE SAME PLANE OR ELEVATION. SAND, GRIND OR FILL AS REQUIRED TO PROVIDE A SMOOTH TRANSITION AT ALL SUCH DIFFERENCES. H. CLEANING: CLEAN AREAS AND SPACES WHERE CUTTING AND PATCHING ARE PERFORMED. COMPLETELY REMOVE PAINT, MORTAR, OILS, PUTTY, AND SIMILAR MATERIALS. END OF SECTION 017329 3 4 SECTION 017315 - HOSPITAL PROCEDURES 1.1 REGULATIONS A. THE CONTRACTOR SHALL AT ALL TIMES ABIDE BY THE REGULATIONS OF (STATE AGENCY OR APPLICABLE CODES) AND ALL AMENDMENTS, INCLUDING THOSE THAT MAY BE ISSUED DURING THE DURATION OF THE CONTRACT. PARTICULAR ATTENTION IS CALLED TO THOSE REGULATIONS PERTAINING TO CIRCULATION, NOISE, SANITATION, SAFETY AND BEHAVIOR. B. THE CONTRACTOR SHALL AT ALL TIMES ABIDE BY THE INTERIM LIFE SAFETY MEASURES AND INFECTION CONTROL REQUIREMENT OUTLINED IN THE CONTRACT DOCUMENTS, APPLICABLE CODES (NFPA 95 AND NFPA 101) AND AIA GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITAL AND HEALTHCARE FACILITIES. 1.2 BAPTIST HEALTH SOUTH FLORIDA - CORPORATE CONSTRUCTION MANAGEMENT A. THE CONTRACTOR SHALL ABIDE BY THE DIRECTIONS OF BAPTIST HEALTH SOUTH FLORIDA - CORPORATE CONSTRUCTION MANAGEMENT IN MATTERS AFFECTING THE OPERATION, SAFETY, AND SECURITY OF THE HOSPITAL, ITS PATIENTS AND ITS VISITORS. B. THE CONTRACTOR SHALL ABIDE BY ALL DIRECTIONS OF BAPTIST HEALTH SOUTH FLORIDA -CORPORATE CONSTRUCTION MANAGEMENT WHICH SHALL BE IMPLEMENTED IMMEDIATELY. CONFIRMATION OR EXPLANATION OF ORAL INSTRUCTION WILL BE MADE BY SOUTH MIAMI HOSPITAL IN WRITING OR INCLUDED IN THE MEETING MINUTES AT THE NEXT SCHEDULED PROGRESS MEETING. C. ALL PERSONNEL EMPLOYED BY THE CONTRACTOR, INCLUDING SUBCONTRACTORS AND THEIR EMPLOYEES, SHALL BE INSTRUCTED TO ABIDE BY ALL PUBLISHED REGULATIONS, AND ALL DIRECTIVES OF BAPTIST HEALTH SOUTH FLORIDA - CORPORATE CONSTRUCTION MANAGEMENT. 1.3 NOISE CONTROL A. THE CONTRACTOR SHALL EXECUTE THE WORK IN THIS CONTRACT AS QUIETLY AS PRACTICABLE TO AVOID UNNECESSARY DISTURBANCES TO PATIENTS WITHIN THE HOSPITAL PREMISES. B. ANY COMPLAINTS DULY REGISTERED BY SOUTH MIAMI HOSPITAL OF UNACCEPTABLE NOISE LEVELS SHALL BE CAUSE FOR THE USE OF SPECIAL PRECAUTIONS AND METHODS OF OPERATION BY THE CONTRACTOR TO REDUCE NOISE TO AN ACCEPTABLE LEVEL. C. SOUTH MIAMI HOSPITAL SHALL BE THE SOLE JUDGE OF THE TOLERABILITY OF NOISE LEVEL. D. THE CONTRACTOR SHALL PREPARE A "NOISE SCHEDULE" AS SOON AS PRACTICABLE INDICATING THE TYPE OF DEMOLITION AND/OR NOISE INDUCING WORK SHOWING THE DATES, TIMES AND DURATION OF SUCH WORK. 1.2 PERSONNEL IDENTIFICATION A. ALL CONTRACTORS ARE REQUIRED TO FOLLOW PROCEDURES ESTABLISHED BY BAPTIST HEALTH SOUTH FLORIDA - CORPORATE CONSTRUCTION MANAGEMENT FOR CONTRACTOR IDENTIFICATION. B. ANY OF THE CONTRACTOR'S OR SUBCONTRACTOR'S PERSONNEL WHO DO NOT COMPLY WITH THESE REQUIREMENTS AT ALL TIMES, WILL BE DENIED ACCESS TO THE HOSPITAL OR WILL BE ESCORTED OFF THE PREMISES BY THE HOSPITAL SECURITY GUARDS. 13 PERSONNEL PARKING A. THE CONTRACTOR SHALL COORDINATE WITH BAPTIST HEALTH SOUTH FLORIDA - CORPORATE CONSTRUCTION MANAGEMENT APPROPRIATE AREAS FOR PARKING OF HIS PERSONNEL AND EMPLOYEES. LOCATION WILL BE AS DIRECTED BY BAPTIST HEALTH SOUTH FLORIDA - CORPORATE CONSTRUCTION MANAGEMENT. 1.4 PERSONNEL DEPORTMENT A. ALTHOUGH INVOLVED IN CONSTRUCTION ACTIVITIES, PERSONNEL MUST RECOGNIZE THAT THEY ARE WORKING IN A HEALTHCARE FACILITY AND GOVERN THEMSELVES ACCORDINGLY. VULGAR OR SEXUAL COMMENTS DIRECTED AT HOSPITAL STAFF OR VISITORS OR ANY OTHER OFFENSIVE BEHAVIOR WILL BE GROUNDS FOR IMMEDIATE REMOVAL FROM THE HOSPITAL. SINCE HOSPITAL PATIENTS ARE FREQUENTLY ON THE OTHER SIDE OF THE TEMPORARY CONSTRUCTION WALLS, EXCESSIVE SOUND TRANSMISSION WILL NOT BE TOLERATED. 1.5 NORMAL LIMIT OF OPERATIONS A. THE CONTRACTOR'S NORMAL LIMIT OF OPERATIONS SHALL BE CONFINED WITHIN THE LIMIT OF CONSTRUCTION AS DESIGNATED ON THE DRAWINGS OR AS DIRECTED BY BAPTIST HEALTH SOUTH FLORIDA - CORPORATE CONSTRUCTION MANAGEMENT. B. SOUTH MIAMI HOSPITAL, ARCHITECT, AND OTHER CONTRACTORS PERFORMING WORK SHALL BE ALLOWED ACCESS TO THE CONSTRUCTION AREA AT ALL TIMES, 1.6 PERIODIC OPERATIONS OUTSIDE LIMITS OF OPERATION A. USE OF CERTAIN LOADING DOCKS, PASSAGEWAYS, ELEVATOR, AND OTHER AREAS, OUTSIDE THE LIMITS OF CONSTRUCTION (AS DEFINED), WILL BE GRANTED TO THE CONTRACTOR BY SOUTH MIAMI HOSPITAL ON AN INTERMITTENT BASIS AS REQUIRED AND REQUESTED IN ADVANCE BY THE CONTRACTOR. SOUTH MIAMI HOSPITAL WILL JUDGE THE PROPER TIME AND EXTENT OF SUCH USE. 1.7 SCHEDULING A. ALL ARRANGEMENTS FOR WORK WHICH WILL INVOLVE INTERFERENCE WITH NORMAL HOSPITAL FUNCTIONING, PARTICULARLY IN OCCUPIED PATIENT AREAS, OR ADJACENT THERETO, SHALL BE SCHEDULED IN ADVANCE WITH BAPTIST HEALTH SOUTH FLORIDA - CORPORATE CONSTRUCTION MANAGEMENT TO PROVIDE MINIMUM DISRUPTION AND INCONVENIENCE. 1.8 UTILITY TIE -INS AND OUTAGES A. THE CONTRACT DOCUMENTS AND/OR FIELD CONSTRUCTION CIRCUMSTANCES MAY REQUIRE A SHUTDOWN OF ONE OR MORE UTILITY SYSTEMS SUCH AS WATER SERVICE, ELECTRIC POWER, MEDICAL GASES OR HVAC PIPING /SYSTEMS. ANYTIME THATA UTILITY SHUTDOWN IS REQUIRED FOR TIE -IN OR OTHER PURPOSE THE CONTRACTOR MUST PROVIDE SOUTH MIAMI HOSPITAL WTH A MINIMUM OF 72 HOURS PRIOR WRITTEN NOTICE OF INTENT. THE NOTICE SHALL BE IN THE FORM OF AN OUTAGE REQUEST AND MUST DETAIL THE REASON, SCOPE AND DURATION. PROVISIONS FOR SUPPORTING ANY CRITICAL LOADS WHICH MAYBE AFFECTED MUST BE DESCRIBED, EVEN IF SOUTH MIAMI HOSPITAL STAFF WILL BE ASSISTING WITH SETUP AND COORDINATION. B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SEARCHING OUT UTILITY AND SERVICE LINES TO DETERMINE IF THEY WOULD RESULT IN AN OUTAGE IN THE HOSPITAL. APPROVAL SHALL BE OBTAINED FROM BAPTIST HEALTH SOUTH FLORIDA - CORPORATE CONSTRUCTION MANAGEMENT TO EXECUTE SUCH SEARCHES IN ADVANCE. 1.9 WORKING HOURS AND OVERTIME NOTIFICATION A. THE CONTRACTOR SHALL RECEIVE PERMISSION FROM BAPTIST HEALTH SOUTH FLORIDA - CORPORATE CONSTRUCTION MANAGEMENT FOR THE CONTRACTOR'S PERSONNEL TO WORK OUTSIDE OF NORMAL DAYTIME HOURS EITHER WITHIN OR OUTSIDE THE LIMITS OF CONSTRUCTION. NORMAL WORKING HOURS ARE CONSIDERED TO BE 7:30 A.M. TO 4:00 P.M., MONDAY THROUGH FRIDAY. 1.10 MAINTAINING BUILDING INTEGRITY A. THE INTEGRITY OF FIRE STOP PARTITIONS, SMOKE COMPARTMENTS AND FIRE DOORS IS A MAJOR CONCERN. BREECHES OF THESE BARRIERS DURING CONSTRUCTION MUST BE MINIMIZED IN BOTH QUANTITY AND DURATION. ALL PIPE, CONDUIT, DUCT OR OTHER PENETRATIONS OF WALLS OR FLOORS MUST BE SEALED. THE HOSPITAL WILL NOT BE RESPONSIBLE FOR SEALING OR REPAIRING WALLS AND FLOOR BREACHED BY THE CONTRACTOR OR CONNECTED WITH HIS WORK. THE CONTRACTOR MAY NOT REMOVE OR PROP OPEN FIRE DOORS UNLESS IT IS REQUIRED TO PERFORM THE WORK AND PERSONNEL ARE CONTINUALLY PRESENT TO SECURE THE OPENING IN THE EVENT OF AN EMERGENCY. 1.11 USE OF FACILITIES: THE CONTRACTOR'S EMPLOYEES SHALL CONFINE THEIR ACTIVITIES TO THE WORK AREA AND SHALL NOT ENTER OTHER PORTIONS OF THE BUILDING WITHOUT PERMISSION FROM SOUTH MIAMI HOSPITAL. END OF SECTION 017315 J SECTION 017700 - CLOSEOUT PROCEDURES 1.1 SUMMARY A. SUBSTANTIAL COMPLETION PROCEDURES. B. FINAL COMPLETION PROCEDURES. C. WARRANTIES. D. FINAL CLEANING. 1.2 SUBSTANTIAL COMPLETION PROCEDURES: BEFORE FINAL INSPECTION BY ARCHITECT: A. FINAL APPLICATION FOR PAYMENT SUBMITTED. B. LIST OF INCOMPLETE ITEMS (PUNCH LIST) ENDORSED BY ARCHITECT AS COMPLETED. C. EVIDENCE OF CONTINUING INSURANCE COVERAGE SUBMITTED. D. FINAL PEST - CONTROL INSPECTION REPORTAND WARRANTY SUBMITTED. 1.3 FINAL COMPLETION A. PRELIMINARY PROCEDURES: BEFORE REQUESTING FINAL INSPECTION FOR DETERMINING FINAL COMPLETION, COMPLETE THE FOLLOWING: 1. SUBMITA FINAL APPLICATION FOR PAYMENT ACCORDING TO DIVISION 01 SECTION "PAYMENT PROCEDURES" 2. SUBMIT CERTIFIED COPY OF ARCHITECTS SUBSTANTIAL COMPLETION INSPECTION LIST OF ITEMS TO BE COMPLETED OR CORRECTED (PUNCH LIST), ENDORSED AND DATED BY ARCHITECT. THE CERTIFIED COPY OF THE LIST SHALL STATE THAT EACH ITEM HAS BEEN COMPLETED OR OTHERWISE RESOLVED FOR ACCEPTANCE. 3. SUBMIT EVIDENCE OF FINAL, CONTINUING INSURANCE COVERAGE COMPLYING WITH INSURANCE REQUIREMENTS. 4. INSTRUCT OWNER'S PERSONNEL IN OPERATION, ADJUSTMENT, AND MAINTENANCE OF PRODUCTS, EQUIPMENT, AND SYSTEMS. SUBMIT DEMONSTRATION AND TRAINING VIDEO RECORDINGSIF REQUIRED. B. INSPECTION: SUBMIT WRITTEN REQUEST FOR FINAL INSPECTION FOR ACCEPTANCE. ON RECEIPT OF REQUEST, ARCHITECT [AND CONSTRUCTION MANAGER] WILL EITHER PROCEED WITH INSPECTION OR NOTIFY CONTRACTOR OF UNFULFILLED REQUIREMENTS. ARCHITECT WILL PREPARE A FINAL PUNCH LIST AFTER INSPECTION AND WI LL NOTIFY CONTRACTOR OF CONSTRUCTION THAT MUST BE COMPLETED. 1. REINSPECTION: REQUEST REINSPECTION WHEN THE WORK IDENTIFIED IN PREVIOUS INSPECTIONS AS INCOMPLETE IS COMPLETED OR CORRECTED 1.4 WARRANTIES: SUBMITTED WITHIN 15 DAYS FOR AREAS OF PARTIAL OCCUPANCY. A. ORGANIZED AND BOUND IN HEAVY -DUTY, THREE -RING, VINYL - COVERED, LOOSE -LEAF BINDERS, WITH PAPER DIVIDERS. BINDER FRONT AND SPINE IDENTIFIED WITH TITLE, PROJECT NAME, AND NAME OF CONTRACTOR. 1.5 FINAL CLEANING: A. EACH SURFACE OR UNIT CLEANED TO CONDITION EXPECTED IN AN AVERAGE COMMERCIAL BUILDING CLEANING AND MAINTENANCE PROGRAM. B. CLEAN DUCTS, BLOWERS, AND COILS FOR UNITS OPERATED WITHOUT FILTERS DURING CONSTRUCTION.1.1 MATERIALS C. CLEANING AGENTS: USE CLEANING MATERIALS AND AGENTS RECOMMENDED BY MANUFACTURER OR FABRICATOR OF THE SURFACE TO BE CLEANED. DO NOT USE CLEANING AGENTS THAT ARE POTENTIALLY HAZARDOUS TO HEALTH OR PROPERTY OR THAT MIGHT DAMAGE FINISHED SURFACES. END OF SECTION 017700 SECTION 017823 - OPERATION AND MAINTENANCE DATA 1.1 SECTION INCLUDES ADMINISTRATIVE AND PROCEDURAL REQUIREMENTS FOR PREPARING OPERATION AND MAINTENANCE MANUALS, A. PRODUCT MAINTENANCE MANUALS. 1.2 EMERGENCY, OPERATION AND MAINTENANCE MANUALS. A. FORMAT:. PDF ELECTRONIC FILES VATH COMPOSITE ELECTRONIC INDEX ON DIGITAL MEDIA ACCEPTABLE TO ARCHITECT. INCLUDE A COMPLETE ELECTRONICALLY- LINKED OPERATION AND MAINTENANCE DIRECTORY. B. HEAVY -DUTY, THREE -RING, VINYL - COVERED, LOOSE -LEAF BINDERS,THREE (3) SETS) OF COPIES. (INCLUDE LAMINATE SAMPLES.) C. PRODUCT MAINTENANCE MANUALS: SOURCE INFORMATION, PRODUCT INFORMATION, MAINTENANCE PROCEDURES, REPAIR MATERIALS AND SOURCES, AND WARRANTIES AND BONDS. END OF SECTION 017823 SECTION 017839 - PROJECT RECORD DOCUMENTS 1.1 RECORD DRAWINGS: A. ONE OF MARKED -UP RECORD PRINTS. B. INITIAL SUBMITTAL: ONE PAPER COPY SET, PDF ELECTRONIC FILES OF MARKED -UP RECORD PRINTS AND ONE SETS) OF PLOTS FROM CORRECTED RECORD DIGITAL DATA FILES. C. FINAL SUBMITTAL: SUBMIT ONE PAPER COPY SETAND PDF ELECTRONIC FILES OF MARKED -UP RECORD PRINTS, D. RECORD SPECIFICATIONS: ANNOTATED PDF ELECTRONIC FILES, 1.2. RECORD PRODUCT DATA: A. ONE PAPER COPY, ANNOTATED PDF ELECTRONIC FILES AND DIRECTORIES. B. MISCELLANEOUS RECORD SUBMITTALS: ONE PAPER COPY AND ANNOTATED PDF ELECTRONIC FILES AND DIRECTORIES. 1.3 PRODUCTS A. RECORD PRINTS: ONE SET OF PAPER COPIES OF CONTRACT DOCUMENTS AND SHOP DRAWINGS, MARKED TO SHOW ACTUAL INSTALLATION. B. RECORD DIGITAL DATA FILES: CORRECTED DIGITAL DATA FILES OF THE CONTRACT DRAWINGS, AS FOLLOWS: 1. FORMAT: ANNOTATED PDF ELECTRONIC FILE WITH COMMENT FUNCTION ENABLED. END OF SECTION 017839 6 7 SECTION 064023 - INTERIOR ARCHITECTURAL WOODWORK 1.1 THIS SECTION INCLUDES THE FOLLOWING: INTERIOR STANDING AND RUNNING TRIM. PLASTIC - LAMINATE CABINETS. CABINET HARDWARE AND ACCESSORIES, PLASTIC-LAMINATE COUN E TOPS. SOLID- SURFACING - MATERIAL COUNTERTOPS. A. FIRE- TEST - RESPONSE CHARACTERISTICS: WHERE FIRE - RETARDANT MATERIALS OR PRODUCTS ARE INDICATED, PROVIDE MATERIALS AND PRODUCTS 100TH SPECIFIED FIRE - TEST - RESPONSE CHARACTERISTICS AS DETERMINED BY TESTING IDENTICAL PRODUCTS PER TE STMETHOD INDICATED B UL ITS OR ANOTHER T ESTING AN D INSPECTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION. IDENTIFY WITH APPROPRIATE MARKINGS OF APPLICABLE TESTING AND INSPECTING GENCY IN THE FORM OF SEPARABLE PAPER LABEL OR, WHERE REQUIRED BY AUTHORITIES HAVING JURISDICTION, IMPRINT ON SURFACES OF MATERIALS THAT WILL BE CONCEALED FROM VIEW AFTER INSTALLATION. 1.2 MATERIALS A. GENERAL: PROVIDE MATERIALS THAT COMPLY WITH REQUIREMENTS OF AN'S QUALITY STANDARD FOR EACH TYPE OF WOODWORK AND Q UALITY GRADE SPECIFIED UNLESS OTHERWISE INDICATED. B. MEDIUM - DENSITY FIBERBOARD: ANSI A208.2, GRADE MD, MADE WITH BINDER CONTAINING NO UREA FORMALDEHYDE. C. HIGH - PRESSURE DECORATIVE LAMINATE: NEMA LID 3, GRADES AS INDICATED OR, IF NOT INDICATED, AS REQUIRED BY WOODWORK QUALITY STANDARD. D. SOLID- SURFACING MATERIAL: HOMOGENEOUS SOLID SHEETS OF FILLED PLASTIC RESIN COMPLYING WITH ISSFA -2. 1.3 CABINET HARDWARE A. GENERAL: PROVIDE CABINET HARDWARE AND ACCESSORY MATERIALS ASSOCIATED WITH ARCHITECTURAL CABINETS, EXCEPT FOR ITEMS SPECIFIED IN DIVISION 08 SECTION "DOOR HARDWARE (SCHEDULED BY DESCRIBING PRODUCTS)." B. BUTT HINGES: 2 -314 -INCH (70 -MM), 5- KNUCKLE STEEL HINGES MADE FROM 0.095 -INCH- (2.4-MM-) THICK METAL, AND AS FOLLOWS: 1. SEMI - CONCEALED HINGES FOR OVERLAY DOORS. BHMA A156.9, 601521. C. FRAMELESS CONCEALED HINGES (EUROPEAN TYPE): BHMAA156.9, B01602,135 DEGREES OF OPENING, HINGES SHALL BE CAM ADJUSTABLE FOR ALIGNMENT. D. BACK- MOUNTED PULLS: BHMA A156.9, B02011. SATIN CHROME FINISH. E. WIRE PULLS: BACK MOUNTED, SOLID METAL 4 INCHES LONG, 5116 INCH IN DIAMETER. F. CATCHES: MAGNETIC CATCHES, BHMA A156.9, B03141. G. ADJUSTABLE SHELF STANDARDS AND SUPPORTS: BHMA Al56A B04071; WITH SHELF RESTS, B04081 BHMA Al 56.9, B04102, WITH SHELF BRACKETS, B04112. H. SHELF RESTS: BHMA A156.9, B04013; METAL. I. DRAWER SLIDES: BHMA A156.9, B05091. 1. HEAVY DUTY (GRADE 1HD 100 AND GRADE 1HD-200): SIDE MOUNTED; FULL - EXTENSION TYPE, ZINC PLATED STEEL BALL - BEARING SLIDES. 2. BOX DRAWER SLIDES: GRADE 1 HD -100; FOR DRAWERS NOT MORE THAN 6INCHES (150 MM) HIGH AND 24 INCHES (600 MM) WIDE. 3. FILE DRAWER SLIDES: GRADE 1HD -200; FOR DRAWERS MORE THAN 13 INCHES (150 MM) HIGH OR 24 INCHES (600 MM) WIDE. 4. PENCIL DRAWER SLIDES: GRADE 1; FOR DRAWERS NOT MORE THAN 3 INCHES (15 MM) HIGH AND 24 INCHES (600 MM) WIDE. J. DOOR LOCKS: BHMA A156.11, E07121. K. DRAWER LOCKS: BHMA Al 56.11, E07041. L. GROMMETS FOR CABLE PASSAGE THROUGH COUNTERTOPS: 2 - INCH OD, CHROME GROMMETS AND MATCHING CAPS WITH SLOT FOR WIRE PASSAGE. 1. PRODUCT: SUBJECT TO COMPLIANCE WITH REQUIREMENTS, PROVIDE "SG SERIES" BY DOUG MOCKETT & COMPANY, INC. 2. EXPOSED HARDWARE FINISHES: FOR EXPOSED HARDWARE, PROVIDE FINISH THAT COMPLIES NTH BHMA A156.18 FOR BHMA FINISH NUMBER INDICATING SATIN CHROMIUM PLATED: BHMA 626 FOR BRASS OR BRONZE BASE, BHMA 652 FOR STEEL BASE. 1.4 CABINET HARDWARE A. GENERAL: PROVIDE CABINET HARDWARE AND ACCESSORY MATERIALS ASSOCIATED WITH ARCHITECTURAL CABINETS, B. BUTT HINGES: 2- 314 -INCH (70-MM), 5- KNUCKLE STEEL HINGES MADE FROM 0.095 -INCH- (2.4-MM-) THICK METAL, AND AS FOLLOWS: 1. SEMI - CONCEALED HINGES FOR OVERLAY DOORS: BFIMA A156.9,1301521. C. FRAMELESS CONCEALED HINGES (EUROPEAN TYPE): BHMAA156.9, B01602,135 DEGREES OF OPENING, HINGES SHALL BE CAM ADJUSTABLE FOR ALIGNMENT. D. BACK - MOUNTED PULLS: BHMA A156.9, B02011. SATIN CHROME FINISH. E. WIRE PULLS: BACK MOUNTED, SOLID METAL 4 INCHES LONG, 5116 INCH IN DIAMETER. F. CATCHES: MAGNETIC CATCHES, BHMA A156.9, B03141. G. ADJUSTABLE SHELF STANDARDS AND SUPPORTS: BHMA A156.9, B04071; WITH SHELF RESTS, B04081 BHMA 0156.9, 604102; WITH SHELF BRACKETS, B04112. H. SHELF RESTS: BHMA Al 56.9, B04013; METAL. I. DRAWER SLIDES: BHMA A156.9, B05091. 1. HEAVY DUTY (GRADE 1 HD -100 AND GRADE 1FID -200): SIDE MOUNTED; FULL - EXTENSION TYPE; ZINC - PLATED STEEL BALL- BEARING SLIDES. 2. BOX DRAWER SLIDES: GRADE 1 HD -100; FOR DRAWERS NOT MORE THAN 6 INCHES (150 MM) HIGH AND 24 INCHES (600 MM) WIDE. 3. FILE DRAWER SLIDES: GRADE 1HD -200; FOR DRAWERS MORE THAN 13 INCHES (150 MM) HIGH OR24INCHES (600 MM) WIDE. 4. PENCIL DRAWER SLIDES: GRADE 1; FOR DRAWERS NOT MORE THAN 3 INCHES (75 MM) HIGH AND 24 INCHES (600 MM) WIDE. J. DOOR LOCKS: BHMAA156.11, E07121. K. DRAWER LOCKS: BHMA Al56.11, E07041. L. GROMMETS FOR CABLE PASSAGE THROUGH COUNTERTOPS: 2 - INCH OD, CHROME GROMMETS AND MATCHING CAPS WITH SLOT FOR WIRE PASSAGE. 1. PRODUCT: SUBJECT TO COMPLIANCE WTH REQUIREMENTS, PROVIDE "SG SERIES" BY DOUG MOCKETT & COMPANY, INC. 2. EXPOSED HARDWARE FINISHES: FOR EXPOSED HARDWARE, PROVIDE FINISH THAT COMPLIES NTH BHMA A156.18 FOR BHMA FINISH NUMBER INDICATING SATIN CHROMIUM PLATED: BHMA 626 FOR BRASS OR BRONZE BASE; BHMA 652 FOR STEEL BASE. h r, , A R R A Y L � healthcare facilities solutions 6800 Broken Sound Boulevard NW Suite 125 Boca Raton, FL 33487 t: 561.995.1700 f: 561.995.1701 www.arrayhfs.com SEAL: MARK D. TAUDIEN CONSULTANTS: Smith Seckman Reid, Inc. 600 West Hillsboro Blvd., Suite 300 Deerfield Beach, FL 33441 firm license number AA26000880 AR001 1821 OWNER: BAPTIST HEALTH SOUTH FLORIDA HOSPITAL: SOUTH MIAMI END OF SECTION 064023 Ihi; rJocurneiit n; a ell Ohi Protected instrui lien cl uervre, property of BRAY and licensed for use in the Utlr_d project only. ReProdui_tion or use of !his rlocurnont without written Permission of ARRAY is illeyfud and swill be prosecuted under the luw. (C)COPYRIGHT - 2012 ARRAY HFS w 4 HOSPITAL 1.5 CABINET HARDWARE AND ACCESSORY MATERIALS A. GENERAL: PROVIDE CABINET HARDWARE AND ACCESSORY MATERIALS FOR CABINETS AS INDICATED AND TO COMPLY WITH ADA'. HARDWARE ITEMS NOT SHOWN BUT REQUIRED FOR FUNCTION INDICATED SHALL BE FURNISHED IN THE SAME FINISH AND QUALITY 1. PULLS: IVES NO. 530. COLOR SELECTED BY INTERIOR DESIGNER. 2. FLUSH - MOUNTED SHELF SUPPORT: KV NO. 255 SHELF STANDARDS WITH KV NO. 239 SHELF SUPPORT CLIPS, BRIGHT PROJECT: ZINC PLATED STEEL UNLESS OTHERWISE INDICATED. 3. CABINET CATCHES SINGLE MAGNETIC TYPE: STANLEY 46 U PLAIN FINISHED ALUMINUM. S I Desk Coffee h 0 4. DRAWER SLIDES: 0 p a. SHALLOW DRAWERS (6" DEEP MAXIMUM): KV1300, SIDE MOUNTING, BALL - BEARING NYLON ROLLERS. b. HEAVY DUTY DRAWERS: KV1429, RATED 100 LBS., FULL EXTENSION. 5. HINGES: a CONCEALED HINGES FOR OVERLAY DOORS: STANLEY 1560 SERIES, SIZE AS REQUIRED. b. LOCKS: CORBIN CABINET LOCK NO. 02065. 1.6 PLASTIC- LAMINATE CABINETS A. GRADE: PREMIUM. ADDRESS: B. AW TYPE OF CABINET CONSTRUCTION: FLUSH OVERLAY C. REVEAL DIMENSION: 112 INCH (13 MM). 6200 Southwest 73rd Street D. LAMINATE CLADDING FOR EXPOSED SURFACES: HIGH - PRESSURE DECORATIVE LAMINATE COMPLYING WITH THE FOLLOWING REQUIREMENTS: South Miami, FL 33143 1. HORIZONTAL SURFACES OTHER THAN TOPS: GRADE FIGS. 2. POSTFORMED SURFACES: GRADE HGP. 3. VERTICAL SURFACES: GRADE FIGS. 4. EDGES: GRADE FIGS EDGE BANDING, 0.12 INCH (3 MM) THICK, MATCHING LAMINATE IN COLOR, PATTERN, AND FINISH. E. MATERIALS FOR SEMIEXPOSED SURFACES: 1. SURFACES OTHER THAN DRAWER BODIES: HIGH - PRESSURE DECORATIVE LAMINATE, GRADE VGS. 2. EDGES OF PLASTIC- LAMINATE SHELVES: PVC EDGE BANDING, 0.12 INCH (3 MM) THICK, MATCHING LAMINATE IN COLOR, PATTERN, AND FINISH. 3. FOR SEMIEXPOSED BACKS OF PANELS WITH EXPOSED PLASTIC- LAMINATE SURFACES, PROVIDE SURFACE OF HIGH- PRESSURE DECORATIVE LAMINATE, GRADE VGS. N0. DESCRIPTION DATE 4. DRAWER SIDES AND BACKS: THERMOSET DECORATIVE PANELS. 5. DRAWER BOTTOMS: THERMOSET DECORATIVE PANELS. REVISIONSfISSUES F. CONCEALED BACKS OF PANELS NTH EXPOSED PLASTIC LAMINATE SURFACES: HIGH - PRESSURE DECORATIVE LAMINATE, - - - - - -- - GRADE BKL. SHEET TITLE: G. COLORS, PATTERNS, AND FINISHES: PROVIDE MATERIALS AND PRODUCTS THAT RESULT IN COLORS AND TEXTURES OF EXPOSED LAMINATE SURFACES COMPLYING WITH THE FOLLOWING REQUIREMENTS: ] a° `q1; 'y'� Al API 1. AS INDICATED BY LAMINATE MANUFACTURER'S DESIGNATIONS. i',1 1�9, ;#")IN G TDr P` Z AS SELECTED BY ARCHITECT FROM LAMINATE MANUFACTURER'S FULL RANGE OF PRODUCTS. SPECIFICATIONS 3. SEE FINISH DRAWINGS FOR MANUFACTURER, STYLE AND COLOR. ,I.� ft- MIAI..SF -C I)PI H. PROVIDE DUST PANELS OF 114 -INCH (6.4 -MM) PLYWOOD OR TEMPERED HARDBOARD ABOVE COMPARTMENTS AND DRAWERS, UNLESS LOCATED DIRECTLY UNDER TOPS. 1.7 PLASTIC - LAMINATE COUNTERTOPS 1vr =r' `3Y A. GRADE: PREMIUM. B. HIGH - PRESSURE DECORATIVE LAMINATE GRADE: HGS, C. COLORS, PATTERNS, AND FINISHES: PROVIDE MATERIALS AND PRODUCTS THAT RESULT IN COLORS AND TEXTURES OF EXPOSED LAMINATE SURFACES COMPLYING WITH THE FOLLOWING REQUIREMENTS: 1. SEE FINISH DRAWINGS FOR MANUFACTURER, STYLE AND COLOR. DRAWN: FL CHECKED: MDT 1.8 SOLID- SURFACING - MATERIAL COUNTERTOPS CON/REF No. 00000 A. GRADE: PREMIUM. B. SOLID - SURFACING - MATERIAL THICKNESS: 1/2 INCH (13 MM) PROJECT No. 3601 C- COLORS, PATTERNS, AND FINISHES: PROVIDE MATERIALS AND PRODUCTS THAT RESULT IN COLORS OF SOLID - SURFACING MATERIAL COMPLYING NTH THE FOLLOWING REQUIREMENTS: DATE: 07/30/2012 SCALE: 12" = V -0" 1. SEE FINISH DRAWINGS FOR MANUFACTURER, STYLE AND COLOR. D. CORE MATERIAL AT NURSING STATION: MFDIUM- DENSITY FIBERBOARD MADE WITH EXTERIOR GLUE. E. RECEPTION AREAS /NURSES STATION: VERTICAL SURFACES OF 112 INCH THICK SOLID POLYMER MATERIAL AND HORIZONTAL SHEET NO. SURFACES OF 112 INCH THICK SOLID POLYMER MATERIAL, ADHESIVELY JOINED WITH INCONSPICUOUS SEAMS, HAVING EDGE DETAILS AS INDICATED ON THE DRAWINGS. 1.9 INSTALLATION A802 A. INSTALL WOODWORK LEVEL, PLUMB, TRUE, AND STRAIGHT. SHIM AS REQUIRED WITH CONCEALED SHIMS. INSTALL LEVEL AND PLUMB (INCLUDING TOPS) TO A TOLERANCE OF 118 INCH IN 96 INCHES (3 MM IN 2400 MM). B. SCRIBE AND CUT WOODWORK TO FIT ADJOINING WORK, REFINISH CUT SURFACES, AND REPAIR DAMAGED FINISH AT CUTS, END OF SECTION 064023 Ihi; rJocurneiit n; a ell Ohi Protected instrui lien cl uervre, property of BRAY and licensed for use in the Utlr_d project only. ReProdui_tion or use of !his rlocurnont without written Permission of ARRAY is illeyfud and swill be prosecuted under the luw. (C)COPYRIGHT - 2012 ARRAY HFS w 4