12-938-002SOLID CONCRETE WALL CONSTRUCTION
0
THROUGH - PENETRATION FIRESTOP SYSTEMS
SYSTEM NO .0 -AJ -1064
APRIL 17, 2006
F RATINGS 2, 3 & 4 HR (SEE ITEM 4 )
T RATING 0 HR
W Rating -CLASS 1 (See ITEMS 2 AND 4)
SECTION A -A
1. FLOOR OR WALL ASSEMBLY - REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100 -150 PCF
(1600 -2400 KG /CU METER)) CONCRETE AS SPECIFIED IN THE TABLE IN ITEM 4 BELOW. FLOOR MAY
ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED HOLLOW -CORE PRECAST CONCRETE UNITS*. WALL
MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF SLEEVED
OPENING IS 32 IN. (813 MM). MAX DIAM OF SLEEVED OPENING IN FLOORS CONSTRUCTED OF
HOLLOW -CORE PRECAST CONCRETE UNITS IS 7 IN. (178 MM).
SEE CONCRETE BLOCKS (CAZT) AND PRECAST CONCRETE UNITS (CFTV) CATEGORIES IN THE FIRE
RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
2. STEEL SLEEVE (OPTIONAL) -- NOM 32 IN. (813 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER)
STEEL PIPE SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH BOTH
SURFACES OF FLOOR OR WALL. AS AN OPTION, SLEEVE MAY EXTEND MAX 2 IN. ABOVE TOP SURFACE
OF FLOOR OR BEYOND ONE OR BOTH SURFACES OF WALL. STEEL SLEEVE MAY BE USED IN 2 AND 3
HR F RATED SYSTEMS ONLY. W RATING APPLIES ONLY WHEN STEEL SLEEVE IS USED.
3. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER
CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. PIPE, CONDUIT OR TUBING TO BE
RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. SEE TABLE IN ITEM 4 FOR
SIZES OF PENETRANTS A, B, D AND E THAT MAY BE USED. SEE ITEM 3C BELOW FOR SIZE OF
CONDUIT THAT MAY BE USED. THE ANNULAR SPACE SHALL BE AS SPECIFIED IN TABLE IN ITEM 4
BELOW. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE - SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE - CAST OR DUCTILE IRON PIPE.
C. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR NOM
6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT.
D. COPPER TUBING - TYPE L (OR HEAVIER) COPPER TUBING.
E. COPPER PIPE - REGULAR (OR HEAVIER) COPPER PIPE.
4. FIRESTOP SYSTEM - THE F RATING OF THE SYSTEM IS DEPENDENT UPON THE TYPE OF
CONCRETE, THICKNESS OF CONCRETE, ANNULAR SPACE, FILL AND PACKING MATERIAL THICKNESS,
PACKING MATERIAL DENSITY AND PENETRANT SIZE AS SHOWN IN THE TABLE BELOW:
F
MIN
ANNULAR
MIN
MIN
MIN
PENETRANT
RATING
THICK
SPACE
THICK
DENSITY
THICK
SIZE,
HR
CONCRETE
IN. (MM)
PACKING
PACKING
FILL
IN. (MM)
DISCONNECT
IN. (MM)
DIVISION
MTL
MTL PCF
MTL,
DIAM
F/A
FIRE ALARM
FBO
IN. (MM)
(KG /CU
IN. (MM)
(OR SMALLER)
FUSE
G
GROUND
HP
METER)
NOTES:
1. ONE -. L CONDUCTOR FOR EACH - CONDUCTOR, • •
INDICATED, c INCLUDED -. OTHERWISE NOTED.
2.ONE INSULATED GREEN GROUNDING • r i- ALTHOUGH NOT r r SHALL
D, E (COPPER)
A, B (STEEL IRON)
2
4 -1/2
1/2 - 3 -3/8
3-1/2
6 (96)
1/2 (13)
4 (102)
16 (406)
(114)
(13 TO 86)
(89)
USING CABLE TIES AT THE PANELBOARD AND ALL JUNCTION BOXES, PULL BOXES 1
AND ALL OTHER LOCATIONS WHERE TERMINATIONS, i i OR SPLICES
2
5 -1/2
0- 1 -7/8
5
4 (64)
1/2 (13)
4 (102)
16 (406)
(140)
(0 TO 48)
(127)
3
4 -1/2
- 3 -3/8
3 -1/2
6 (96)
1/2 (13)
4 (102)
8 (203)
(114)
11/2
(13 TO 86)
(89)
3
4 -1/2
0- 2 -1/8
4 -1/4
4 (64)
1/4 (6)
6 (152)
30 (762)
(114)
(0 TO 54)
(108)
4
5 -1/2
0- 1 -7/8
5
4 (64)
1/4 (13)
4 (102)
8 (203)
(140)
(0 TO 48)
(127)
A. PACKING MATERIAL - MIN 3 -1/2, 4 -1/4 OR 5 IN. (89,108 OR 127 MM) THICKNESS OF MIN 4.0 OR
6.0 PCF (64 OR 96 KG /CU METER) MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING
AS A PERMANENT FORM AS SPECIFIED IN THE TABLE ABOVE. PACKING MATERIAL TO BE RECESSED
FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE
THE REQUIRED THICKNESS OF FILL MBA CARULK�
B. FILL, VOID OR CAVITY MATERIAL * - MIN * OR 1/2 IN. (6 OR 13 MM) THICKNESS OF FILL
MATERIAL AS SPECIFIED IN THE TABLE ABOVE APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP
SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL. AT THE POINT CONTACT LOCATION BETWEEN
PIPE AND CONCRETE OR SLEEVE , A MIN 1/2 IN. (13 MM) DIAM BEAD OF FILL MATERIAL SHALL BE
APPLIED .
TREMCO INC - FYRE -SIL (FLOORS OR WALLS) AND FYRE -SIL S.L. (FLOORS)
*BEARING THE UL CLASSIFICATION MARK
ABBREVIATIONS
SYMBOL DESCRIPTION
ABC
ABOVE COUNTER
ACLG
ABOVE FINISHED CEILING
AFF
ABOVE FINISHED FLOOR
AFG
ABOVE FINISHED GRADE
BKR
BREAKER
CB
CIRCUIT BREAKER
cd
CANDELA
CKT
CIRCUIT
CL
CENTER LINE
CLG
CEILING MOUNTED DEVICE
DISC
DISCONNECT
DIV
DIVISION
EX
EXISTING
F
FRAME
F/A
FIRE ALARM
FBO
FURNISHED BY OTHERS
FLA
FULL LOAD AMPS
FU
FUSE
G
GROUND
HP
HORSE POWER
ABBREVIATIONS
SYMBOL DESCRIPTION
K
KILO
MCB
MAIN CIRCUIT BREAKER
MLO
MAIN LUGS ONLY
NEC
NATIONAL ELECTRIC CODE
NIC
NOT IN CONTRACT
OC
OVER CURRENT
OCP
OVER CURRENT PROTECTION
P
POLE
PH
PHASE
SMH
SPECIAL MOUNTING HEIGHT
TV
TELEVISION
TYP
TYPICAL
UH
UNIT HEATER
UG
UNDER GROUND ELECTRICAL
LION
UNLESS OTHERWISE NOTED
V
VOLT(S)
VA
VOLT - AMPS)
W
WATT(S), WIRE, WALL TELEPHONE OUTLET
WP
WEATHERPROOF DEVICE, NEMA 313
XFMR
TRANSFORMER
INFECTION CONTROL MEASURES:
A. INFECTION OBTAIN
ON CONTROL RISK ASSESSMENT T EP T
S MEN (ICRA) FOR THIS
PROJECT. CONTRACTOR SHALL REVIEW THE REQUIREMEJTS IN
THE REPORT AND PERFORM ALL WORK IN ACCORDANCE WITH
THOSE REQUIREMENTS. CONTRACTOR SHALL STRICTLY ADHERE
TO THE LIMITS OF THE CONSTRUCTION AREA, AND WPERE
PHASING APPLIES SHALL ADHERE TO THE PHASING PUN.
ANY WORK OUTSIDE THE CONSTRUCTION AREA SHALL 3E
COORDINATED WITH THE OWNER AND PERFORMED IN ACCORDANCE
WITH THE ICRA REPORT, UNDER THE SUPERVISION OF -HE
OWNER'S REPRESENTATIVE OR OTHER DESIGNATED ICR,
COMMITTEE OFFICER.
B- TO THE EXTENT THAT IT IS REQUIRED BY THE ICRA, -HE
CONTRACTOR SHALL ENDEAVOR TO MAINTAIN EXISTING LEVELS
OF INDOOR AIR QUALITY IN AREAS SURROUNDING AND ADJACENT
TO THE CONSTRUCTION WORK ZONE, AND ELSEWHEREN THE
FACILITY. IT SHOULD BE ANTICIPATED THAT THE ICRi
REPORT WILL REQUIRE MEASURES TO THIS EFFECT IRLUDING
ERECTION OF CONSTRUCTION ZONE BARRIERS AND PRVISION
OF NEGATIVE AIR PRESSURE IN THE CONSTRUCTION ZNE
RELATIVE TO OTHER AREAS OF THE FACILITY.
SCOPE SCOPE (F WORK
LEGEND
SYMBOL DESCRIPTION MOUNTING -
HEitaHT
LIGHTING FIXTURE SCHEDULE
TYPE
MANUF.
CATALOG N0.
pp%d_
NON-FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING/POLES)
INPUT
WATTAGE
MOUNTING
FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING/POLES)
E3.1
ELECTRICAL RISER
E4.1
PANEL SCHEDULES
FACTORY i CONTROLLER OR EQUIPMENT
.
EMERGENCY BATTERY
MOTOR CONNECTION
BEGHELLI
BS100T5- 4- SA- 228W -FP -CH
JUNCT ION :•
48W
-A BOAR• - FLUSH MOUNTED
CHAIN HUNG VAPOR TIGHT FLUORESCENT
PANELBOARD - SURFACE MOUNTED
Co r CONDUIT
CONDUIT • r IN FLOOR OR BELOW -. r
HOMER HOMERUN TO -. :•A.r -NUMBER OF CONDUCTORS
•
CONDUIT NOTED OTHERWISE
NOTES:
1. ONE -. L CONDUCTOR FOR EACH - CONDUCTOR, • •
INDICATED, c INCLUDED -. OTHERWISE NOTED.
2.ONE INSULATED GREEN GROUNDING • r i- ALTHOUGH NOT r r SHALL
BE INCLUDED IN EACH RACEWAY UNLESS OTHERWISE NOTED.
3. HOMERUNS TO PANELBOARDS SHALL HAVE A MAXIMUM OF THREE (3) PHASE
Uj
CONDUCTORS • NE PER PHASE) PLUS THREE (3) NEUTRAL CONDUCTORS AND
ONE GROUND CONDUCTOR IN EACH • r
4. MULTI-WIRE BRANCH CIRCUITS THAT SHARE A COMMON NEUTRAL SHALL NOT BE
PERMITTED FOR INDIVIDUAL LINE-TO-NEUTRAL LOADS.
5. EACH CIRCUIT (PHASE AND NEUTRAL CONDUCTORS) SHALL BE GROUPED TOGETHER
USING CABLE TIES AT THE PANELBOARD AND ALL JUNCTION BOXES, PULL BOXES 1
AND ALL OTHER LOCATIONS WHERE TERMINATIONS, i i OR SPLICES
.- MADE.
6.ALL CONDUCTORS • OTHERWISE • 1
ALL WORK COMPLY •!: EDITION OF
LIGHTING FIXTURE SCHEDULE
TYPE
MANUF.
CATALOG N0.
LAMPS
VOLTS
INPUT
WATTAGE
MOUNTING
REMARKS
* COORDINATE VOLTAGE WITH CIRCUIT FOR LIGHT
GENERAL LIGHTING FIXTURE NOTES:
1. CONTRACTOR MUST QUOTE SPECIFIED LIGHTING FIXTURES AS BASE BID. ANY ALTERNATE LIGHTING
PRODUCTS MUST BE SHOWN AS AN EXCEPTION TO BASE BID, AND MUST BE ACCOMPANIED BY UNIT
PRICES AND TOTAL DOLLAR DEDUCT FROM THE BASE BID.
2. ANY PROPOSED ALTERNATES SHALL MATCH SPECIFIED LIGHTING FIXTURE CHARACTERISTICS AS FOLLOWS:
a. ALL RATINGS INCLUDING, BUT NOT LIMITED TO, WATTAGE, FIRE RATINGS, AND SPECIAL LOCATION
RATINGS SUCH AS DAMP OR WET LABELS, HAZARDOUS LOCATION, CLEAN ROOM, TAMPER PROOF, ETC.
b. PHYSICAL SIZE AND DIMENSION
c. CONSTRUCTION
d. MATERIAL
e. LAMP AND BALLAST TYPE
f. LENS AND REFLECTOR TYPE
g. PAINT APPLICATION PROCESS
h. PHOTOMETRIC CHARACTERISTICS
3. PROVIDE IN -LINE FUSING FOR ALL FLUORESCENT FIXTURES ON THE LIFE SAFETY AND CRITICAL BRANCHES.
THE OF PROJECT • PRIORITY ONE • LOADS ONTO ONE
NON-LOAD SHEDDABLE ORDER TO C0501LIDATE THE QUANTITY OF PRIORITY ONE EQUIPMENT
BRANCH
AT COMPLETION OF RE- CIRCUITING, ALL PRIaTY ONE EQUIPMENT LOADS (GENERATOR ACCESSORIES,
MED GAS EQUIPMENT, ETC.) WILL BE FED FRIC A SINGLE PRIORTY ONE EQUIPMENT ATS AND THE
REMAINING EQUIPMENT BRANCH ATS'S WILL AVE LOAD SHED FUNCTIONALITY ENABLED AND BE
RE- PROGRAMMED TO A LOWER PRIORITY LEVI.
IN ADDITION, THIS PROJECT WILL MAKE UPG[DES TO THE EMERGENCY LIGHTING WITHIN THE MAIN
CENTRAL ENERGY PLANT.
ELECTRICAL DRAWING INDEX
NO. SHEET TITLE
EO.0
GARDCO
121- EM- WT- 50LA- CW- UNIV- BLP -WS
LED
277
47.1W
WALL
EXTERIOR LED WALL SCONCE WITH
E3.1
ELECTRICAL RISER
DIAGRAM
E4.1
PANEL SCHEDULES
& COORDINATION STUDIES
E4.2
EMERGENCY BATTERY
®
BEGHELLI
BS100T5- 4- SA- 228W -FP -CH
2 -28WT5
48W
SUSPENDED
CHAIN HUNG VAPOR TIGHT FLUORESCENT
WITH INTEGRAL BATTERY PACK
* COORDINATE VOLTAGE WITH CIRCUIT FOR LIGHT
GENERAL LIGHTING FIXTURE NOTES:
1. CONTRACTOR MUST QUOTE SPECIFIED LIGHTING FIXTURES AS BASE BID. ANY ALTERNATE LIGHTING
PRODUCTS MUST BE SHOWN AS AN EXCEPTION TO BASE BID, AND MUST BE ACCOMPANIED BY UNIT
PRICES AND TOTAL DOLLAR DEDUCT FROM THE BASE BID.
2. ANY PROPOSED ALTERNATES SHALL MATCH SPECIFIED LIGHTING FIXTURE CHARACTERISTICS AS FOLLOWS:
a. ALL RATINGS INCLUDING, BUT NOT LIMITED TO, WATTAGE, FIRE RATINGS, AND SPECIAL LOCATION
RATINGS SUCH AS DAMP OR WET LABELS, HAZARDOUS LOCATION, CLEAN ROOM, TAMPER PROOF, ETC.
b. PHYSICAL SIZE AND DIMENSION
c. CONSTRUCTION
d. MATERIAL
e. LAMP AND BALLAST TYPE
f. LENS AND REFLECTOR TYPE
g. PAINT APPLICATION PROCESS
h. PHOTOMETRIC CHARACTERISTICS
3. PROVIDE IN -LINE FUSING FOR ALL FLUORESCENT FIXTURES ON THE LIFE SAFETY AND CRITICAL BRANCHES.
THE OF PROJECT • PRIORITY ONE • LOADS ONTO ONE
NON-LOAD SHEDDABLE ORDER TO C0501LIDATE THE QUANTITY OF PRIORITY ONE EQUIPMENT
BRANCH
AT COMPLETION OF RE- CIRCUITING, ALL PRIaTY ONE EQUIPMENT LOADS (GENERATOR ACCESSORIES,
MED GAS EQUIPMENT, ETC.) WILL BE FED FRIC A SINGLE PRIORTY ONE EQUIPMENT ATS AND THE
REMAINING EQUIPMENT BRANCH ATS'S WILL AVE LOAD SHED FUNCTIONALITY ENABLED AND BE
RE- PROGRAMMED TO A LOWER PRIORITY LEVI.
IN ADDITION, THIS PROJECT WILL MAKE UPG[DES TO THE EMERGENCY LIGHTING WITHIN THE MAIN
CENTRAL ENERGY PLANT.
ELECTRICAL DRAWING INDEX
NO. SHEET TITLE
EO.0
ELECTRICAL LEGEND, ABBREVIATIONS & DRAWING INDEX
E2.1
CEP FIRST FLOOR
PLAN - NEW WORK - LIGHTING & POWER
E2.2
CEP ROOF PLAN -
DEMO & NEW WORK - ELECTRICAL
E3.1
ELECTRICAL RISER
DIAGRAM
E4.1
PANEL SCHEDULES
& COORDINATION STUDIES
E4.2
ELECTRICAL FAULT
STUDY
E5.1
ELECTRICAL SPECIFICATIONS
I.
mi h
SS e0 an
el,Tnc.
600 West Hillsboro, Suite 300
Deerfield Beach, FL 33441
(954) 421 -1260
ry " -FAX: (954) 421 -1466
www.ssr - inc.com
Firm Certification - EB- 0000857
John E. Moulder PE - 33200
Michael A Steward PE - 65701
SSR JOB # 1232030.0
DRAWN
CHECKED
DATE •8
REVISED
' 5
. . . . , •
r r__.
LIJ
i
0
LU CO
.
0
•
•
Uj
DRAWN
CHECKED
DATE •8
REVISED
' 5
. . . . , •
r r__.