12-938-002SOLID CONCRETE WALL CONSTRUCTION 0 THROUGH - PENETRATION FIRESTOP SYSTEMS SYSTEM NO .0 -AJ -1064 APRIL 17, 2006 F RATINGS 2, 3 & 4 HR (SEE ITEM 4 ) T RATING 0 HR W Rating -CLASS 1 (See ITEMS 2 AND 4) SECTION A -A 1. FLOOR OR WALL ASSEMBLY - REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100 -150 PCF (1600 -2400 KG /CU METER)) CONCRETE AS SPECIFIED IN THE TABLE IN ITEM 4 BELOW. FLOOR MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED HOLLOW -CORE PRECAST CONCRETE UNITS*. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF SLEEVED OPENING IS 32 IN. (813 MM). MAX DIAM OF SLEEVED OPENING IN FLOORS CONSTRUCTED OF HOLLOW -CORE PRECAST CONCRETE UNITS IS 7 IN. (178 MM). SEE CONCRETE BLOCKS (CAZT) AND PRECAST CONCRETE UNITS (CFTV) CATEGORIES IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS. 2. STEEL SLEEVE (OPTIONAL) -- NOM 32 IN. (813 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE SLEEVE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH BOTH SURFACES OF FLOOR OR WALL. AS AN OPTION, SLEEVE MAY EXTEND MAX 2 IN. ABOVE TOP SURFACE OF FLOOR OR BEYOND ONE OR BOTH SURFACES OF WALL. STEEL SLEEVE MAY BE USED IN 2 AND 3 HR F RATED SYSTEMS ONLY. W RATING APPLIES ONLY WHEN STEEL SLEEVE IS USED. 3. THROUGH PENETRANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. SEE TABLE IN ITEM 4 FOR SIZES OF PENETRANTS A, B, D AND E THAT MAY BE USED. SEE ITEM 3C BELOW FOR SIZE OF CONDUIT THAT MAY BE USED. THE ANNULAR SPACE SHALL BE AS SPECIFIED IN TABLE IN ITEM 4 BELOW. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY BE USED: A. STEEL PIPE - SCHEDULE 10 (OR HEAVIER) STEEL PIPE. B. IRON PIPE - CAST OR DUCTILE IRON PIPE. C. CONDUIT - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR NOM 6 IN. (152 MM) DIAM (OR SMALLER) STEEL CONDUIT. D. COPPER TUBING - TYPE L (OR HEAVIER) COPPER TUBING. E. COPPER PIPE - REGULAR (OR HEAVIER) COPPER PIPE. 4. FIRESTOP SYSTEM - THE F RATING OF THE SYSTEM IS DEPENDENT UPON THE TYPE OF CONCRETE, THICKNESS OF CONCRETE, ANNULAR SPACE, FILL AND PACKING MATERIAL THICKNESS, PACKING MATERIAL DENSITY AND PENETRANT SIZE AS SHOWN IN THE TABLE BELOW: F MIN ANNULAR MIN MIN MIN PENETRANT RATING THICK SPACE THICK DENSITY THICK SIZE, HR CONCRETE IN. (MM) PACKING PACKING FILL IN. (MM) DISCONNECT IN. (MM) DIVISION MTL MTL PCF MTL, DIAM F/A FIRE ALARM FBO IN. (MM) (KG /CU IN. (MM) (OR SMALLER) FUSE G GROUND HP METER) NOTES: 1. ONE -. L CONDUCTOR FOR EACH - CONDUCTOR, • • INDICATED, c INCLUDED -. OTHERWISE NOTED. 2.ONE INSULATED GREEN GROUNDING • r i- ALTHOUGH NOT r r SHALL D, E (COPPER) A, B (STEEL IRON) 2 4 -1/2 1/2 - 3 -3/8 3-1/2 6 (96) 1/2 (13) 4 (102) 16 (406) (114) (13 TO 86) (89) USING CABLE TIES AT THE PANELBOARD AND ALL JUNCTION BOXES, PULL BOXES 1 AND ALL OTHER LOCATIONS WHERE TERMINATIONS, i i OR SPLICES 2 5 -1/2 0- 1 -7/8 5 4 (64) 1/2 (13) 4 (102) 16 (406) (140) (0 TO 48) (127) 3 4 -1/2 - 3 -3/8 3 -1/2 6 (96) 1/2 (13) 4 (102) 8 (203) (114) 11/2 (13 TO 86) (89) 3 4 -1/2 0- 2 -1/8 4 -1/4 4 (64) 1/4 (6) 6 (152) 30 (762) (114) (0 TO 54) (108) 4 5 -1/2 0- 1 -7/8 5 4 (64) 1/4 (13) 4 (102) 8 (203) (140) (0 TO 48) (127) A. PACKING MATERIAL - MIN 3 -1/2, 4 -1/4 OR 5 IN. (89,108 OR 127 MM) THICKNESS OF MIN 4.0 OR 6.0 PCF (64 OR 96 KG /CU METER) MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM AS SPECIFIED IN THE TABLE ABOVE. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MBA CARULK� B. FILL, VOID OR CAVITY MATERIAL * - MIN * OR 1/2 IN. (6 OR 13 MM) THICKNESS OF FILL MATERIAL AS SPECIFIED IN THE TABLE ABOVE APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL. AT THE POINT CONTACT LOCATION BETWEEN PIPE AND CONCRETE OR SLEEVE , A MIN 1/2 IN. (13 MM) DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED . TREMCO INC - FYRE -SIL (FLOORS OR WALLS) AND FYRE -SIL S.L. (FLOORS) *BEARING THE UL CLASSIFICATION MARK ABBREVIATIONS SYMBOL DESCRIPTION ABC ABOVE COUNTER ACLG ABOVE FINISHED CEILING AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE BKR BREAKER CB CIRCUIT BREAKER cd CANDELA CKT CIRCUIT CL CENTER LINE CLG CEILING MOUNTED DEVICE DISC DISCONNECT DIV DIVISION EX EXISTING F FRAME F/A FIRE ALARM FBO FURNISHED BY OTHERS FLA FULL LOAD AMPS FU FUSE G GROUND HP HORSE POWER ABBREVIATIONS SYMBOL DESCRIPTION K KILO MCB MAIN CIRCUIT BREAKER MLO MAIN LUGS ONLY NEC NATIONAL ELECTRIC CODE NIC NOT IN CONTRACT OC OVER CURRENT OCP OVER CURRENT PROTECTION P POLE PH PHASE SMH SPECIAL MOUNTING HEIGHT TV TELEVISION TYP TYPICAL UH UNIT HEATER UG UNDER GROUND ELECTRICAL LION UNLESS OTHERWISE NOTED V VOLT(S) VA VOLT - AMPS) W WATT(S), WIRE, WALL TELEPHONE OUTLET WP WEATHERPROOF DEVICE, NEMA 313 XFMR TRANSFORMER INFECTION CONTROL MEASURES: A. INFECTION OBTAIN ON CONTROL RISK ASSESSMENT T EP T S MEN (ICRA) FOR THIS PROJECT. CONTRACTOR SHALL REVIEW THE REQUIREMEJTS IN THE REPORT AND PERFORM ALL WORK IN ACCORDANCE WITH THOSE REQUIREMENTS. CONTRACTOR SHALL STRICTLY ADHERE TO THE LIMITS OF THE CONSTRUCTION AREA, AND WPERE PHASING APPLIES SHALL ADHERE TO THE PHASING PUN. ANY WORK OUTSIDE THE CONSTRUCTION AREA SHALL 3E COORDINATED WITH THE OWNER AND PERFORMED IN ACCORDANCE WITH THE ICRA REPORT, UNDER THE SUPERVISION OF -HE OWNER'S REPRESENTATIVE OR OTHER DESIGNATED ICR, COMMITTEE OFFICER. B- TO THE EXTENT THAT IT IS REQUIRED BY THE ICRA, -HE CONTRACTOR SHALL ENDEAVOR TO MAINTAIN EXISTING LEVELS OF INDOOR AIR QUALITY IN AREAS SURROUNDING AND ADJACENT TO THE CONSTRUCTION WORK ZONE, AND ELSEWHEREN THE FACILITY. IT SHOULD BE ANTICIPATED THAT THE ICRi REPORT WILL REQUIRE MEASURES TO THIS EFFECT IRLUDING ERECTION OF CONSTRUCTION ZONE BARRIERS AND PRVISION OF NEGATIVE AIR PRESSURE IN THE CONSTRUCTION ZNE RELATIVE TO OTHER AREAS OF THE FACILITY. SCOPE SCOPE (F WORK LEGEND SYMBOL DESCRIPTION MOUNTING - HEitaHT LIGHTING FIXTURE SCHEDULE TYPE MANUF. CATALOG N0. pp%d_ NON-FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING/POLES) INPUT WATTAGE MOUNTING FUSIBLE SAFETY SWITCH, SIZE AS NOTED (AMP RATING/POLES) E3.1 ELECTRICAL RISER E4.1 PANEL SCHEDULES FACTORY i CONTROLLER OR EQUIPMENT . EMERGENCY BATTERY MOTOR CONNECTION BEGHELLI BS100T5- 4- SA- 228W -FP -CH JUNCT ION :• 48W -A BOAR• - FLUSH MOUNTED CHAIN HUNG VAPOR TIGHT FLUORESCENT PANELBOARD - SURFACE MOUNTED Co r CONDUIT CONDUIT • r IN FLOOR OR BELOW -. r HOMER HOMERUN TO -. :•A.r -NUMBER OF CONDUCTORS • CONDUIT NOTED OTHERWISE NOTES: 1. ONE -. L CONDUCTOR FOR EACH - CONDUCTOR, • • INDICATED, c INCLUDED -. OTHERWISE NOTED. 2.ONE INSULATED GREEN GROUNDING • r i- ALTHOUGH NOT r r SHALL BE INCLUDED IN EACH RACEWAY UNLESS OTHERWISE NOTED. 3. HOMERUNS TO PANELBOARDS SHALL HAVE A MAXIMUM OF THREE (3) PHASE Uj CONDUCTORS • NE PER PHASE) PLUS THREE (3) NEUTRAL CONDUCTORS AND ONE GROUND CONDUCTOR IN EACH • r 4. MULTI-WIRE BRANCH CIRCUITS THAT SHARE A COMMON NEUTRAL SHALL NOT BE PERMITTED FOR INDIVIDUAL LINE-TO-NEUTRAL LOADS. 5. EACH CIRCUIT (PHASE AND NEUTRAL CONDUCTORS) SHALL BE GROUPED TOGETHER USING CABLE TIES AT THE PANELBOARD AND ALL JUNCTION BOXES, PULL BOXES 1 AND ALL OTHER LOCATIONS WHERE TERMINATIONS, i i OR SPLICES .- MADE. 6.ALL CONDUCTORS • OTHERWISE • 1 ALL WORK COMPLY •!: EDITION OF LIGHTING FIXTURE SCHEDULE TYPE MANUF. CATALOG N0. LAMPS VOLTS INPUT WATTAGE MOUNTING REMARKS * COORDINATE VOLTAGE WITH CIRCUIT FOR LIGHT GENERAL LIGHTING FIXTURE NOTES: 1. CONTRACTOR MUST QUOTE SPECIFIED LIGHTING FIXTURES AS BASE BID. ANY ALTERNATE LIGHTING PRODUCTS MUST BE SHOWN AS AN EXCEPTION TO BASE BID, AND MUST BE ACCOMPANIED BY UNIT PRICES AND TOTAL DOLLAR DEDUCT FROM THE BASE BID. 2. ANY PROPOSED ALTERNATES SHALL MATCH SPECIFIED LIGHTING FIXTURE CHARACTERISTICS AS FOLLOWS: a. ALL RATINGS INCLUDING, BUT NOT LIMITED TO, WATTAGE, FIRE RATINGS, AND SPECIAL LOCATION RATINGS SUCH AS DAMP OR WET LABELS, HAZARDOUS LOCATION, CLEAN ROOM, TAMPER PROOF, ETC. b. PHYSICAL SIZE AND DIMENSION c. CONSTRUCTION d. MATERIAL e. LAMP AND BALLAST TYPE f. LENS AND REFLECTOR TYPE g. PAINT APPLICATION PROCESS h. PHOTOMETRIC CHARACTERISTICS 3. PROVIDE IN -LINE FUSING FOR ALL FLUORESCENT FIXTURES ON THE LIFE SAFETY AND CRITICAL BRANCHES. THE OF PROJECT • PRIORITY ONE • LOADS ONTO ONE NON-LOAD SHEDDABLE ORDER TO C0501LIDATE THE QUANTITY OF PRIORITY ONE EQUIPMENT BRANCH AT COMPLETION OF RE- CIRCUITING, ALL PRIaTY ONE EQUIPMENT LOADS (GENERATOR ACCESSORIES, MED GAS EQUIPMENT, ETC.) WILL BE FED FRIC A SINGLE PRIORTY ONE EQUIPMENT ATS AND THE REMAINING EQUIPMENT BRANCH ATS'S WILL AVE LOAD SHED FUNCTIONALITY ENABLED AND BE RE- PROGRAMMED TO A LOWER PRIORITY LEVI. IN ADDITION, THIS PROJECT WILL MAKE UPG[DES TO THE EMERGENCY LIGHTING WITHIN THE MAIN CENTRAL ENERGY PLANT. ELECTRICAL DRAWING INDEX NO. SHEET TITLE EO.0 GARDCO 121- EM- WT- 50LA- CW- UNIV- BLP -WS LED 277 47.1W WALL EXTERIOR LED WALL SCONCE WITH E3.1 ELECTRICAL RISER DIAGRAM E4.1 PANEL SCHEDULES & COORDINATION STUDIES E4.2 EMERGENCY BATTERY ® BEGHELLI BS100T5- 4- SA- 228W -FP -CH 2 -28WT5 48W SUSPENDED CHAIN HUNG VAPOR TIGHT FLUORESCENT WITH INTEGRAL BATTERY PACK * COORDINATE VOLTAGE WITH CIRCUIT FOR LIGHT GENERAL LIGHTING FIXTURE NOTES: 1. CONTRACTOR MUST QUOTE SPECIFIED LIGHTING FIXTURES AS BASE BID. ANY ALTERNATE LIGHTING PRODUCTS MUST BE SHOWN AS AN EXCEPTION TO BASE BID, AND MUST BE ACCOMPANIED BY UNIT PRICES AND TOTAL DOLLAR DEDUCT FROM THE BASE BID. 2. ANY PROPOSED ALTERNATES SHALL MATCH SPECIFIED LIGHTING FIXTURE CHARACTERISTICS AS FOLLOWS: a. ALL RATINGS INCLUDING, BUT NOT LIMITED TO, WATTAGE, FIRE RATINGS, AND SPECIAL LOCATION RATINGS SUCH AS DAMP OR WET LABELS, HAZARDOUS LOCATION, CLEAN ROOM, TAMPER PROOF, ETC. b. PHYSICAL SIZE AND DIMENSION c. CONSTRUCTION d. MATERIAL e. LAMP AND BALLAST TYPE f. LENS AND REFLECTOR TYPE g. PAINT APPLICATION PROCESS h. PHOTOMETRIC CHARACTERISTICS 3. PROVIDE IN -LINE FUSING FOR ALL FLUORESCENT FIXTURES ON THE LIFE SAFETY AND CRITICAL BRANCHES. THE OF PROJECT • PRIORITY ONE • LOADS ONTO ONE NON-LOAD SHEDDABLE ORDER TO C0501LIDATE THE QUANTITY OF PRIORITY ONE EQUIPMENT BRANCH AT COMPLETION OF RE- CIRCUITING, ALL PRIaTY ONE EQUIPMENT LOADS (GENERATOR ACCESSORIES, MED GAS EQUIPMENT, ETC.) WILL BE FED FRIC A SINGLE PRIORTY ONE EQUIPMENT ATS AND THE REMAINING EQUIPMENT BRANCH ATS'S WILL AVE LOAD SHED FUNCTIONALITY ENABLED AND BE RE- PROGRAMMED TO A LOWER PRIORITY LEVI. IN ADDITION, THIS PROJECT WILL MAKE UPG[DES TO THE EMERGENCY LIGHTING WITHIN THE MAIN CENTRAL ENERGY PLANT. ELECTRICAL DRAWING INDEX NO. SHEET TITLE EO.0 ELECTRICAL LEGEND, ABBREVIATIONS & DRAWING INDEX E2.1 CEP FIRST FLOOR PLAN - NEW WORK - LIGHTING & POWER E2.2 CEP ROOF PLAN - DEMO & NEW WORK - ELECTRICAL E3.1 ELECTRICAL RISER DIAGRAM E4.1 PANEL SCHEDULES & COORDINATION STUDIES E4.2 ELECTRICAL FAULT STUDY E5.1 ELECTRICAL SPECIFICATIONS I. mi h SS e0 an el,Tnc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 ry " -FAX: (954) 421 -1466 www.ssr - inc.com Firm Certification - EB- 0000857 John E. Moulder PE - 33200 Michael A Steward PE - 65701 SSR JOB # 1232030.0 DRAWN CHECKED DATE •8 REVISED ' 5 . . . . , • r r__. LIJ i 0 LU CO . 0 • • Uj DRAWN CHECKED DATE •8 REVISED ' 5 . . . . , • r r__.