12-637R-001SCOPE of WORK
This is an existing 2 -Story Human Resources building located at South Miami
Hospital, with an existing Faraday Firewatch XVI fire alarm control panel. The
scope of this project shall be the remodeling & renovation of a portion of the 2nd
floor. Under this scope, new Fire Alarm Notification devices shall be installed.
There are existing initiating devices, and these devices (Smoke Detectors) shall
remain in the same location, and not altered. Also, there are two (2) existing Pull
Stations that shall be replaced with new devices. All new initiating devices will be
connected to and supervised by the existing fire alarm panel, which will result in
a fully functional single system for the existing facility. There shall be no other
work preformed under this scope.
The new Notification Appliances (Horn /Strobes & Strobe Lights) shall be
connected to a new Remote Power Booster that shall be located on the 1st floor
next to the existing Fire Alarm Control Panel. This new Power Booster shall be
connected to, powered & supervised by the existing Fire Alarm Control Panel per
the manufacturer's instructions & NFPA 72.
NOTE: The existing Firewatch 16 Fire Alarm Control Panel is NOT capable of
silencing the Horns, and leaving the Strobe Lights flashing. When the Silence
switch is activated, the Horns will silence, and the Strobe Lights shall turn off as
well.
The devices being installed in this project are of the same manufacturer, and are
UL /FM listed per NFPA 72 and are 100% compatible.
THIS EXISTING FIRE ALARM SYSTEM IS
CONVENTIONAL, HARDWIRED, NOT ADDRESSABLE
THIS IS AN EXISTING 'REMOTE SUPERVISING STATION
FIRE ALARM SYSTEM' REQUIRING 24 HOURS STANDBY
BATTERY CALCULATION TIME.
NOTE:
ALL CIRCUITS ARE TO BE "CLASS B"
THIS BUILDING IS FULLY SPRINKLED
THE EXISTING FIRE ALARM ZONING OF INITIATING
DEVICES SHALL NOT BE ALTERED UNDER THIS
SCOPE, AND SHALL REMAIN AS IS.
THE LISTED CABLES COMPLY WITH
NEC 760- 30(a)(1); 760- 30(b)(4);
760- 31(e); AND 760- 71(f)(i).
FIRE ALARM SYSTEM CONDUIT SHALL NOT
BE FILLED TO GREATER THAN 40% OF ITS
CAPACITY
FIRE ALARM SYSTEM IS POWER- LIMITED. ALL EQUIPMENT
IS OF THE SAME MANUFACTURER AND IS 100%
COMPATIBLE AND IS UL /FM LISTED PER N.F.P.A. 72
THERE ARE NO NEW DEVICES BEING CONNECTED UNDER THIS SCOPE
TO THE EXISTING FIRE ALARM CONTROL PANEL, THEREFORE NO STANDBY
BATTERY CALCULATIONS FOR THE EXIST FIRE ALARM PANEL ARE REQUIRED.
INSTALLING CONTRACTOR SHALL
VERIFY THAT THE
EXISTING SMOKE DETECTORS TO
REMAIN ARE
COVERED & PROTECTED DURING
THE REMODELING
FROM DEMOLITION /CONSTRUCTION DEBRIS AND DUST
PARTICLES.
FIREWATCH XVI
IF TAPE (MASKING /DUCT, ETC.)
IS USED TO COVER
& PROTECT SMOKE DETECTORS,
CONTRACTOR SHALL
VERIFY THAT NO TAPE RESIDUE
IS LEFT ON THE
SMOKE DETECTORS AFTER REMOVAL OF TAPE.
EXISTING SMOKE DETECTORS
REPLACED WITH NEW ('ETRN')
TYPICAL
SCOPE OF
WORK
2nd FLOOR FIRE ALARM
SCALE: 1/8"- 1'0"
THE INTENT IS TO SHOW THE AREA OF
WORK UNDER THIS SCOPE. IT IS NOT THE
INTENT TO SHOW THE ENTIRE FACILITY OR
THE COMPLETE FIRE ALARM SYSTEM.
NOTE:
THE RELAY USED FOR THE MAG LOCK
OVERRIDE SHALL RELEASE THE MAG LOCK
UPON ACTIVATION OF THE FIRE ALARM,
DEVICE LEGEND
SYMBOL
DESCRIPTION
MODEL #
SURFACE BACKBOX
FLUSH BACKBOX
EACP EX
EXISTING FIRE ALARM CONTROL PANEL
FIREWATCH XVI
N/A
EXISTING
RPS
NEW REMOTE POWER BOOSTER
RSE -300
SUPPLIED w/ PRODUCT
SUPPLIED w/ PRODUCT
®
SMOKE DETECTOR
2W —B
1900 BOX w/ 1 GANG RING
1900 BOX w/ 1 GANG RING
LEI
PULL STATION
10561
1900 BOX w/ 1 GANG RING
1900 BOX w/ 1 GANG RING
®
LOAD RELAY — SPST
R712 -1
SUPPLIED w/ PRODUCT
SUPPLIED w/ PRODUCT
t) The 120VAC primary power shall conform to NFPA 72
HORN /STROBE 75CD WALL MNT
ZH —MC —R
1900 DEEP BOX —NO RING
1900 DEEP BOX —NO RING
O
STROBE LIGHT 75CD WALL MNT
ZR —MC —R
1900 DEEP BOX ---NO RING
1900 DEEP BOX —NO RING
O C
STROBE LIGHT 75CD CEILING MNT
ZR —MC —CR
1900 DEEP BOX —NO RING
1900 DEEP BOX —NO RING
"N" DENOTES NEW DEVICE.
"EX" DENOTES EXISTING DEVICE.
"ETRN" DENOTES EXISTING DEVICE REPLACED WITH NEW.
111AiA�! -DARE C0UNTY FIRE DEPARTF"EN
EL 3, ; :t�l!'6 eta: A,.a"'Trrt
pis E F" k sei l A tit�l."�"%::T. -
,:s:� r.r.�
rM ALARM SYSTEM TO $T�
MSTAI. LED IN ACCor�(OANCE WITH
NFPA 72; 70;101
• � u
r • •eWr`...,,.Rww.l Wal..,�,,..
Y�
r�
•
W�
-F-IRE N11TES
WIRE LEGEND
SYMBOL
,I) The,CICr,,,alarm d;%titem IsmLI.1,1_15ted as POWER LIMITED L
DESCRIPTION
U.L. Listed forW Its Intenaed use,
CIRCUIT /FUNCTION
A
1
PAIR #18 FPL, FPLP, FPLR,
THHN
INITIATING DEVICE CIRCUIT
P
1
PAIR #14 FPL, FPLP, FPLR,
THHN
MAGNETIC DOOR LOCK RELAY CIRCUIT
SX
1
PAIR #14 FPL, FPLP, FPLR,
THHN
NAC (NOTIFICATION APPLIANCE CIRCUIT ( "x" DENOTES CIRCUIT NUMBER)
IT IS RECOMMENDED THAT YOU DO NOT
SUBSITUTE FOR THE SPECIFIED CABLES ABOVE, AS THEY ARE FACTORY APPROVED TO INSURE
PROPER OPERATION OF THE INSTALLED
SYSTEM.
NOTE: THE
ABOVE LISTED CABLES COMPLY WITH NEC 760- 30(x)(1), 760- 30(b)(4), 760- 31(e), AND 760- 71(f)(i).
NOTE, Do NOT disconnect the AC power feed from
the terminal block to disconnect power,
t) The 120VAC primary power shall conform to NFPA 72
2002 Edition Section 4.4141
111AiA�! -DARE C0UNTY FIRE DEPARTF"EN
EL 3, ; :t�l!'6 eta: A,.a"'Trrt
pis E F" k sei l A tit�l."�"%::T. -
,:s:� r.r.�
rM ALARM SYSTEM TO $T�
MSTAI. LED IN ACCor�(OANCE WITH
NFPA 72; 70;101
• � u
r • •eWr`...,,.Rww.l Wal..,�,,..
Y�
r�
•
W�
1 ■
Engineer
Engineering Corp. 0.506-"
7816 SW 195 TEAR CE "
Miami, Florida 00. 1 Dll
(305) 772 -50
S i f a n Z h a o � � '� � �'� � "•t ' �'
9 Y
C.A.N. 9324 Fl. Re 0 5.,
These Fire Alarm drawings are approved and `comply
with the Engineer of Record's design criteria.
Project Name and Address
BAPTIST HEALTH
OF SOUTH FLORIDA
SOUTH MIAMI HOSPITAL
HR RELOCATION -2nd FL
FIRE AIJARM
6200 SW 73rd ST. SUITE 200
SOUTH MIAMI, JFL. ;33143
�" •.'
ill I
Fire ,alarm System Distribllbtor
DIVERSI &+E
SYSTEMS I� INC. '
13830 N.W. 19TH AVE.
MIAMI, FLORID k 33054
(305) 681-1:3216
STATE EF # 0000220
Project Sheet
Date FA — 3 9 0 2
01 -30 -202
Drawn .Y: SHEET
i. G. 1 of 3
■i I m
-F-IRE N11TES
ALL MAY NOT APPLY
,I) The,CICr,,,alarm d;%titem IsmLI.1,1_15ted as POWER LIMITED L
• of the g „nera, alar,-9 type pe • NFPA 72. All equipment Is
U.L. Listed forW Its Intenaed use,
2i Zhe �i�► alnrr-Y oanbl Ls Liroviwed with standby battery
per I�FP ;�72 withV 24 hours standby and 5 minutes alarm.
Should loss of normal 120VAC operating power occur, the
fire alarm panel will autematically transfer to the
standby battery,
3) A break In any field wiring or grounding of any
conductor will result In the activation of the fire alarm
panel trouble buzzer, which can I•e slenced by operating
the 'Trouble Silence” button on the fire alarm panel,
4) Pull stations to be mounted at 43' AFF per the ADA
code,
5) A/V devices to be mounted at 20' AFF per the NFPA
code,
G) Celing mounted smoke detectors shall not be located In
a direct alrflow, nor closer than 3 feet from an air
supply difuser per NFPA 72,
7) Power up and power down of the fire alarm panel must
Ise .lone In the proper sequoncei
Power Down, Disconnect battery and then turn
off the AC power at the breaker,
Power Up' Turn on the AC power at the breaker
and then connect the battery,
NOTE, Do NOT disconnect the AC power feed from
the terminal block to disconnect power,
t) The 120VAC primary power shall conform to NFPA 72
2002 Edition Section 4.4141
4,4,1,4,2 - Mechanical Protection
4,414,2A - The dedicated branch clrcult(s) and connectlo
shall be mechanlcally protected,
4,4,1,4,2.2 - Clrcult disconnecting means shall have a red
marking, shall be accessible only to authorized personnel
and shall be Idenlfled as 'FIRE ALARM CIRCUIT"
4,4,1,4.2,3 - The location of the disconnecting means shall
be permanetly Idendlfled at the fire alarm control unit,
9) The control (relay) module for AHU shutdown shall be
located within three (3) feet of the device I•eing
controlled, NFPA 101, The control module
shall be located such that the front mounted LED Is
vlslble upon entry Into mechanical room, Should the duct
detectors be located above the telling, the control
module shall be located In the telling dlrectly below the
duct detector so the LED Is clearly vlSlble, The relay
contacts have a MAXIMUM cababillty of 1.0 amps @ 24v
and 0.3 amps E 120VAC, Contractor must verify that the
shutdown circuit does NOT exceed these maximum current
ratings,
10) The installing contractor shall set the device address
as Identified on the Installation wiring dls•9rams, and
there shall be no changes from the addresses shown, as
this drawing will serve as the as -bunt drawing, and the
software program Is being written based on the
addresses shown,
11) The specified 'SLC /Data" loop cable Is extremely
Important, and It Is recommended that It NOT be
substituted by the Installer, The specified cable has
been selected because It Meets all of the techlnal
requirements of the system being Installed and Is on the
approved factory list of cables,
NOTICE. This drawing and all data
Contained herein is the intellectual
property of Diversifire Systems,
Inc. and shall not be duplicated
electronically or mechanically,
modified or altered, used or
disclosed in part or in whole for
any reason or pupose without the
express written consent of a
principal of the firm, or be liable
for the fullest legal recourse.
FIRE INSPECTOR CHANGES
8/2/2012
No.
Revision /Issue
Date
1 ■
Engineer
Engineering Corp. 0.506-"
7816 SW 195 TEAR CE "
Miami, Florida 00. 1 Dll
(305) 772 -50
S i f a n Z h a o � � '� � �'� � "•t ' �'
9 Y
C.A.N. 9324 Fl. Re 0 5.,
These Fire Alarm drawings are approved and `comply
with the Engineer of Record's design criteria.
Project Name and Address
BAPTIST HEALTH
OF SOUTH FLORIDA
SOUTH MIAMI HOSPITAL
HR RELOCATION -2nd FL
FIRE AIJARM
6200 SW 73rd ST. SUITE 200
SOUTH MIAMI, JFL. ;33143
�" •.'
ill I
Fire ,alarm System Distribllbtor
DIVERSI &+E
SYSTEMS I� INC. '
13830 N.W. 19TH AVE.
MIAMI, FLORID k 33054
(305) 681-1:3216
STATE EF # 0000220
Project Sheet
Date FA — 3 9 0 2
01 -30 -202
Drawn .Y: SHEET
i. G. 1 of 3
■i I m