12-637-003DEVICE MOUNTING HEIGHT
N.T.S.
VISUAL OR 1900 BOX
AUDIBLE/VISUAL 2.125" DE
DEVICE; 'ZH'
OR 7R' SERIES F U
R U
80" A.F.F. OR E tJ
6" BELOW CEILING
WHICHEVER IS LOWER f
PL
ST
42 " -54" A.F.F.
HORN /STROBE MOUNTING
WALL MOUNTED APPLIANCES SHALL BE MOUNTED SUCH THAT
THE ENTIRE STROBE LENS SHALL NOT BE LESS THAN 80 "'
AND NOT GREATER THAN 96" ABOVE THE FINISHED FLOOR.
NFPA 72 2007 Ed.
ADA SFBC
THE APPLIANCE SHALL BE PLACED 80" ABOVE THE HIGHEST
FLOOR LEVEL WITHIN THE SPACE, OR 6" BELOW THE CEILING
WHICHEVER IS LOWER.
SFBC Sec. 11
PULL STATION MOUNTING
THE OPERABLE PORTION OF EACH MANUAL PULL STATION
SHALL BE NOT LESS THAT 3 1/2 FT, NOR GREATER THAN
4 1/2 FT ABOVE FLOOR LEVEL
NFPA 72 2007 Ed.
FLORIDA BUILDING CODE - SECTION 907.3.2 - 2004 Ed.:
THE HEIGHT OF THE MANUAL FIRE ALARM BOXES SHALL BE A
MINIMUM OF 42 IN (1067mm) AND A MAXIMUM OF 48 IN
(1219mm), MEASURED VERTICALLY, FROM THE FLOOR LEVEL TO
TTHE ACTIVATING HANDLE OR LEVER OF THE BOX.
G`Q55 I p /P9>
UL
`lYV tee'`
WL1147
�
'061,
TV00098
3735 Green Rd.
Beachwood, OH, 44122
F- rating = 1 and 2 Hr.
T- rating = 0 and 1/2 Hr.
1D 1 or 2 - hour fire rated gypsum wallboard /stud assembly
® A) Steel Pipe - 6" diam.(or smaller) Sch. 40 (or heavier steel
B) Conduit - 4" diam.(or smaller) EMT or rigid steel
Q TREMstopWBM - fill Max. 3/4" annulus at a thickness
of 1 " (2 Hr. F- rating) or 3/4" (1 Hr. F- rating).
1
R712 -1
LOAD
RELAY
'-78 5/8" TO
BOTTOM OF
BOX
NO MUDRING IS REQUIRED.
FRONT OF 1900 BOX MUST BE
/CARD
READER OVERRIDE)
MEASURED
MEASURED
FLUSH WITH FINISHED WALL.
_
1.653
FROM A.F.F.
PL
ST
42 " -54" A.F.F.
HORN /STROBE MOUNTING
WALL MOUNTED APPLIANCES SHALL BE MOUNTED SUCH THAT
THE ENTIRE STROBE LENS SHALL NOT BE LESS THAN 80 "'
AND NOT GREATER THAN 96" ABOVE THE FINISHED FLOOR.
NFPA 72 2007 Ed.
ADA SFBC
THE APPLIANCE SHALL BE PLACED 80" ABOVE THE HIGHEST
FLOOR LEVEL WITHIN THE SPACE, OR 6" BELOW THE CEILING
WHICHEVER IS LOWER.
SFBC Sec. 11
PULL STATION MOUNTING
THE OPERABLE PORTION OF EACH MANUAL PULL STATION
SHALL BE NOT LESS THAT 3 1/2 FT, NOR GREATER THAN
4 1/2 FT ABOVE FLOOR LEVEL
NFPA 72 2007 Ed.
FLORIDA BUILDING CODE - SECTION 907.3.2 - 2004 Ed.:
THE HEIGHT OF THE MANUAL FIRE ALARM BOXES SHALL BE A
MINIMUM OF 42 IN (1067mm) AND A MAXIMUM OF 48 IN
(1219mm), MEASURED VERTICALLY, FROM THE FLOOR LEVEL TO
TTHE ACTIVATING HANDLE OR LEVER OF THE BOX.
G`Q55 I p /P9>
UL
`lYV tee'`
WL1147
�
'061,
TV00098
3735 Green Rd.
Beachwood, OH, 44122
F- rating = 1 and 2 Hr.
T- rating = 0 and 1/2 Hr.
1D 1 or 2 - hour fire rated gypsum wallboard /stud assembly
® A) Steel Pipe - 6" diam.(or smaller) Sch. 40 (or heavier steel
B) Conduit - 4" diam.(or smaller) EMT or rigid steel
Q TREMstopWBM - fill Max. 3/4" annulus at a thickness
of 1 " (2 Hr. F- rating) or 3/4" (1 Hr. F- rating).
1
R712 -1
LOAD
RELAY
CONNECTION DETAIL
(DOOR
MAGNET
/CARD
READER OVERRIDE)
DOOR MAGNET/
DOOR LOCK
N OTE:
THE R712 -1 RELAY IS SHOWN
IN A NORMAL ENERGIZED' STATE
NORMALLY CLOSED IS OPEN AND
NORMALLY OPEN IS CLOSED F-0
U
1
100@1
NC C NO
R712 -1
POWER FROM
DOOR CONTROLLER
01
)a 24 115 230
1) CD 0
1 O
2 Hour Fire Rated Thr,
Gs-oo, ls i fI Penetration Firestop for
Plastic Pipe througl
Co ncrete Floors or We
yst00 using BlazeMaster Caulk
CAJ 2221 F- Rating = 2 Hr.
T- Rating = 1 -1/2 Hr.
NOTE:
'THE R712 -1 RELAY IS NORMALLY
ENERGIZED (FAILSAFE) AND DROPS
OUT ON ALARM CONDITION. CONNECT
THE CONTROL CIRCUIT TO THE N/0
CONTACT, WHICH IS HELD CLOSED
UNDER NON -ALARM CONDITION
24 VDC ('P') HOMERUN
TO EXISTING FACP
VTOB098
3735 Green Rd.
Beachwood, OH, 44122
(D Pre -Rated Concrete Floors or Block Walls = Min. 4 -1/2" thickness
2Q Plastic Pipe - A) Nom. 2" diam., (or smaller) Sch. 40 PVC pipe.
B) Nom. 2" diam. (or smaller) CPVC pipe
The annular space range shall be min min 1/4" to max 3/8"
NOTE: For use in closed (process or supply) piping systems.
30 Forming Material - Foam backer rod firmly packed into the opening as a permanent form.
® BlazeMaster Caulk & walk ,- min'1 /2" thickness of sealant applied within opening, flush
top surface of floor or both surfaces of wall assembly'
RSE -300 REMOTE POWER BOOSTER BATTERY SIZE CALCULATIONS
Panel I.D.: RPS'P2' Model : Faraday RSE -300 Power Booster Max Circuit Current: 3A
Location: 1st FLR LOBBY Volts: 24 VDC Max Panel Current: 6A
Ckt. #
Circuit Name
Current Draw
Standby Alarm
Wire AWG
& Type
Ohms per
1000 ft.
Length (ft)
One Way
Actual
Ohms
Volts @
EOL
1
CIRCUIT P2 -1
FACP /
BOOSTER
1.653
#14 Solid
3.07
300
1.842
17.36
2
CIRCUIT P2 -2
0.000
#14 Solid
3.07
0
0.000
20.40
3
CIRCUIT P2 -3
#14
0.000
#14 Solid
3.07
1 0
1 0.000
1 20.40
4
CIRCUIT P24
75
0.000
#14 Solid
3.07
0
1 0.000
20.40
Aux
Aux Power Out
41
116
#14
0.712
20.01
P2 -14
ZH -MC -R
RSE -300
Main Board
0.075
0.175
1.828
(Amps) Total Output Power Required
Total Standby Current (Amps)
0.075
1.828
Total Alarm Current (Amps)
Alarm Time in Minutes if (5 min.)
Total Alarm AH Required
75cd HORN /STROBE RED
0.188
Standby Time in Hours
24
0.084
Total Standby AH Required
1.800
0.154
Total Combined AH Required
= 1.954
Multiply by the Derating Factor
= 1.20
Minimum Battery AmpHours Required = 2.344
Battery Size Provided: 5.0 AH
CURRENT DRAW AND VOLTAGE DROP CALCULATIONS
NOTIFICATION APPLIANCE CIRCUIT (NAC)'# 1 (S1)
DEVICE # ON
DRAWING
DEVICE
MODEL
NUMBER
DEVICE DESCRIPTION
DEVICE
CURRENT
(amps)
CIRCUIT
CURRENT
(amps)
DISTANCE (in fret) FROM:
WIRE
SIZE
(awg)
CIRCUIT
RESISTANCE
(Ohms)
CIRCUIT
VOLTAGE
(Vdc)
LAST
DEVICE
FACP /
BOOSTER
ALL MAY NOT .1PPLY -
1) The fire alarm system Is U.L. Listed as POWER LIMITED &
P2 -1 -1
ZH -MC -R
75cd HORN /STROBE RED
0.188
0.188
39
#14
0.239
20.35
P2 -1 -2
ZH -MC -R
75cd HORN /STROBE RED
0.188
0.376
36
75
#14
0.461
20.23
P2 -1 -3
ZR -MC -CR
75cd STROBE LIGHT CEILING MNT
0.175
0.551
41
116
#14
0.712
20.01
P2 -14
ZH -MC -R
75cd HORN /STROBE RED
0.188
0.739
23
139
#14
0.853
19.77
P2 -1 -5
ZH -MC -R
75cd HORN /STROBE RED
0.188
0.927
43
182
#14
1.117
19.36
P2 -1 -6
ZH -MC -R
75cd HORN /STROBE RED
0.188
1.115
27
209
#14
1.283
18.97
P2 -1 -7
ZR -MC -R
75cd STROBE LIGHT RED
0.17
1.290
44
253
# 14
1.553
18.40
P2 -1 -8
ZR -MC -R
75cd STROBE LIGHT RED
0.175
1.465
18
271
#14
1.064
17.96
P2 -1 -9
ZH -MC -R
75cd HORN /STROBE RED
0.188
1.653
29
300
#14
1 1.842
17.36
7) Power up and power down of the fire alarm panel must
NOTE:'Circuit voltage is calculated using 20:4 V per NFPA 72'02Ed.
2.5 Amps Wire resistance is taken from Chapter, 9 Table 8 of the National Electric
20.4 Vdc Code (NFPA 70)'05 Ed. Resistance shown is calculated at 75 degrees
16 Vdc Centigrade (167 degrees Fahrenheit)
TOTAL CUMULATIVE CIRCUIT CURRENT DRAW"
MAX ALLOWABLE CIRCUIT CURRENT DRAW:
CIRCUIT SOURCE VOLTAGE:
MINIMUM OPERATING VOLTAGE:
CIRCUIT POWERED FROM: RIPS P2 NAC CKT #1
THERE ARE NO NEW DEVICES BEING CONNECTED UNDER THIS SCOPE
TO THE EXISTING FIRE ALARM CONTROL PANEL,, THEREFORE NO STANDBY
BATTERY CALCULATIONS FOR THE EXIST FIRE ALARM PANEL ARE REQUIRED.
THIS EXISTING FIRE ALARM SYSTEM IS
CONVENTIONAL, HARDWIRED, NOT
ADDRESSABLE
SEQUENCE OF OPERATION
MATRIX
WATER FLOW DEVICES
TAMPERS
MANUAL PULL STATION
SMOKE DETECTOR
HEAT DETECTOR
DUCT SMOKE DETECTOR
AUDIBLE DEVICES
VISUAL DEVICES
MISSING DETECTOR
OPEN CIRCUIT /CABLING GROUND
AC POWER LOSS
LOW BATTERY
4PGQ A
oG� �p o��
�� PJ @ �P� v �Q" J�O o�
��V
LR0��0�0
NOTE #1: THE EXISTING FACP IS NOT CAPABLE OF SILENCING THE HORNS, & THE -STROBE LIGHTS CONTINUE
TO FLASH, THEREFORE UPON ACTIVATION OF THE SILENCE SWITCH, THE AUDIBLES (HORNS) & THE VISUALS
STROBE LIGHTS) WILL BOTH SILENCE & TURN OFF.
NOTE #2: THE EXISTING FACP (FIREWATCH XVI) DOES NOT HAVE SUPERVISORY SIGNAL CAPABILITIES, ONLY
ALARM & TROUBLE CONTACTS.
VOLTAGE DROP CALCULATIONS, DETAILS & SEQUENCE of OPERATION
FIRE ALARM SYS'T'EM TO BE
INSTALLED hN Ac:CoRDANCZ NN I'
NFPA 72; 70;101
Contract Set Sheet #:
N/A
Contract Set Date:
General Notes ^
Revision # /Date:
N/A
FIRE-- AF �,RM;NIETES: ^
ALL MAY NOT .1PPLY -
1) The fire alarm system Is U.L. Listed as POWER LIMITED &
of the general •sLo ^n type_ ner .NFPA 72. All equipment Is
NOTE #1: THE EXISTING FACP IS NOT CAPABLE OF SILENCING THE HORNS, & THE -STROBE LIGHTS CONTINUE
TO FLASH, THEREFORE UPON ACTIVATION OF THE SILENCE SWITCH, THE AUDIBLES (HORNS) & THE VISUALS
STROBE LIGHTS) WILL BOTH SILENCE & TURN OFF.
NOTE #2: THE EXISTING FACP (FIREWATCH XVI) DOES NOT HAVE SUPERVISORY SIGNAL CAPABILITIES, ONLY
ALARM & TROUBLE CONTACTS.
VOLTAGE DROP CALCULATIONS, DETAILS & SEQUENCE of OPERATION
FIRE ALARM SYS'T'EM TO BE
INSTALLED hN Ac:CoRDANCZ NN I'
NFPA 72; 70;101
I I property of Diversifire Systems,
Inc. and shall not be duplicated V;,„ W`
electronically or mechanically,
modified or altered, used or
disclosed in part or in whole for
any reason or pupose without the
express written consent of a
principal of the firm, or be liable
for the fullest legal recourse.
No. I Revision /Issue I Date
Drawing Reference
Contract Set Sheet #:
N/A
Contract Set Date:
General Notes ^
Revision # /Date:
N/A
FIRE-- AF �,RM;NIETES: ^
ALL MAY NOT .1PPLY -
1) The fire alarm system Is U.L. Listed as POWER LIMITED &
of the general •sLo ^n type_ ner .NFPA 72. All equipment Is
U.L. Listed for I-s ^In +ended use, ^
2) The fire alarm ?anel-Is prov'ded with standby ;)atte�-y
per NFPA 72 wltn -24 hours standby and 5- minu =es aLarm.
Should loss of normal 120VAC operating - power- OCcL.: , the
fire alarm panel will automatically transfer to the
standby battery.
3) A break In any field wiring or grounding of any
conductor will result In the activation of the fire alarm
panel trouble buzzer; which can be slenced by operating
the 'Trouble Silence' button on the fire alarm panel.
4) Pull stations to be mounted at 48' AFF per the ADA
code.
5) A/V devices to be mounted at 80' AFF per the NFPA
code.
6) Celing mounted smoke detectors shall not be located In
a direct dlrflow, nor closer than 3 feet from an air
supply difuser per NFPA 72.
7) Power up and power down of the fire alarm panel must
be done In the proper sequences
Power Dowrn Disconnect battery and then turn
off the AC power at the breaker.
Power Up, Turn an the AC power at the breaker
and then connect the battery,
NOTEt Do NOT disconnect the AC power feed from
the terminal block to disconnect power.
b) The 120VAC primary power shall conform to NFPA 72
2002 Edition Section 4.4.1.4:
4,4.1.4,2 - Mechanical Protection
4.4.1.4.2.1 - The dedicated branch circuits) and connectlo
shall be mechanically protected.
4.414.2,2' - Circuit disconnecting means shall have a red
marking, shall be accessible only to authorized personnel
and shall be Idenifled as 'FIRE ALARM CIRCUIT.'
4.4.1.4.2.3 - The location of the disconnecting means shall
be permanetly Idendifled at the fire alarm control unit.
9) The control (relay) module for AHU shutdown $hall be
located within three (3) feet of the device being
controlled. NFPA 101. The control module
shall be located such that the front mounted LED Is
vlsIbte upon entry Into mechanical room. Should the duct
detectors be located above the ceiling, the control
module shall be located In the ceiling directly below the
duct detector so the LED Is clearly visible. The relay
contacts have a MAXIMUM cababillty of 1.0 amps @ 24v
and 0.3 amps @ 120VAC. Contractor must verify that the
shutdown circuit does NOT exceed these maximum current
ratings.
10), The Installing contractor shall set the device address
as Identified on the Installation wiring disgrams, and
there shall be no changes from the addresses shown, as
this drawing will serve as the as -built drawing, and the
software program Is being written based on the
addresses shown.
11) The specified 'SLC /Data' loop cable Is extremely
Important, and It Is recommended that It NOT be
substituted by the Installer. The specified cable has
been selected because It meets all of the techinal
requirements of the system being Installed and Is on the
approved factory list of cables.
NOTICE. This drawing and all data
"!
Contained herein is the intellectual
I I property of Diversifire Systems,
Inc. and shall not be duplicated V;,„ W`
electronically or mechanically,
modified or altered, used or
disclosed in part or in whole for
any reason or pupose without the
express written consent of a
principal of the firm, or be liable
for the fullest legal recourse.
No. I Revision /Issue I Date
Drawing Reference
Contract Set Sheet #:
N/A
Contract Set Date:
N/A
Revision # /Date:
N/A
Engineer is
E r;s'•
Engineering ,e&r
7 816 SW 1, 9 S *f•L R PACP l� s
Miami, Florida :33157* ",�/
(305) 772:�*Q23 AT
Sifang Zhao•� ;
C.A.N. 9324 Fl. R'� ,gr '� 685
These Firg Alarm drawings' are approv d, arid" comply
with the Engineer of Record's' desigri criteria.
Installing Contractor
' TRICITY
'ELECTRIC CO.
625 NW 16 AVENUE
MIAMI, FL. 33125
(305) 642 4011
EC •0000136
Project Name and Address
BAPTIST HEALTH
OF SOUTH FLORIDA
SOUTH ' MIAMI HOSPITAL
HR RELOCATION -2nd FL
FIRE ALARM
6200 SW 73rd ST. SUITE 200
SOUTH MIAMI, FL. 33143
Fire Alarm System Distributor
DIVERSIFIRE
SYSTEMS .INC.
13830 N.W. 19TH AVE.
MIAMI, FLORIDA 33054
(305) 681 -3216
STATE EF # 0000220 J
Project Sheet
Date
FA-3904
01 -30 -2012
Drawn By: SHEET
J.G. 3 of 3
/I
4 °g
w
tl '
4 ,
e'h
i'
L