Loading...
12-637-002DEVICE LEGEND WIDE ]LEGEND DESCRIPTION MODEL # SYMBOL FLUSH BACKBOX E T N EXISTING FIRE ALARM CONTROL PANEL CIRCUIT/FUNCTIOM A 1 PAIR #18 FPL, FPLP, FPLR, THHN INITIATING DEVICE CIRCUIT SUPPLIED w/ PRODUCT P 1 PAIR #14 FPL, FPLP, FPLR, THHN MAGNETIC DOOR LOCK RELAY CIRCUIT SX 11 PAIR #14 FPL, FPLP, FPLR, THHN NAC (NOTIFICATION APPLIANCE CIRCUIT ( %" DENOTES CIRCUIT NUMBER) IT IS RECOMMENDED THAT YOU DO NOT SUBSITUTE FOR THE SPECIFIED CABLES ABOVE, AS THEY ARE FACTORY APPROVED TO INSURE t, PROPER OPERATION OF THE INSTALLED SYSTEM. HORN /STROBE 75CD WALL MNT NOTE: THE ABOVE LISTED CABLES COMPLY WITH NEC 760- 30(a)(1), 760- 30(b)(4), 760- 31(e), AND 760- 71(f)(i). O STROBE LIGHT 75CD WALL MNT ZR —MC —R 1900 DEEP BOX —NO RING DEVICE LEGEND SYMBOL DESCRIPTION MODEL # SURFACE BACKBOX FLUSH BACKBOX FACP EX EXISTING FIRE ALARM CONTROL PANEL FIREWATCH XVI N/A EXISTING IRES ]NEW REMOTE POWER BOOSTER RSE -300 SUPPLIED w/ PRODUCT SUPPLIED w/ PRODUCT ® ETR SMOKE DETECTOR EXISTING EXISTING EXISTING EXISTING PULL STATION 10561 1900 BOX w/ 1 GANG RING 1900 BOX w/. 1 GANG RING ® LOAD RELAY — SPST R712 -1 SUPPLIED w/ PRODUCT SUPPLIED w/ PRODUCT HORN /STROBE 75CD WALL MNT ZH —MC —R 1900 DEEP BOX —NO RING 1900 DEEP BOX —NO RING O STROBE LIGHT 75CD WALL MNT ZR —MC —R 1900 DEEP BOX —NO RING 1900 DEEP BOX —NO RING O C STROBE LIGHT 75CD CEILING MNT ZR —MC —CR 1900 DEEP BOX —NO RING 1900 DEEP BOX -NO RING "ETR" DENOTES EXISTING DEVICE TO REMAIN. SCOPE OF I A A WORK A P P A A A A A A A S1 S1 S1 S1 S1 S1 S1 S1 EOL I S1 F F F C F F F F F LF CKT 'P2 -1' I F F R M3 ETR ETR ETR ETR ETR ETR ETR -N� EOL M1 M2 MAGNETIC DOOR EOL D7 D6 D5 D4 D3 D2 D1 75cd 75cd 75cd 75cd 75cd 75cd 75cd 75cd 75cd 1.65 PULL SMOKE P2 -1 -1 P2 -1 -2 P2 -1 L 3 P2 -1 -4 P2 -1 -5 P2 -1 -6 P2 -1 -7 P2 -1 -8 P2 -1 -9 1.65A LOCK OVERRIDE STATION DET EXISTING INITIATING DEVICES TO REMAIN NEW NAC DEVICES 17.36V 7Z � � � � � � � �� � � � � � � � � �� � � � � � � � � �� � � �� � � �� tee• NOTE: THE RELAY USED FOR THE MAC EX EX EX � EX FF EX F LOCK OVERRIDE MUST HAVE A H EX SEPARATE, 1 PAIR, 2 CONDUCTOR D16 D17 D18 75cd 75cd 75cd WIRE ('P') HOMERUN TO THE I P1_1 P1-2 P1 —7 EXISTING INITIATING DEVICES EXISTING FACP. EXISTING NAC DEVICES DO NOT CONNECT THIS RELAY TO ANY OTHER CIRCUIT (INITIATING, 2ND FLOOR , I 2ND FLOOR NAC, ETC.) F HEX F EX HEX HEXHEX F EX M12 D15 M11 D14 D13 D12 M10 ETR ETR ETR ETR EXISTfNG INITIATING DEVICES EXISTING GUTTER /JUNCTION BOX �PS P2 NEW REMOTE POWER BOOSTER RSE -300 P1 EXISTING FIRE ALARM CONTROL PANEL S1 1� 7 F� � r F I F EX LF� EX LFJ EX LFi EX �- EX � 75cd 75cd 75cd 75cd 75cd 75cd EX N1 N2 N3 N6 N7 N8 EXISTING NAC DEVICES THE EXISTING FACP IS LOCATED ON THE 1 ST FLOOR RECEPTION AREA. THE NEW REMOTE POWER BOOSTER SHALL BE LOCATED AND IN-STALLED NEXT TO THE EXISTING FACP ON THE 1 ST FLOOR. FIREWATCH XVI L_ ELEC PANEL 1st FLR ELEC ROOM CKT #36 20A EXISTING 120 VAC CKT. CONNECT NEW P2 BOOSTER TO EXISTING DIAGRAMTIC RISER 1 ST FLOOR FACP 120 VAC CIRCUIT ST FLOOR MIAW -DAD COUNTY FIRE UE fsALANRn�aA.4IrN i?LDG. PE "'M1T —, - -_ r, „MAIN FACT.._+-- - FIRESI)Pf REPS +ON___ -._.. Y�tv�`j\1 YSTE A O BV FIl�c CEwV v ICC0FD ST�,VA72; 70•, 101 General Notes FIRE _A_RK NL1-TE 1 ALL MAY NOT Ar3PLv 1) The fire alarm system Is U.L. Listed as POWER LIMITED g of the general ol.orm typeDor NFPA,72. All equipment Is U.L. Listed for; Its_ I itended ure. 2) The fire alari� panel Is prcwided with standby; battery per NFPA 72 w-th P_y hour,e„standbl- and -5 mimites- alarm. Should loss of normal 12UVHC opera{ic g power— =cur, -the fire alarm panel will automatically transfer to the standby battery. 3) A break in any field wiring or grounding of any conductor will result In the activation of the fire alarm panel trouble buzzer, which can be slenced by operating the 'Trouble Silence' button on the fire alarm panel. 4) Putt stations to be mounted at 48' AFF per the ADA code. 5) A/V devices to be mounted at 80' AFF per the NFPA code. 6) Ceiing mounted smoke detectors shall not be located In p direct airflow, nor closer than 3 feet from an air supply difuser per NFPA 72. 7) Power up and power down of the fire alarm panel must be done In the proper sequences Power Down, Disconnect battery and then turn off the AC power at the breaker. Power Upt Turn on the AC power at the breaker and then connect the battery. NOTEi Do NOT disconnect the AC power feed from the terminal block to disconnect power. 8) The 120VAC primary power shall conform to NFPA 72 2002 Edition Section 4.4.1.41 4,4142 -'Mechanical Protection 4.4.1.4.2.1 - The dedicated branch clrcuit(s) and connectlor shall be mechanically protected. 4.4,1.4.2.2 - Circuit disconnecting means shall have a red marking, shall be accessible only to authorized personnel, and shall be Idenlfled as 'FIRE ALARM CIRCUIT.' 4.4,1.4,2.3 - The location of the disconnecting means shrill' be permanetly Idendlfled at the fire alarm control unit. 9) The control (relay) module for AHU shutdown shalt be located within three (3) feet of the device being controlled. NFPA 101. The control module shall be located such that the front mounted LED Is visible upon entry Into mechanical room. Should the duct detectors be located above the ceiling, the control module shall be located In the ceiling directly below the duct • detector so the LED Is clearly visible. The relay contacts have a MAXIMUM cnbabillty of 1.0 amps 2 24v and 0.3 amps 2 120VAC. Contractor must verify that the shutdown circuit does NOT exceed these maximum current ratings. 10) The Installing contractor shall set the device address as Identified on the Installation wiring disgrams,' and there shall be no changes from the addresses shown, as this drawing will serve as the as -built drawing, and the software program Is being written based on the addresses shown, 11) The specified 'SLC /Data' loop cable is extremely Important, and it Is recommended that It NOT be substituted by the Installer. The specified cable has been selected because It meets all of the techinal requirements of the system being Installed and Is on the approved factory list of cables. NOTICE, This drawing and all data Contained herein is the intellectual property of Diversifire Systems, Inc. and 'shall not be duplicated electronically or mechanically, modified or altered, used or disclosed in part or in whole for any reason or pupose without the express written consent of a principal of the firm, or be liable for the fullest legal recourse. No. I Revision /Issue I Date Drawing Reference Contract Set Sheet #: N/A Contract Set Date: N/A Revision # /Date: N/A Engineer •G./86 Engineer$ ;� qr)D. E • W 7816 SW 196 *TekRk5 :o Miami, FloricEo 33157,$' X (305) 772' 023 T T = Sifang Zhaor- ,,,,P.; q C.A.N. 9324 FI. Rat. 1`85 These Fire Alarm drawings are approz;bnd comply with the Engineer of Record's design criteria. Installing Contractor TRICITY ELECTRIC CO. 625 NW 16 AVENUE MIAMI, FL. 33125 (305) 642 4011 ` EC 0000136 Project Name and Address BAPTIST HEALTH OF SOUTH' FLORIDA SOUTH MIAMI HOSPITAL HR RELOCATION -2nd FL FIRE ALARM 6200 SW 73rd ST. SUITE 200 SOUTH MIAMI, FL. 33143 J Fire Alarm System Distributor DIVERSIFIRE SYSTEMS INC. 13830 N.W. 19TH AVE. MIAMI, FLORIDA 33054 (305) 681 -3216 STATE EF # 0000220 Project Sheet Date FA-3903 01 -30 -2012 Drawn By: SHEET J. G. 2 of 3