12-521-018J u in 14 13 12 11 im .GENERAL NOTES D 1. TYPE V. HIGHEST RISK CLASS IV 2 OBTAIN INFECTION CONTROL PERMIT BEFORE CONSTRUCTION BEGINS. 3. ISOLATE HVAC SYSTEM IN AREA *ERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF THE DUCT SYSTEM. 4. COMPLETE ALL CRITICAL BARRIERS I.E. SHEET ROCK, PLYWOOD, PLASTIC. TO SEAL AREA FROM NON WORK AREA OR IMPLEMENT CONTROL WE METHOD (CART WITH PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM FOR VACUUMING PRIOR TO EXIT) BEFORE CONSTRUCTION BEGINS. 5. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA /CARBON EQUIPPED AIR FILTRATION UNITS. (3. SEAL HOLES, PIPES. CONDUITS, AND PUNCTURES. 7. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL M PASS THROUGH THIS ROOM SO THEY CAN BE VACUUMED USING A HEPA VACUUM CLEANER BEFORE LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR PAPER COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE WORK SITE. 8. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR SHOE COVERS. SHOE COVERS MUST BE CHANGED EACH TIME THE WORKER EXITS THE WORK AREA 9. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY THE OWNER'S SAFETY DEPARTMENT AND INFECTION PREVENTION & CONTROL DEPARTMENT AND THOROUGHLY CLEANED BY THE MEWS ENVIRONMENTAL SERVICES DEPT. 10. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH CONSTRUCTION. 11. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS. 12 COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID. 11 VACUUM WORK AREA WITH HEPA FILTERED VACUUMS. 14. WET MOP AREA WITH CLEANER/bISINFECTANT. 15. UPON COMPLETION, RESTORE HVAC SYSTEM WHERE WORK WAS PERFORMED. 18. VISWEEN CUBE CONSTRUCTION ISOLATION SHALL BE CREATED WHEN WORK IS REQUIRED IN AREAS THAT DO NOT REQUIRE NEGATIVE AIR MACHINES AND /OR CONSTRUCTION BARRIER ISOLATION. HEPA VACUUM SHALL BE USED M CLEAN WITHIN THE CUBE AFTER THE WORK HAS BEEN COMPLETED. 17. PORTABLE HEPA /CARBON FILTER NEGATIVE AIR MACHINE($) SHALL BE INSTALLED TO CLEAN THE AIR IN THE ROOM. AIR QUANTITY SHALL BE ADJUSTED TO MAINTAIN A MINIMUM OF O.OY W.g. NEGATIVE PRESSURE VISUAL PRESSURE INDICATOR WILL BE INSTALLED AT THE ENTRANCE. AFTER INSTALLATION OF CONSTRUCTION BARRIER WALLS AND THE ABOVE MEASURES, A CERTIFIED TEST AND BALANCE FIRM SHALL CONFIRM THAT THE ABOVE ITEMS ARE IN PLAICE AND WORKING PRIOR TO STARTING DEMOLITION. STICKY MAT SHALL ALSO BE INSTALLED. VISQUEEN SHALL BE INSTALLED AT THE EXISTING DOORS. CONTRACTOR SHALL COMPLY WITH OWNER REQUFMAD T5 FOR INFECTION CONTROL FINAL FILTER EFFICIENCY SHALL BE 99.97 7i'Jlx OR HIGHER FOR 1 MICRON PARTICLES. DO NOT POSITIVELY PRESSURIZE EXISTING DUCTWORK. USE THE NEGATIVE AIR MACHINE FOR SPOT FILTRATION/EXHAUST SERVICE WHEN WORKING ABOVE THE CEILING OUTSIDE THE WALLS OF THE RENOVATED SPACE 18. STRONG ODORS ARE NOT EXPECTED DUE TO THE SCOPE OF WORK. 19. REFERENCE ARCHITECTURAL PLANS FOR LOCATION OF TEMPORARY CONSTRUCTION WALLS AND PHASING. 20. REFERENCE INFECTION CONTROL CONSTRUCTION PERMIT FOR ADDITIONAL REQUIREMENTS. 21. REFERENCE CONSTRUCTION DOCUMENTS FOR ADDITIONAL REQUIREMENTS. 22 PROVIDE A FIRE WATCH IN AREAS AREAS OF CORSTRUCTION DURING ENTIRE CONSTRUCTION PERIOD. ' 'w-'4N COMPLY WITH FBC 419.4210. COORDINATE REQUIREMENT OF FIRE EXTINGUISHERS WITH GENERAL CONTRACTOR LEGEND NOTES OCONTRACTOR SHALL INSTALL NEGATIVE AIR MACHINE AND TEMPORARY ROUND FLEX DUCT FROM MACHINE AS INDICATED. REMOVE AT END OF CONSTRUCTION. OCONTRACTOR SHALL INSTALL MAGNETIC DRAFT GAUGE MAINTAIN 0.02" W.C. NEGATIVE PRESSURE. IN THE CONSTRUCTION AREA OA CERTIFIED TEST AND BLALANCE FIRM SHALL PERFORM A PRE - CONSTRUCTION TEST AND BALANCE IN THE SCOPE OF WORK AREA TO DETERMINE ACTUAL FLOW RATES AT ALL SUPPLY, RETURN AND EXHAUST DEVICES. FOLLOIMG T&B, CONTRACTOR SHALL CLOSE SUPPLY, RETURN AND EXHAUST DAMPERS THAT SERVE THE SCOPE OF WORK AREA AND REBALANCE THE AIR HANDLING UNIT AND FAN THAT SERVE THE AREA, REDUCING THE TOTAL AIRFLOW AMOUNT AT THE EQUIPMENT BY THE AMOUNT BEING REMOVED FROM THE SYSTEM. CONTRACTOR SHALL COVER ALL AIR DEVICES WITHIN RENOVATED AREA WITH VISWEEN PLASTIC. AT SUBSTANTIAL COMPLETION OF THE PROJECT, THE CONTRACTOR SHALL REMOVE VMEEN PLASTIC AND REBALANCE AIR HANDLING UNIT, FANS AND AIRFLOW DEVICES IN THE SPACE BACK TO THE PRE - CONSTRUCTION QUANTITIES. O4 TEMPORARILY CONNECT TO NEAREST EMERGENCY POWER CONTRACTOR SHALL PROVIDE ALL NECESSARY ELECTRICAL APPURENTECES AS REQUIRED FOR THIS CONNECTION. OTEMPORARY CONSTRUCTION WALL/ VISQUEEN PLASTIC. REFER TO ARCHITECTURAL PLANS OTEMPORARY ROUND FLEX DUCT SIZED FOR 0.1' W.G. AT A MAXIMUM OF 1,200 FPM. OCONTRACTOR SHALL INSTALL NEGATIVE HEPA AIR MACHINE AS INDICATED. REMOVE AT END OF CONSTRUCTION. OPROVIDE DUCT COLLARS IN TEMPORARY PARIT10N TO FIT TEMPORARY ROUND AIR DUCT AS INDICATED. AT THE END OF CONSTRUCTION CONTRACTOR SHALL PATCH, SEAL. REINSULATE, PAINT, ETC... WALL/IMNDOW TO MATCH EXISTING. PROVIDE BIRD SCREEN AT OPENING. OPROVIDE INTAKE LOUVER WITH BIRD SCREEN INSTALLED IN TEMPORARY PARTITION. PROVIDE THE FOLLOYYING FILTERS WITH PORTABLE AIR SCRUBBER: STAGE 1 PRE - FILTER: ONE -INCH DEEP FIBER TRAPPER STAGE 2 PRE - FILTER: TWO -INCH MERV 7 STAG: 3 PRE - FILTER: TWO -INCH DEEP FIBER TRAPPER CARBON FILTER. STAG: 4 FINAL - FILTER: METAL -FRAME 99.97X OR HIGHER HEPA FILTER. 'I �1 0 [ 3 Ilk 0117 01 "10) L' Kyfxly • METAL FLEX (TYP•) PORTABLE AIR SCRUBBER — WITH HEPA & THROUGH LOUVER I I CARBON FILTER MANUFACTURER,( MODEL 1I PORTABLE AIR SCRUBBER TO BE SIMILAR TO: ABATEMENT TECHNOLOGIES/ PAS2400 02 AIR St BBER DETAIL --- - - ----- 8 7 8 6 4 3 Project #:411447.000 r 2121 Ponce de `_ecn Bovievard - PICSuite 350 :. Coral Gables, FL 33134 .. , phone: 305.569.1692 .- fax. 305.175Q 1693 ----- Tp Professional Consultlng Engineers � � - I�.1fll Austin . Dallas • Denver • Houston : Xaosas City,--Miami , Nashville . Phoenix . Richmond . Washingtcq D.C. EB00007658 [ ^ ^ DATE- 3123.12 A CLINICAL LABORATORY n.4PFTH FLOOR PLAN V I SCALE: 1/4" C T -0" - M -ICRA NK • ,9 888% O H rul LL :18 co 0 N V 0� 8 UU cm NP DESORPTION DATE I I mmew 1 42U 1 t 9 7 X 4i N. JOB 19 , 4= U-11k, • MACRA-1 0 wvvrW L1YA 4 Fn