12-509-033PLUMBING FIXTURE SCHEDULE rt
(CONTRACTOR SHALL COORDINATE ALL PLUMBING REQUIREMENTS WITH FINAL OWNER FURNISHED EQUIPMENT BROCHURE)
FIXTURE
FITTING
FLOOR
OISCRPTIN
C.IL
ILI.
DL
p
BASTE
REMARKS
OFCI EOUIPMENT BOOM
MOUNTED
P.W
C.W
H.W.
WASTE
REMARKS
MANUFACTURER
MODEL
TYPE
SIZE
MANUFACTURER
TYPE
SUPPLY
TRAP
FAUCET
SYMBOL
CARRIER
-
SHUTOFF VALVE MODEL •FRM1812S. COORDINATE MOUNTING HEIGHT WITH EOUIPMENT.
LINE PRESSURE ALARM PANEL
1
(1)02. (1)N20. (DA, (I)V. (i)CA.
(3)SPARE
P_3
(PUBLIC)
WELLWORTH
K -4406
FLUSH VALVE
FLOOR MOUNTED
ELONGATED
SLOAN ROYAL
' Ill- 1.28 -TD YBYC
NA
INTEGRAL
NA
NA
__
I•
__
4•
K-4670G WHITE SEAT,
SO-2 BACKFLOW PREVENTER BETWEEN SHUTOFF VALVE AND EOUIPMENT
WATER
WATER CLOSET
W
1.28 GALLON
VITREOUS CHINA
BOWL
HUB DRAIN
FLUSH VALVE
MECH. ROOMS
CONNECTOR.
AIR DRYERS 120V.
MOUNT IS' A.F.F. AFF
FLUSH VALVE
Y' FIRE RATED AL WHITE WALL X NI H
72 OB NOISE
SHUTOFF VALVE MODEL •FRM1812S. COORDINATE MOUNTING HEIGHT WITH EOUPMENT.
0088
P -3A
KOHLER (PUBLIC)
HIGHLINE
FLOOR MOUNTED
ELONGATED
' SLOAN ROYAL
' 111 - 1.28 -TD YBYC
NA
INTEGRAL
NA
NA
--
1•
--
4•
K -4670C WHITE SEAT,
WATER CLOSET -HC
K -4405
VITREOUS CHINA
BOWL
FLUSH VALVE
CONNECTOR.
MOUNT (HC) 18' A.F.F.
1.28 GALLON
PROVIDE SHUTOFF VALVE (ACCESSIBLE PER EO.MANUF.GUIDELINES) AND UNION AT
P -6A
URINAL (HC)
URINAL
BARDON
•K- 4960 -ET
WALL HUNG
NA
SLOAN ROYAL
'186 -0.5
NA
INTEGRAL
NA
ZURN
21221
--
3
/;
__
2•
MOUNT
17' A.F.F.
0.5 GALLON
VITREOUS CHINA
PROVIDE DEARBORN BRASS •814 BRANCH TAIL PIECE WITH SIDE INLET. INSTALL
IN SINK ADJACENT TO STERILIZER.& ROUTE WASTE FROM STERILIZER TO
TO RIM
5' BACKSPLASH
CONNECTION OF TAILPIECE. PROVIDE WITH AR GAP FITTING. ROUTE WASTE FROM
CHICAGO FAUCET
P -13A
KOHLER (HC)
KINGSTON
WALL HUNG
CONCEALED ARM
21' X 18'
McGUIRE
8155WC GRID DRAIN
WITH PROWRAP
H -2165
88902 I'/Z INLET 70
1'/J- P -TRAP
3895- 31TE2805 "5CP
WRSTBLAOE HANDLE.
ZURN
, /i
, /f
,
t/f
MOUNT 34' A.F.F. TO
RIM.
LAVATORY
K-2005
VITREOUS CHINA
4• FAUCET CTR
'PW2125 -WC
O SET FOR WHEEL
COORDINATE OS GPM NON
AERATOR FLOW CONTROL
Z -1231
CHAIR USE
DEVICE WITH MFGR.
CHICAGO FAUCET
COORDINATE HOLE
CORIAN COUNTERTOP WITH
9155WC GRID DRAIN
08902 1'/Z INLET TO
0895- 3ITE2805 -5CP
PUNCHES FOR FAUCET
P -14
INTEGRAL SINK SPECIFIED
McGUIRE
WITH PROWRAP
H -2165
11/ OUTLET P -TRAP
OFFSET FOR WHEEL
WRISTBLADE HANDLE.
COORDINATE OS GPM NON
NA
__
, /f
1
/f
ti
/i
WITH COUNTERTOP
BY ARCHITECT
'PW2125 -WC
CHAIR USE
AERATOR FLOW CONTROL
BY ARCHITECT PRIOR
DEVICE WITH MFGR.
TO FAUCET PURCHASE
JUST - (STAFF)
'SL-ADA-
SINGLE COMP.
PROWRAP
PROWRAP •PW2150
CHICAGO FAUCET
P -20A
S.S. SINK
2019-A -GR
(S.S.) 18 GAUGE
14' X 16' X 61/2
McGUIRE
EPW1151WC
H -2165
It /2 P -TRAP OFFSET
8786- GN2FCCP
NA
--
yf
'/f
tyf
ADA
SELF- RIMMING
OFFSET STRAINER
FOR WHEEL CHAIR USE
(1.5 GPM)
JUST - (STAFF)
'SL -ADA-
SINGLE COMP.
PROWRAP
PROWRAP OPW2150
CHICAGO FAUCET
ZURN 'Z -1236
P -20B
S.S. SINK
2019 -A -GR
(S.S.) 18 GAUGE
14• X 16' X 61/2
McGUIRE
■PWI152WC
H-2165
11/2 P -TRAP OFFSET
0786- GN2FCCP
WITH 11' LONG
--
'/f
'/i
I' /i
ADA
SELF - RIMMING
OFFSET STRAINER
FOR WHEEL CHAIR USE
(1.5 GPM)
ARM
P -34
STERN - WILLIAM
SB- 900 -BP
WITH STAINLESS
STEEL CAP & 3'
24' X 24' X 12'
GUARDIAN
EYE WASH/
DRENCH HOSE
NA
NA
CHICAGO FAUCET
NA
__
I/2
I/f
3.
STAINLESS STEEL
FLOOR BASIN
CHROME DRAIN.
G50468P
'897 -CP
BACK PANEL
DOUBLE COMPARTMENT SCRUB SINK WITH KNEE CONTROLS.
COORDINATE FLOOR
P -26B
OWNER FURNISHED CONTRACTOR INSTALLED.
H -2165
12)'8912
NA
ZURN 21236 -WS
__
(2) yf
(2) '/1
(2)11&
MOUNTED CARRIER WITH
HJCT ED. 8018
McGUIRE
NA
11/2 P -TRAPS
FINAL OWNER SELECTION.
P -42
SHOWER TILE
ZURN
NA
NA
WITH INTREGRAL
NA
SYMMONS
•l- 1170VT- H401 -V -X -830
NA
--
'/i
'/f
A A. PROVIDE ALSONS
0476PK FOR VOLUME
SPEC BY ARCH.
ZN415 -B
NA
NA
STOPS
SET TO 1.5 GPM WITH
2'
CONTROL OF HAND
30' SLOE BAR
SHOWER.
SIZE AS REQUIRED TO
P -58
P.P.P. PRIME -RITE
PR -500
NA
NA
NA
NA
NA
NA
NA
NA
""
, /z
--
-"
SERVE NUMBER OF
TRAP PRIMER
DRAIN
P -62B
CHICAGO FAUCET
MODEL 9952 -CP
HOSE BIBB
NA
NA
NA
NA
NA
NA
NA
y2
__
--
NA
NOTES:
I. INSTALLATION OF FIXTURES SHALL BE FULLY COORDINATED WITH GRAB BARS. PROVIDE FLUSH VALVES WITH OFFSETS AS REQUIRED.
2. PROVIDE SYMMONS THERMOSTATIC MIXING VALVE 85-210-CK 1/2 GPM MIN. 2 GPM MAX ON P -13A. P -14. P -20A &', P -20B FAUCETS. SET AT 110'F. SEE DETAILS. INSTALL PER MANUFACTURERS WRITTEN INSTRUCTIONS.
3. CONTRACTOR SHALL PROVIDE ALL REOUIRED MATERIAL FOR A COMPLETE INSTALLATION OF THE PLUMBING FIXTURES INCLUDING ANY GROUT AS REOUIRED AT WALL HUNG FIXTURES. COORDINATE WITH ARCHITECT FOR SPECIFIC GROUT REQUIREMENTS.
OWNER FURNISHED EQUIPMENT
(CONTRACTOR SHALL COORDINATE ALL PLUMBING REQUIREMENTS WITH FINAL OWNER FURNISHED EQUIPMENT BROCHURE)
HJCT
EOUWENT NO.
EOLO MENT
VENDOR NO.
LOCATION
OISCRPTIN
C.IL
ILI.
DL
CA
BASTE
REMARKS
OFCI EOUIPMENT BOOM
ZN- 415 -6B -P
(002. (DA. (3)V. (3)SL
GENERAL DELIVERY ROOM. CA OPERATES
ZURN
TRAP PRIMER
NON
THE BRAKING SYSTEM.
PROVIDE •GUY GREY• FIRE RATED METAL WHITE PONDER COATED WALL BOX WITH
006
FD-2
SEE PLANS
COFFEE MAKER
O
-
-
-
-
SHUTOFF VALVE MODEL •FRM1812S. COORDINATE MOUNTING HEIGHT WITH EOUIPMENT.
LINE PRESSURE ALARM PANEL
1
(1)02. (1)N20. (DA, (I)V. (i)CA.
(3)SPARE
NURSE'S STATION
ZURN R DRAM
'Z550 -G -P
GALVANIZED CAST
IRON
AS SHOWN
9• DOA. MEDIUM DUTY
COORDINATE INSTALLATION OF EOUIPMENT WGR. RECOMMENDED FILTER AND WATTS
INSTRUMENT
DRAIN WITH TRAP PRIMER
RECEIVER. PROVIDE
CAST IRON
SO-2 BACKFLOW PREVENTER BETWEEN SHUTOFF VALVE AND EOUIPMENT
MIN V AF.F
HD-1
-- - ---
-----------
HUB DRAIN
3'
MECH. ROOMS
CONNECTOR.
AIR DRYERS 120V.
Y' FIRE RATED AL WHITE WALL X NI H
72 OB NOISE
SHUTOFF VALVE MODEL •FRM1812S. COORDINATE MOUNTING HEIGHT WITH EOUPMENT.
0088
SEE
�/{
-
-
COORDINATE INSTALLATION OF EOLIPMENT MIFGR.RECOMMENDED FILTER AND WATTS
SO -2 BACKFLOW PREVENTER BETWEEN SHUTOFF VALVE AND EOUPMENT
CONNECTOR.
PROVIDE SHUTOFF VALVE (ACCESSIBLE PER EO.MANUF.GUIDELINES) AND UNION AT
EACH UTILITY SUPPLY CON)ECTKOL PROVIDE WATTS 009 RPBP AND SHUTOFF
034
SEE PLANS
FLASH STERILIZER
-
'/f
'W
PROVIDE DEARBORN BRASS •814 BRANCH TAIL PIECE WITH SIDE INLET. INSTALL
IN SINK ADJACENT TO STERILIZER.& ROUTE WASTE FROM STERILIZER TO
CONNECTION OF TAILPIECE. PROVIDE WITH AR GAP FITTING. ROUTE WASTE FROM
RPBP TO SPILL OVER MOP SINK IN ADJACENT ROOM WITH CHROME PLATED
ESCUTCHEON AT CEILING PENETRATION.
GENERAL NOTES.
I. PPE SIZES SHOWN ARE CONNECTION SIZES AT EOUIPMENT. BRANCH LINES TO EOUIPMENT SHALL BE ONE PPE SIZE LARGER THAN EOUIPMENT CONNECTION SIZE UNLESS OTHERWISE
NOTED ON PLANS.
2. ALL STERLIZNG EQUIPMENT AND ASSOCIATED COMPONENTS TO BE INSTALLED BY THE EOUIPMENT SUPPLIER.
3. SEE MEDICAL GAS SCHEDULE FOR MEDICAL GAS OWNER FURNISHED EOUPMENT.
4. PROVIDE BACKFLOW PREVENTER AT EACH CONNECTION OF POTABLE WATER TO EOUIPMENT N ACCORDANCE WITH FBC 2007. SECTION 608.
S. PROVIDE SHOCK ABSORBERS AT ALL CW & HW EOUIPMENT CONNECTIONS.
L SEE EOUIPMENT DRAWINGS FOR LOCATIONS OF EOUIPMENT.
T. COORDINATE INSTALLATION OF FILTERS WITH CASEWORK AND EOUPMENT.PROVIDE CLEARANCES TO ALLOW FILTER SERVICE PER FILTER MFGR.
L PROVIDE PRESSURE REGULATOR AT EACH EOUIPMENT CONNECTION AS REOUIRED TO REDUCE INLET PRESSURES TO MANUFACTURER GUIDELINES.
9. NOT WATER TEMPERATURE IS 120• F. UNLESS OTHERWISE NOTED.
10. COORDINATE ALL EOUPMENT SERVICE CONNECTIONS AND THEIR ROUGH -N LOCATIONS WITH FINAL VENDOR EOUIPMENT DRAWINGS. REPORT ANY DISCREPANCIES WITH ARCH/ENGR.
11. PROVIDE SHUT OFF VALVE AT ALL SERVICE CONNECTORS TO EACH PIECE OF EOUIPMENT.
MEDICAL GAS SCHEDULE
SYMBOL
DESCRIPTION
HJCT
EQUIP, N0.
EQUIPPED WITH
REMARKS
O
ZONE VALVE BOX
I
1 /ZCA. /202.1 /¢N20.3 / ;A.1' / ;V
GENERAL DELIVERY ROOM
0
OFCI EOUIPMENT BOOM
ZN- 415 -6B -P
(002. (DA. (3)V. (3)SL
GENERAL DELIVERY ROOM. CA OPERATES
ZURN
TRAP PRIMER
NON
THE BRAKING SYSTEM.
OC
OFCI ANESTHESIA BOOM
FD-2
12)02. (I)N20. (DA, (3)V. (I)WAGD.
(3)SL
GENERAL DELIVERY ROOM. FRICTION BRAKES.
O
WALL OUTLETS
9"M HEAVY DUTY
(3)02. (3)A. (3)V. (3)SL
GENERAL DELIVERY ROOM (BASSINET)
O
LINE PRESSURE ALARM PANEL
1
(1)02. (1)N20. (DA, (I)V. (i)CA.
(3)SPARE
NURSE'S STATION
NOTES:
1• CONTRACTOR SHALL PROVIDE PERMANENTLY ENGRAVED LABELS AT ALL ZONE VALVE BOXES AND ALARM PANELS IDENTIFIED
ABOVE IN SCHEDULE, TO INDICATE SPECIFIC ROOMS SERVED. COORDINATE LABELING WITH FINAL ROOM NAMES AND NUMBERS,
AND AREA SERVED WITH HOSPITAL. NOTE ALARM PANEL ALSO SERVES EXISTING C- SECTION ROOMS.
2. PROVIDE PERMANENT ENGRAVED LABELS AT ALL ALARM PANELS, IDENTIFIED ABOVE IN SCHEDULE, INDICATING ELECTRICAL
LIFE SAFETY CIRCUIT FEE ING ALARM PANEL.
3. CONTRACTOR SHALL COORDINATE INSTALLATION OF BOOM MANUFACTURER FURNISHED CAS
/VACUUM RISERS AND RISER BRACKET PER BOOM MANUFACTURER
GUIDELINES. COORDINATE PIPE ROUTING WITH CEILING ACCESS PANELS TO ALLOW ACCESSIBILTY. EOUIPMENT BOOM HAS PNEUMATIC BKAKES; COORDINATE
PRESSURE REGULATING VALVE (VFCOINSTALLATION AND PRESSURE SETTING WITH BOOM MANUFACTURER. ..
PLUMBING DRAIN SCHEDULE
SYMBOL
ITEM
WASTE
REMARKS
MANUFACTURER
MODEL
TYPE
H.P.
DESCRp•
EACH
FD -1
ZURN
FLOOR DRAIN
ZN- 415 -6B -P
POLISHED NICKEL
BRONZE TOP
AS SHOWN
IN PLAN
ZURN
TRAP PRIMER
NON
P- OPTION
FD-2
ZURN R DRAIN
'Z520 -G -P
I GALVANIZED CAST
ANTS SHOWN
PLAN
9"M HEAVY DUTY
HIGH PRESSURE
DRAIN WITH TRAP PRIMER
FD -3
ZURN R DRAM
'Z550 -G -P
GALVANIZED CAST
IRON
AS SHOWN
9• DOA. MEDIUM DUTY
DUPLEX PUMP
PKG W/ 80 GAL
INSTRUMENT
DRAIN WITH TRAP PRIMER
RECEIVER. PROVIDE
CAST IRON
MIN V AF.F
HD-1
-- - ---
-----------
HUB DRAIN
3'
MECH. ROOMS
OMPRESSED
AIR EQUIPMENT SCHEDULE
ITEM
MANUFACTURER
S.C.F.M.O
145 Psig
VOLTAGE
H.P.
DESCRp•
EACH
TOTAL
EACH
TOTAL
& MODEL NO.
NON
MEDICAL AIR
POWEREX
HIGH PRESSURE
COMPRESSOR
NICU O.R.
MSD- MT- 0503HP
SCROLL TYPE
12.5
12.5
460
5
10
DUPLEX PUMP
PKG W/ 80 GAL
INSTRUMENT
RECEIVER. PROVIDE
AIR
W/ (2) DESICCANT
AIR DRYERS 120V.
72 OB NOISE
LEVEL
NOTE: 1. TOTAL COMPRESSED AIR SCFM IS BASED ON I OF 2 COMPRESSORS RUNNING.
2. AIR COMPRESSOR CONTROL PANEL SHALL HAVE CAPABILITY
TO MONITOR LOCAL ALARM POINTS AS REOUIRED BY NFPA 99.
3. PROVIDE WITH AUTOMATIC RESET UPON LOSS OF POWER.
4. PROVIDE WITH DRY CONTACTS FOR CO. DEW POINT, GENERAL FAULT HAT AND LOG IN USE ALARM.
IMAI
11
1