12-509-030Ot IF FSD DAMPER ACTUATORS END SWITCH SHALL BE WIRED TO EXHAUST FAN STARTER INTERLOCK RELAY. WIRE SAFETY CIRCUIT SO EXHAUST FAN WILL OPERATE ONLY IF FSD ARE OPEN. DETAIL MC FSD EF NC EXHAUST FAN EXHAUST FAN The DDC system uses a differential pressure switch to monitor the exhaust fan status and shall provide and alarm if the fan fails during the occupied mode. Interlock all associated Fire /Smoke dampers with the exhaust fan. Dampers shall open when fan is running and close when fan is shut down manually, through the interlock or if the fan fails. If exhaust fan is associated with an air handling unit (AHU) the exhaust fan shall be interlocked with the AHU starter to run when the AHU is energized and shutdown when the AHU de- energizes. EXHAUST FAN APOGEE 540 110 t L t t R .t R R It 1,2di1ii i sIin n n I I G 24 VAC 2 V -1 14 GAGE 0 5881 DOB CBL -1 LAN TRIM( 3 24 GAGE TSP 8 540 680FA e TTE -1 HTE -1 HWR 55/95 •F HVS 48' AFF DEG F SA INSTALLATION NOTES: O7 TEC -1 TO BE MOUNTED AT SITE BY SIEMENS. 2O REFER TO BUILDING POWER TRUNK DRAWING FOR 24 VAC POWER. O3 REPLACE EXISTING PNEUMATIC THERMOSTAT, PROVIDE HUMIDITY SENSOR OPERATING ROOMS ONLY. 4O VALVE INSTALLED BY OTHERS. NOTES: 1. OPERATING ROOM TEMPERATURE SET POINT 68 "F WITH SET POINT DIAL ENABLED. SET POINTS LOWER THAN 68•F SHALL BE LOCKED OUT. 2. CONVERT DUCT MOUNTED REHEAT COILS ASSOCIATED WITH SMH-6 FROM PNEUMATIC CONTROL TO DDC, INCLUDING CONTROL VALVE CHANGE OUT TO A 2 —WAY MODULATING VALVE AND REPLACING WALL MOUNTED PNEUMATIC TEMPERATURE SENSOR WITH DDC TEMPERATURE SENSOR. LOCAL AND REMOTE BAS CONTROL AND MONITORING. 3. PROVIDE A WALL MOUNTED HUMIDITY SENSOR IN OPERATING ROOM FOR BAS MONITORING. DUCT MOUNTED REHEAT COIL A 544 339 TTE -3 538 891 — 40/240 eF HTE -1 A01RAT 0 /100 PCT RH 0 PTNAME DETAIL MR 0 DETAIL MF 1.01 000 5 BY OTHERS 24 VAC Q2 q SD -1 A01SSD 1 ETAILMC 544 339 TTE -1 —40/240* F A01RAT AOIOAD 0 DETAIL MR DETAIL MN AP22297 000 -I � I OA �HEIGHTJ D -2 269 062 WIDTH NC SPP -1 tH L} ZZZ U _ A01 A01CCV 141 0574 0 DPS -1 DETAIL MN 24 VAC IN WC A01FIL 0 DETAIL MC O 6 536 774 TTE -5 INSTALLATION NOTES: OSEE WIRING DETAIL ON ELECTRICAL DRAWING. FSD RA O NC 3 CONTROL TRANSFORMERS AND RELAYS MOUNTED IN COMPONENT PANEL, OPROVIDE WIRING CONTACTS PER ELECTRICAL DRAWING OSMOKE DETECTOR PROVIDED. MOUNTED. AND WIRED BY DIVISION 16. OCOMMON TEMPERATURE SENSOR, TO BE LOCATED IN MECHANICAL ROOM. OINTERLOCK ASSOCIATED EXHAUST FANS 141 0518 O INTERLOCK ASSOCIATED FIRE /SMOKE DAMPERS 544 339 DPS -4 TTE -2 1.5IN WG - 40/240 'F AOiSAF 0 A01SAT 0 DETAIL MC DETAIL MR 000 L I SF -1 269 062 269 062 0 CFM SPP P -2 SPP -3 0 HP 'AO1SVD 5 0 H L BY OTHERS DETAIL W L H q SD -1 OpQ�d6Y� 141 W4 AO1 SSD 1 VFD -1 DETAIL MC DPSIN WC O 1 DETAIL MC ❑ A01FFL 141 0575 SA_ FETY SHUT DOWN DETAIL MC 4P IN WC 41EZOMETER RING WITH TRANSDUCER INTERFACE 20/70 DEG F PTNAME 6 Q COMPONENT PANEL- 0 36 774 DETAIL MF TTE-6 1/2.' X 3 1/2' NPT 20/70 DEG F 3 PTNAME G CAHUTEM FLOW DIAGRAM 567 35 DETAIL MF CP -1 SMH -6 1/2' X 3 1/2' NPT fl � N U U i The constant volume air handling unit consists of a mixed air section with outdoor a r damper, pre - filter, final filter, chilled water cooling coil and supply fan with VFD. The unit is DDC controlled using electric actuation. The air handling unit is scheduled for automatic operation. The air handling unit operates in Occupied, Unoccupied, and Safety modes as follows (All suggested set points and settings are adjustable.): The an starts or continues to run and the unit is controlled as follows: The outside air damper is open and flow monitor station activated. The VFD will be controlled to maintain a constant volume of air from the fan measured by the Air Flow Measuring station at the fan inlet flow sensor. 2 The cooling coil valve modulates to maintain the coil leaving air temperature set point. t Interlocked exhaust fans will run when the AHU is running and will shut down when the AHU stops. All fire smoke dampers in the exhaust system shall be interlocked with the exhaust fan. End switches shall be wired back to the fan starter to only allow the fan to start once the dampers are open. Fire /Smoke dampers are interlocked to open when the AHU is energized. End switches on the Fire /Smoke dampers will be wired back to the VFD to only allow the AHU to start once the dampers are open. Alarms An alarm willbe generated if the fan status does not match the start /stop of the fan (if fan is commanded on, but status is off, an alarm will be generated). And alarm will be generated if either of the filter DPS's are activated signifying a dirty filter. High supply air temperature or return air humidity shall generate an alarm. Safety Smoke detectors In the supply and return air streams shall be interlocked with the fire alarm system. The fire alarm shall de- energize the supply fan upon activation. All other dampers associated exhaust fans and valves position to their normal is closed or off position after thefan is de- energized. A, pressure switch is installed across the supply fan. The DDC system uses this switch to confirm the fan is In the desired state (i.e. on or off) and generates an alarm If status deviates from DDC start /stop control. A high static pressure switch with manual reset is installed and wired into the VFD safety circuit to shut down the fan if the pressure in the duct becomes too high. 3 AIR HANDLER W nn n �� ono CL of 2 U2 • M J u. p W LLi 0 a: W 0 IL act g =1011111" ui U Q CO Q g FSD SA NC O U 0 z � o w a ILL 0 �~ U g� 0 to Jima o SSR RSmith eckman Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- inc.com Firm Certification- EB-0000857 D -.% D -: PE -5m a J.anLM.wa. PE -== W iidvdA&a+md PE -6&701 SBB JOB s 1382063.0 cc O U Z J Q U_ cc W M T o_o� CC = J O H U- F_ J W Cr) O U CO m o H = W Z — W 0 W ~ CID CO � � ~ Z 0) V CL M 0 QONO m 0) CID Or Comm. No: 11087.00 Date: 01/18/12 Drawn: Revised: OWNER REQUESTED 2/27/12 ��111111/// V '• lb 33 S F — P1.xGk�� 't•.ItI�► M4.1 GCA161.1P AE -1 0-10 VOLTS PTNAME H904 � J EF11 ST � J D 0.90.0.20.1 l EXHAUST FAN The DDC system uses a differential pressure switch to monitor the exhaust fan status and shall provide and alarm if the fan fails during the occupied mode. Interlock all associated Fire /Smoke dampers with the exhaust fan. Dampers shall open when fan is running and close when fan is shut down manually, through the interlock or if the fan fails. If exhaust fan is associated with an air handling unit (AHU) the exhaust fan shall be interlocked with the AHU starter to run when the AHU is energized and shutdown when the AHU de- energizes. EXHAUST FAN APOGEE 540 110 t L t t R .t R R It 1,2di1ii i sIin n n I I G 24 VAC 2 V -1 14 GAGE 0 5881 DOB CBL -1 LAN TRIM( 3 24 GAGE TSP 8 540 680FA e TTE -1 HTE -1 HWR 55/95 •F HVS 48' AFF DEG F SA INSTALLATION NOTES: O7 TEC -1 TO BE MOUNTED AT SITE BY SIEMENS. 2O REFER TO BUILDING POWER TRUNK DRAWING FOR 24 VAC POWER. O3 REPLACE EXISTING PNEUMATIC THERMOSTAT, PROVIDE HUMIDITY SENSOR OPERATING ROOMS ONLY. 4O VALVE INSTALLED BY OTHERS. NOTES: 1. OPERATING ROOM TEMPERATURE SET POINT 68 "F WITH SET POINT DIAL ENABLED. SET POINTS LOWER THAN 68•F SHALL BE LOCKED OUT. 2. CONVERT DUCT MOUNTED REHEAT COILS ASSOCIATED WITH SMH-6 FROM PNEUMATIC CONTROL TO DDC, INCLUDING CONTROL VALVE CHANGE OUT TO A 2 —WAY MODULATING VALVE AND REPLACING WALL MOUNTED PNEUMATIC TEMPERATURE SENSOR WITH DDC TEMPERATURE SENSOR. LOCAL AND REMOTE BAS CONTROL AND MONITORING. 3. PROVIDE A WALL MOUNTED HUMIDITY SENSOR IN OPERATING ROOM FOR BAS MONITORING. DUCT MOUNTED REHEAT COIL A 544 339 TTE -3 538 891 — 40/240 eF HTE -1 A01RAT 0 /100 PCT RH 0 PTNAME DETAIL MR 0 DETAIL MF 1.01 000 5 BY OTHERS 24 VAC Q2 q SD -1 A01SSD 1 ETAILMC 544 339 TTE -1 —40/240* F A01RAT AOIOAD 0 DETAIL MR DETAIL MN AP22297 000 -I � I OA �HEIGHTJ D -2 269 062 WIDTH NC SPP -1 tH L} ZZZ U _ A01 A01CCV 141 0574 0 DPS -1 DETAIL MN 24 VAC IN WC A01FIL 0 DETAIL MC O 6 536 774 TTE -5 INSTALLATION NOTES: OSEE WIRING DETAIL ON ELECTRICAL DRAWING. FSD RA O NC 3 CONTROL TRANSFORMERS AND RELAYS MOUNTED IN COMPONENT PANEL, OPROVIDE WIRING CONTACTS PER ELECTRICAL DRAWING OSMOKE DETECTOR PROVIDED. MOUNTED. AND WIRED BY DIVISION 16. OCOMMON TEMPERATURE SENSOR, TO BE LOCATED IN MECHANICAL ROOM. OINTERLOCK ASSOCIATED EXHAUST FANS 141 0518 O INTERLOCK ASSOCIATED FIRE /SMOKE DAMPERS 544 339 DPS -4 TTE -2 1.5IN WG - 40/240 'F AOiSAF 0 A01SAT 0 DETAIL MC DETAIL MR 000 L I SF -1 269 062 269 062 0 CFM SPP P -2 SPP -3 0 HP 'AO1SVD 5 0 H L BY OTHERS DETAIL W L H q SD -1 OpQ�d6Y� 141 W4 AO1 SSD 1 VFD -1 DETAIL MC DPSIN WC O 1 DETAIL MC ❑ A01FFL 141 0575 SA_ FETY SHUT DOWN DETAIL MC 4P IN WC 41EZOMETER RING WITH TRANSDUCER INTERFACE 20/70 DEG F PTNAME 6 Q COMPONENT PANEL- 0 36 774 DETAIL MF TTE-6 1/2.' X 3 1/2' NPT 20/70 DEG F 3 PTNAME G CAHUTEM FLOW DIAGRAM 567 35 DETAIL MF CP -1 SMH -6 1/2' X 3 1/2' NPT fl � N U U i The constant volume air handling unit consists of a mixed air section with outdoor a r damper, pre - filter, final filter, chilled water cooling coil and supply fan with VFD. The unit is DDC controlled using electric actuation. The air handling unit is scheduled for automatic operation. The air handling unit operates in Occupied, Unoccupied, and Safety modes as follows (All suggested set points and settings are adjustable.): The an starts or continues to run and the unit is controlled as follows: The outside air damper is open and flow monitor station activated. The VFD will be controlled to maintain a constant volume of air from the fan measured by the Air Flow Measuring station at the fan inlet flow sensor. 2 The cooling coil valve modulates to maintain the coil leaving air temperature set point. t Interlocked exhaust fans will run when the AHU is running and will shut down when the AHU stops. All fire smoke dampers in the exhaust system shall be interlocked with the exhaust fan. End switches shall be wired back to the fan starter to only allow the fan to start once the dampers are open. Fire /Smoke dampers are interlocked to open when the AHU is energized. End switches on the Fire /Smoke dampers will be wired back to the VFD to only allow the AHU to start once the dampers are open. Alarms An alarm willbe generated if the fan status does not match the start /stop of the fan (if fan is commanded on, but status is off, an alarm will be generated). And alarm will be generated if either of the filter DPS's are activated signifying a dirty filter. High supply air temperature or return air humidity shall generate an alarm. Safety Smoke detectors In the supply and return air streams shall be interlocked with the fire alarm system. The fire alarm shall de- energize the supply fan upon activation. All other dampers associated exhaust fans and valves position to their normal is closed or off position after thefan is de- energized. A, pressure switch is installed across the supply fan. The DDC system uses this switch to confirm the fan is In the desired state (i.e. on or off) and generates an alarm If status deviates from DDC start /stop control. A high static pressure switch with manual reset is installed and wired into the VFD safety circuit to shut down the fan if the pressure in the duct becomes too high. 3 AIR HANDLER W nn n �� ono CL of 2 U2 • M J u. p W LLi 0 a: W 0 IL act g =1011111" ui U Q CO Q g FSD SA NC O U 0 z � o w a ILL 0 �~ U g� 0 to Jima o SSR RSmith eckman Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- inc.com Firm Certification- EB-0000857 D -.% D -: PE -5m a J.anLM.wa. PE -== W iidvdA&a+md PE -6&701 SBB JOB s 1382063.0 cc O U Z J Q U_ cc W M T o_o� CC = J O H U- F_ J W Cr) O U CO m o H = W Z — W 0 W ~ CID CO � � ~ Z 0) V CL M 0 QONO m 0) CID Or Comm. No: 11087.00 Date: 01/18/12 Drawn: Revised: OWNER REQUESTED 2/27/12 ��111111/// V '• lb 33 S F — P1.xGk�� 't•.ItI�► M4.1 I I G 24 VAC 2 V -1 14 GAGE 0 5881 DOB CBL -1 LAN TRIM( 3 24 GAGE TSP 8 540 680FA e TTE -1 HTE -1 HWR 55/95 •F HVS 48' AFF DEG F SA INSTALLATION NOTES: O7 TEC -1 TO BE MOUNTED AT SITE BY SIEMENS. 2O REFER TO BUILDING POWER TRUNK DRAWING FOR 24 VAC POWER. O3 REPLACE EXISTING PNEUMATIC THERMOSTAT, PROVIDE HUMIDITY SENSOR OPERATING ROOMS ONLY. 4O VALVE INSTALLED BY OTHERS. NOTES: 1. OPERATING ROOM TEMPERATURE SET POINT 68 "F WITH SET POINT DIAL ENABLED. SET POINTS LOWER THAN 68•F SHALL BE LOCKED OUT. 2. CONVERT DUCT MOUNTED REHEAT COILS ASSOCIATED WITH SMH-6 FROM PNEUMATIC CONTROL TO DDC, INCLUDING CONTROL VALVE CHANGE OUT TO A 2 —WAY MODULATING VALVE AND REPLACING WALL MOUNTED PNEUMATIC TEMPERATURE SENSOR WITH DDC TEMPERATURE SENSOR. LOCAL AND REMOTE BAS CONTROL AND MONITORING. 3. PROVIDE A WALL MOUNTED HUMIDITY SENSOR IN OPERATING ROOM FOR BAS MONITORING. DUCT MOUNTED REHEAT COIL A 544 339 TTE -3 538 891 — 40/240 eF HTE -1 A01RAT 0 /100 PCT RH 0 PTNAME DETAIL MR 0 DETAIL MF 1.01 000 5 BY OTHERS 24 VAC Q2 q SD -1 A01SSD 1 ETAILMC 544 339 TTE -1 —40/240* F A01RAT AOIOAD 0 DETAIL MR DETAIL MN AP22297 000 -I � I OA �HEIGHTJ D -2 269 062 WIDTH NC SPP -1 tH L} ZZZ U _ A01 A01CCV 141 0574 0 DPS -1 DETAIL MN 24 VAC IN WC A01FIL 0 DETAIL MC O 6 536 774 TTE -5 INSTALLATION NOTES: OSEE WIRING DETAIL ON ELECTRICAL DRAWING. FSD RA O NC 3 CONTROL TRANSFORMERS AND RELAYS MOUNTED IN COMPONENT PANEL, OPROVIDE WIRING CONTACTS PER ELECTRICAL DRAWING OSMOKE DETECTOR PROVIDED. MOUNTED. AND WIRED BY DIVISION 16. OCOMMON TEMPERATURE SENSOR, TO BE LOCATED IN MECHANICAL ROOM. OINTERLOCK ASSOCIATED EXHAUST FANS 141 0518 O INTERLOCK ASSOCIATED FIRE /SMOKE DAMPERS 544 339 DPS -4 TTE -2 1.5IN WG - 40/240 'F AOiSAF 0 A01SAT 0 DETAIL MC DETAIL MR 000 L I SF -1 269 062 269 062 0 CFM SPP P -2 SPP -3 0 HP 'AO1SVD 5 0 H L BY OTHERS DETAIL W L H q SD -1 OpQ�d6Y� 141 W4 AO1 SSD 1 VFD -1 DETAIL MC DPSIN WC O 1 DETAIL MC ❑ A01FFL 141 0575 SA_ FETY SHUT DOWN DETAIL MC 4P IN WC 41EZOMETER RING WITH TRANSDUCER INTERFACE 20/70 DEG F PTNAME 6 Q COMPONENT PANEL- 0 36 774 DETAIL MF TTE-6 1/2.' X 3 1/2' NPT 20/70 DEG F 3 PTNAME G CAHUTEM FLOW DIAGRAM 567 35 DETAIL MF CP -1 SMH -6 1/2' X 3 1/2' NPT fl � N U U i The constant volume air handling unit consists of a mixed air section with outdoor a r damper, pre - filter, final filter, chilled water cooling coil and supply fan with VFD. The unit is DDC controlled using electric actuation. The air handling unit is scheduled for automatic operation. The air handling unit operates in Occupied, Unoccupied, and Safety modes as follows (All suggested set points and settings are adjustable.): The an starts or continues to run and the unit is controlled as follows: The outside air damper is open and flow monitor station activated. The VFD will be controlled to maintain a constant volume of air from the fan measured by the Air Flow Measuring station at the fan inlet flow sensor. 2 The cooling coil valve modulates to maintain the coil leaving air temperature set point. t Interlocked exhaust fans will run when the AHU is running and will shut down when the AHU stops. All fire smoke dampers in the exhaust system shall be interlocked with the exhaust fan. End switches shall be wired back to the fan starter to only allow the fan to start once the dampers are open. Fire /Smoke dampers are interlocked to open when the AHU is energized. End switches on the Fire /Smoke dampers will be wired back to the VFD to only allow the AHU to start once the dampers are open. Alarms An alarm willbe generated if the fan status does not match the start /stop of the fan (if fan is commanded on, but status is off, an alarm will be generated). And alarm will be generated if either of the filter DPS's are activated signifying a dirty filter. High supply air temperature or return air humidity shall generate an alarm. Safety Smoke detectors In the supply and return air streams shall be interlocked with the fire alarm system. The fire alarm shall de- energize the supply fan upon activation. All other dampers associated exhaust fans and valves position to their normal is closed or off position after thefan is de- energized. A, pressure switch is installed across the supply fan. The DDC system uses this switch to confirm the fan is In the desired state (i.e. on or off) and generates an alarm If status deviates from DDC start /stop control. A high static pressure switch with manual reset is installed and wired into the VFD safety circuit to shut down the fan if the pressure in the duct becomes too high. 3 AIR HANDLER W nn n �� ono CL of 2 U2 • M J u. p W LLi 0 a: W 0 IL act g =1011111" ui U Q CO Q g FSD SA NC O U 0 z � o w a ILL 0 �~ U g� 0 to Jima o SSR RSmith eckman Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- inc.com Firm Certification- EB-0000857 D -.% D -: PE -5m a J.anLM.wa. PE -== W iidvdA&a+md PE -6&701 SBB JOB s 1382063.0 cc O U Z J Q U_ cc W M T o_o� CC = J O H U- F_ J W Cr) O U CO m o H = W Z — W 0 W ~ CID CO � � ~ Z 0) V CL M 0 QONO m 0) CID Or Comm. No: 11087.00 Date: 01/18/12 Drawn: Revised: OWNER REQUESTED 2/27/12 ��111111/// V '• lb 33 S F — P1.xGk�� 't•.ItI�► M4.1 5 BY OTHERS 24 VAC Q2 q SD -1 A01SSD 1 ETAILMC 544 339 TTE -1 —40/240* F A01RAT AOIOAD 0 DETAIL MR DETAIL MN AP22297 000 -I � I OA �HEIGHTJ D -2 269 062 WIDTH NC SPP -1 tH L} ZZZ U _ A01 A01CCV 141 0574 0 DPS -1 DETAIL MN 24 VAC IN WC A01FIL 0 DETAIL MC O 6 536 774 TTE -5 INSTALLATION NOTES: OSEE WIRING DETAIL ON ELECTRICAL DRAWING. FSD RA O NC 3 CONTROL TRANSFORMERS AND RELAYS MOUNTED IN COMPONENT PANEL, OPROVIDE WIRING CONTACTS PER ELECTRICAL DRAWING OSMOKE DETECTOR PROVIDED. MOUNTED. AND WIRED BY DIVISION 16. OCOMMON TEMPERATURE SENSOR, TO BE LOCATED IN MECHANICAL ROOM. OINTERLOCK ASSOCIATED EXHAUST FANS 141 0518 O INTERLOCK ASSOCIATED FIRE /SMOKE DAMPERS 544 339 DPS -4 TTE -2 1.5IN WG - 40/240 'F AOiSAF 0 A01SAT 0 DETAIL MC DETAIL MR 000 L I SF -1 269 062 269 062 0 CFM SPP P -2 SPP -3 0 HP 'AO1SVD 5 0 H L BY OTHERS DETAIL W L H q SD -1 OpQ�d6Y� 141 W4 AO1 SSD 1 VFD -1 DETAIL MC DPSIN WC O 1 DETAIL MC ❑ A01FFL 141 0575 SA_ FETY SHUT DOWN DETAIL MC 4P IN WC 41EZOMETER RING WITH TRANSDUCER INTERFACE 20/70 DEG F PTNAME 6 Q COMPONENT PANEL- 0 36 774 DETAIL MF TTE-6 1/2.' X 3 1/2' NPT 20/70 DEG F 3 PTNAME G CAHUTEM FLOW DIAGRAM 567 35 DETAIL MF CP -1 SMH -6 1/2' X 3 1/2' NPT fl � N U U i The constant volume air handling unit consists of a mixed air section with outdoor a r damper, pre - filter, final filter, chilled water cooling coil and supply fan with VFD. The unit is DDC controlled using electric actuation. The air handling unit is scheduled for automatic operation. The air handling unit operates in Occupied, Unoccupied, and Safety modes as follows (All suggested set points and settings are adjustable.): The an starts or continues to run and the unit is controlled as follows: The outside air damper is open and flow monitor station activated. The VFD will be controlled to maintain a constant volume of air from the fan measured by the Air Flow Measuring station at the fan inlet flow sensor. 2 The cooling coil valve modulates to maintain the coil leaving air temperature set point. t Interlocked exhaust fans will run when the AHU is running and will shut down when the AHU stops. All fire smoke dampers in the exhaust system shall be interlocked with the exhaust fan. End switches shall be wired back to the fan starter to only allow the fan to start once the dampers are open. Fire /Smoke dampers are interlocked to open when the AHU is energized. End switches on the Fire /Smoke dampers will be wired back to the VFD to only allow the AHU to start once the dampers are open. Alarms An alarm willbe generated if the fan status does not match the start /stop of the fan (if fan is commanded on, but status is off, an alarm will be generated). And alarm will be generated if either of the filter DPS's are activated signifying a dirty filter. High supply air temperature or return air humidity shall generate an alarm. Safety Smoke detectors In the supply and return air streams shall be interlocked with the fire alarm system. The fire alarm shall de- energize the supply fan upon activation. All other dampers associated exhaust fans and valves position to their normal is closed or off position after thefan is de- energized. A, pressure switch is installed across the supply fan. The DDC system uses this switch to confirm the fan is In the desired state (i.e. on or off) and generates an alarm If status deviates from DDC start /stop control. A high static pressure switch with manual reset is installed and wired into the VFD safety circuit to shut down the fan if the pressure in the duct becomes too high. 3 AIR HANDLER W nn n �� ono CL of 2 U2 • M J u. p W LLi 0 a: W 0 IL act g =1011111" ui U Q CO Q g FSD SA NC O U 0 z � o w a ILL 0 �~ U g� 0 to Jima o SSR RSmith eckman Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- inc.com Firm Certification- EB-0000857 D -.% D -: PE -5m a J.anLM.wa. PE -== W iidvdA&a+md PE -6&701 SBB JOB s 1382063.0 cc O U Z J Q U_ cc W M T o_o� CC = J O H U- F_ J W Cr) O U CO m o H = W Z — W 0 W ~ CID CO � � ~ Z 0) V CL M 0 QONO m 0) CID Or Comm. No: 11087.00 Date: 01/18/12 Drawn: Revised: OWNER REQUESTED 2/27/12 ��111111/// V '• lb 33 S F — P1.xGk�� 't•.ItI�► M4.1 20/70 DEG F PTNAME 6 Q COMPONENT PANEL- 0 36 774 DETAIL MF TTE-6 1/2.' X 3 1/2' NPT 20/70 DEG F 3 PTNAME G CAHUTEM FLOW DIAGRAM 567 35 DETAIL MF CP -1 SMH -6 1/2' X 3 1/2' NPT fl � N U U i The constant volume air handling unit consists of a mixed air section with outdoor a r damper, pre - filter, final filter, chilled water cooling coil and supply fan with VFD. The unit is DDC controlled using electric actuation. The air handling unit is scheduled for automatic operation. The air handling unit operates in Occupied, Unoccupied, and Safety modes as follows (All suggested set points and settings are adjustable.): The an starts or continues to run and the unit is controlled as follows: The outside air damper is open and flow monitor station activated. The VFD will be controlled to maintain a constant volume of air from the fan measured by the Air Flow Measuring station at the fan inlet flow sensor. 2 The cooling coil valve modulates to maintain the coil leaving air temperature set point. t Interlocked exhaust fans will run when the AHU is running and will shut down when the AHU stops. All fire smoke dampers in the exhaust system shall be interlocked with the exhaust fan. End switches shall be wired back to the fan starter to only allow the fan to start once the dampers are open. Fire /Smoke dampers are interlocked to open when the AHU is energized. End switches on the Fire /Smoke dampers will be wired back to the VFD to only allow the AHU to start once the dampers are open. Alarms An alarm willbe generated if the fan status does not match the start /stop of the fan (if fan is commanded on, but status is off, an alarm will be generated). And alarm will be generated if either of the filter DPS's are activated signifying a dirty filter. High supply air temperature or return air humidity shall generate an alarm. Safety Smoke detectors In the supply and return air streams shall be interlocked with the fire alarm system. The fire alarm shall de- energize the supply fan upon activation. All other dampers associated exhaust fans and valves position to their normal is closed or off position after thefan is de- energized. A, pressure switch is installed across the supply fan. The DDC system uses this switch to confirm the fan is In the desired state (i.e. on or off) and generates an alarm If status deviates from DDC start /stop control. A high static pressure switch with manual reset is installed and wired into the VFD safety circuit to shut down the fan if the pressure in the duct becomes too high. 3 AIR HANDLER W nn n �� ono CL of 2 U2 • M J u. p W LLi 0 a: W 0 IL act g =1011111" ui U Q CO Q g FSD SA NC O U 0 z � o w a ILL 0 �~ U g� 0 to Jima o SSR RSmith eckman Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- inc.com Firm Certification- EB-0000857 D -.% D -: PE -5m a J.anLM.wa. PE -== W iidvdA&a+md PE -6&701 SBB JOB s 1382063.0 cc O U Z J Q U_ cc W M T o_o� CC = J O H U- F_ J W Cr) O U CO m o H = W Z — W 0 W ~ CID CO � � ~ Z 0) V CL M 0 QONO m 0) CID Or Comm. No: 11087.00 Date: 01/18/12 Drawn: Revised: OWNER REQUESTED 2/27/12 ��111111/// V '• lb 33 S F — P1.xGk�� 't•.ItI�► M4.1 FSD SA NC O U 0 z � o w a ILL 0 �~ U g� 0 to Jima o SSR RSmith eckman Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- inc.com Firm Certification- EB-0000857 D -.% D -: PE -5m a J.anLM.wa. PE -== W iidvdA&a+md PE -6&701 SBB JOB s 1382063.0 cc O U Z J Q U_ cc W M T o_o� CC = J O H U- F_ J W Cr) O U CO m o H = W Z — W 0 W ~ CID CO � � ~ Z 0) V CL M 0 QONO m 0) CID Or Comm. No: 11087.00 Date: 01/18/12 Drawn: Revised: OWNER REQUESTED 2/27/12 ��111111/// V '• lb 33 S F — P1.xGk�� 't•.ItI�► M4.1 SSR RSmith eckman Reid, Inc. 600 West Hillsboro, Suite 300 Deerfield Beach, FL 33441 (954) 421 -1260 FAX: (954) 421 -1466 www.ssr- inc.com Firm Certification- EB-0000857 D -.% D -: PE -5m a J.anLM.wa. PE -== W iidvdA&a+md PE -6&701 SBB JOB s 1382063.0 cc O U Z J Q U_ cc W M T o_o� CC = J O H U- F_ J W Cr) O U CO m o H = W Z — W 0 W ~ CID CO � � ~ Z 0) V CL M 0 QONO m 0) CID Or Comm. No: 11087.00 Date: 01/18/12 Drawn: Revised: OWNER REQUESTED 2/27/12 ��111111/// V '• lb 33 S F — P1.xGk�� 't•.ItI�► M4.1 Comm. No: 11087.00 Date: 01/18/12 Drawn: Revised: OWNER REQUESTED 2/27/12 ��111111/// V '• lb 33 S F — P1.xGk�� 't•.ItI�► M4.1