12-487-009* * * * * * * * * * * * * * * ** F A U ------------------------------------------------------------------------------- L T A N A L Y S I S S U M M A R Y * * * * * * * * * * * * * ** ------------------------------------------------------------------------------- BUS NAME VOLTAGE AVAILABLE FAULT CURRENT REMARKS L -L AFC (AMPS) AIC (AMPS) 2LSL1 208. 1200 10000 2MCL1 208. 3237 10000 PBX UPS BUS* 208. 2776 10000 CDPA 480. 26033 35000 LSDPA 480. 24174 65000 * * * * * * * * * * * * * * * * * * * * * ** FAULT ANALYSIS REPORT COMPLETED * * * * * * * * * * * * * * * * * * * * * ** NOTE: FAULT CURRENT ANALYSIS WAS TAKEN FROM ORIGINAL COORDINATION & SHORT CIRCUIT STUDY DATED 11/30/2011 PROVIDED BY SMH. * AVAILABLE FAULT CURRENT WAS CALCULATED BASED ON THE TRANSFORMER INFORMATION PROVIDED BY MANUFACTURER. NEW WORK NOTES: A.) THE EQUIPMENT GROUNDING TERMINAL BARS OF THE NORMAL AND EMERGENCY ELECTRICAL. SYSTEM (CRITICAL & LIFE SAFETY) PANELBOARDS THAT SERVE THE SAME PATIENT AREA SHALL BE BONDED TOGETHER WITH AN INSULATED CONTINUOUS COPPER CONDUCTOR NOT SMALLER THAN #8 AWG (N.E.C. ART. 517.14). B.) SEE RISER DIAGRAM FOR FEEDER SIZES. C.) CONTRACTOR SHALL FIELD VERIFY THAT ALL PANELBOARDS SERVING "CRITICAL CARE" AREAS ARE GROUNDED IN ACCORDANCE WITH N.E.C, ART. 517- 19(d), METAL FEEDER RACEWAYS SHALL HAVE GROUNDING BUSHING AND A CONTINUOUS COPPER BONDING JUMPER SIZED IN ACCORDANCE WITH N.E.C. TABLE 250 -95. D.) REFER TO PANELBOARD SCHEDULES FOR REQUIRED PANELBOARD AIC RATINGS. E.) FOR PANEL SHOWN IN THIS SHEET CONTRACTOR SHALL PROVIDE NEW UPDATED TYPE WRITTEN DIRECTORY. F.) ALL CIRCUITS EXISTING AND NEW SHALL HAVE DEDICATED NEUTRAL IN ORDER TO COMPLY WITH NEC ART. 210.4B. 1100 n„ ,f, 4µ 0<1 PDU MB 1;r. <r: } 0 1P. F :Pf :rtf U %2 .,trm lllcfi 11 �� '!� "�;I�..Cjk6 f:.2 i ✓f �i.�F M�.. ti, ��1�7f �f�.,� .'J'<. S. COORDINATION: PBX PDU m TrpF' CUTLER HAMMER (EXISTING) AAMM Qi is FnA WIP VOLTAGE 120/208V, 3 PH, 4W PANEL "2LSL1 AIC ✓ -v 10KAIC MOUNTING SURFACE FED FROM: T -2LSL1 (LIFE SAFETY BRANCH) LOCATION 2ND FL, ELEC, ROOM VOLT AMP POLE TRIP CON DUI WIRE REMARKS CKT. NO. REMARKS CKT. NO. REMARKS WIRE CON DUI TRIP POLE VOLT AMP CON DUI 1 20 VOLT AMP 1 MGAP HEART CENTER 1 M M EXISTING 2 3RD FL. LAB DELIV. MGAP 1 3 5 20 1 PANEL R1CL1 m 1 20 80 3 MGAP HEART CENTER 3 4 3RD FL. LAB DELIV. MGAP EXISTING PBX RECEPTACLE 20 1 80 1 CYSTO 1 20 8 10 12 1 1 MGAP HEART CENTER 5 6 2ND FL. POWER DOORS 3 1 20 1 1 20 1 20 40 7 POWER DOORS HEART CENTER 7 8 2ND FL. F/A PANEL NAC 14 PANEL CH4 20 1 50 70 1 20 20 POWER DOORS HEART CENTER 9 10 2ND FL. HEART MGAP 3 80 20 1 PBX UPS 2ND FLOOR EXISTING 19 21 23 20 22 24 1 20 FACP 11 12 NICU NAC F A PANEL 20 1 3 100 1 20 PANEL 3CH1 55 57 HEART CENTER PROC AUTO DR 13 14 NICU MGAP 20 1 2 1 201 1 HEART CENTER PROC AUTO DR 15 16 NICU 180 MON. 20 1 1 20 HEART CENTER PROC AUTO DR 17 18 NICU POWER DOORS 20 1 20 1 20 PBX RECEPTACLE 63 65 SPARE 19 20 NICU POWER DOORS 20 1 66 SPACE 1 20 SPARE 21 21 22 PBX FIRE ALARM PRINTER 3J121/21 20 20 1 600 68 SPACE 1 1 20 EXISTING PBX RECEPTACLE NORTH TOWER NCA PANEL 24 23 24 PBX FIRE ALARM PANEL 311211/2 1 20 1 G00 1 20 1 20 EXISTING PBX RECEPTACLE 25 SPARE EXISTING PBX RECEPTACLE 25 26 4TH FL.. FIRE ALARM PANEL 3L12V2 20 1 600 1 20 73 1 20 27 28 SPARE 27 28 SPARE 20 1 1 20 EXISTING PBX RECEPTACLE 1 20 30 NEW PBX QUAD. RECEPTACLE SPARE 1 2 29 30 SPARE 78 1 20 1 EXISTING PBX RECEPTACLE 31 32 NEW PBX QUAD. RECEPTACLE 9121/2' SPACE 20 31 32 SPACE 1 20 20 1 EXISTING PBX RECEPTACLE 33 34 NEW PBX QUAD. RECEPTACLE 4101/2" 20 1 SPACE 33 34 ISPACE 1 20 20 1 EXISTING PBX RECEPTACLE 35 36 NEW PBX QUAD. RECEPTACLE 121/20 20 1 SPACE 35 36 ISPACE 1 20 20 1 EXISTING PBX RECEPTACLE TOTAL CONNECTED LOAD: 7.6KVA + 1.8KVA(LOAD BEING ADDED) = 9.4KVA I = 9.4KVA = 26.1A. 0 208V 0.360V NOTES: 10 CONTRACTOR SHALL RE -USE EXISTING 1-POLE, 20A CIRCUIT BREAKER. 2. CONNECTED LOAD TAKEN FROM DRAWINGS DATED 12 -05 -06 PROVIDED BY SMH. TYPE SQUARE -D I -LINE (EXISTING) KAAIKI Q1 is RMA AAA n VOLTAGE MOUNTING 277/48OV, 3 PH, 4W PANEL "CDPA" SURFACE FED FROM: ATS -10 AIC 35KAIC LOCATION 15T FL. ELEC, ROOM VOLT AMP POLE TRIP CON DUI WIRE REMARKS CKT. N0. CKT. N0. WIRE CKT. NO. REMARKS POLE WIRE CON DUI TRIP POLE VOLT AMP 1 3 50 M M EXISTING PANEL 2CPL1 /4CPL1 EXISTING PBX RECEPTACLE 1 3 5 20 2 PANEL R1CL1 m 1 20 80 3 EXISTING PBX RECEPTACLE 4 6 4 EXISTING PBX RECEPTACLE EXISTING PBX RECEPTACLE 20 3 80 1 CYSTO 20 7 9 11 8 10 12 PANEL 3CL4 6 EXISTING PBX RECEPTACLE 60 3 1 48 SPARE 1 20 3 40 7 8 PANEL ORCL1 30 13 15 17 14 PANEL CH4 PBX RECEPTACLE 49 50 70 3 20 20 16 18 9 10 EXISTING PBX RECEPTACLE 3 80 11` 1 #8 PBX UPS 2ND FLOOR EXISTING 19 21 23 20 22 24 PANEL 1HE7 20 100 3 12 EXISTING PBX RECEPTACLE 20 1 3 100 1 20 PANEL 3CH1 55 57 25 27 29 26 28 30 PANEL R1CH1 EXISTING PBX RECEPTACLE 125 3 2 1 TOTAL CONNECTED LOAD: 150.5KVA* + 40KVA(LOAD BEING ADDED) = 190.5KVA I = 190.5KVA = 229A ® 480V NOTES: 0.831V O CONTRACTOR SHALL PROVIDE /INSTALL NEW 3 -POLE, 80A CIRCUIT BREAKER SQUARE -D POWERPACT HJ & MAKE PROPER SPLICES TO EXISTING FEEDER TO SECOND FLOOR. * DEMAND LOAD TAKEN FROM DRAWINGS DATED 06- 03--11 PROVIDED BY SMH. Is TYVp- SQUARE -D QO (NEW) LAAIAI MI IQ '))rA AAI n /1 rOA KWn VOLTAGE 120/208V, 3 PH, 4W PANEL "P D U - 1 " AIC 1 OKAIC MOUNTING PDU CABINET FED FROM: CDPA THRU UPS LOCATION 2ND FL. PBX ROOM VOLT AMP POLE TRIP CON DUI WIRE REMARKS CKT. NO. REMARKS CKT. N0. REMARKS WIRE CON DUI TRIP POLE VOLT AMP TRIP 1 20 d� 1 EXISTING PBX RECEPTACLE 1 M M EXISTING 2 EXISTING PBX RECEPTACLE e 20 1 m 1 20 1 EXISTING PBX RECEPTACLE 3 4 EXISTING PBX RECEPTACLE EXISTING PBX RECEPTACLE 20 1 SPARE 1 20 20 1 EXISTING PBX RECEPTACLE 5 6 EXISTING PBX RECEPTACLE 20 1 48 SPARE 1 20 20 EXISTING PBX RECEPTACLE 7 8 EXISTING PBX RECEPTACLE 30 20 1 PBX RECEPTACLE 49 50 SPARE 1 20 20 EXISTING PBX RECEPTACLE 9 10 EXISTING PBX RECEPTACLE 2 20 1 EXISTING PBX RECEPTACLE 51 53 1 20 EXISTING PBX RECEPTACLE 11 12 EXISTING PBX RECEPTACLE 20 1 20 1 20 PBX RECEPTACLE 55 57 EXISTING PBX RECEPTACLE 13 14 EXISTING PBX RECEPTACLE 20 1 2 1 20 EXISTING EXISTING PBX RECEPTACLE 15 16 EXISTING PBX RECEPTACLE 20 1 1 20 EXISTING PBX RECEPTACLE 17 18 EXISTING PBX RECEPTACLE 20 1 20 1 20 PBX RECEPTACLE 63 65 EXISTING PBX RECEPTACLE 19 20 EXISTING PBX RECEPTACLE 20 1 66 SPACE 1 20 EXISTING PBX RECEPTACLE 21 22 EXISTING PBX RECEPTACLE 30 20 1 PBX RECEPTACLE 67 69 68 SPACE 1 20 EXISTING PBX RECEPTACLE 23 24 EXISTING PBX RECEPTACLE 70 SPACE 20 1 1 20 2 EXISTING PBX RECEPTACLE 25 26 EXISTING PBX RECEPTACLE PBX RECEPTACLE 71 20 1 1 20 73 74 EXISTING PBX RECEPTACLE 27 28 EXISTING PBX RECEPTACLE 20 1 2 30 1 20 EXISTING PBX RECEPTACLE EXISTING PBX RECEPTACLE 29 30 NEW PBX QUAD. RECEPTACLE 3 1 1 2 20 1 360 78 1 20 EXISTING PBX RECEPTACLE 31 32 NEW PBX QUAD. RECEPTACLE 9121/2' 180 20 1 360 3#12 1 20 80 SPACE EXISTING PBX RECEPTACLE 33 34 NEW PBX QUAD. RECEPTACLE 4101/2" 20 1 360 SPACE 1 20 82 ISPACE EXISTING PBX RECEPTACLE 35 36 NEW PBX QUAD. RECEPTACLE 121/20 20 1 360 1 20 183 84 EXISTING PBX RECEPTACLE 37 38 NEW PBX QUAD. RECEPTACLE 1 1 2 20 1 360 1 20 EXISTING PBX RECEPTACLE 39 40 NEW PBX QUAD. RECEPTACLE 20 1 360 1 20 EXISTING PBX RECEPTACLE 41 42 NEW PBX QUAD. RECEPTACLE 1 1 2 20 1 720 NOTES: 1. ALL LOADS CONNECTED TO THIS PANEL SHALL BE TRANSFERRED FROM PANELS: LS2 PBX, LS1 & PBX1. EXCEPT FOR CIRCUITS 30,32,34,36,38,40 & 42 WHICH ARE NEW CIRCUITS TO FEED NEW QUADRUPLEX RECEPTACLES LOCATED IN PBX ROOM. 2, CONTRACTOR SHALL PROVIDE TRACING OF EACH ONE OF THE CIRCUITS BEING TRANSFERRED TO THIS PANEL & PROVIDE AN UPDATED PANEL SCHEDULE AND LABEL EACH RECEPTACLE TO MATCH CIRCUIT NUMBER AND PANEL NAME. �3 CONTRACTOR SHALL RUN NEW CONDUIT & WIRES FROM PDU PANEL TO NEW RECEPTACLE. 4. ALL CIRCUIT BREAKERS SHALL BE FACTORY SUPPLIED WITH UPS /PDU. -rvor IMI IARF -D 00 (NEW) LiAm ni ic, 009A ►Ai n /i rnA AArQ VOLTAGE 120/208V, 3 PH, MOUNTING PDU CABINET 4W PANEL 99PDU -2" AIC 1OKAIC FED FROM: CDPA THRU UPS LOCATION 2ND FL. PBX ROOM VOLT AMP POLE TRIP CON DUI WIRE W 1- REMARKS CKT. NO. _ CKT. NO. REMARKS D 0 V) WIRE CON DUI TRIP POLE VOLT AMP d� 1 20 ~Q Z M M EXISTING PBX RECEPTACLE 43 e 42 SPARE m Q 20 1 1 30 EXISTING PBX RECEPTACLE 45 46 SPARE 20 1 1 30 EXISTING PBX RECEPTACLE 47 48 SPARE W 20 1 1 30 EXISTING PBX RECEPTACLE 49 50 SPARE 20 1 2 20 EXISTING PBX RECEPTACLE 51 53 52 54 56 SPARE 100 3 2 20 EXISTING PBX RECEPTACLE 55 57 58 SPACE 2 20 EXISTING PBX RECEPTACLE 59 61 60 SPACE 62 SPACE 2 20 EXISTING PBX RECEPTACLE 63 65 64 SPACE 66 SPACE 2 30 EXISTING PBX RECEPTACLE 67 69 68 SPACE 70 SPACE 2 30 EXISTING PBX RECEPTACLE 71 72 SPACE 73 74 SPACE 2 30 EXISTING PBX RECEPTACLE 75 77 76 SPACE 78 SPACE 180 1 20 1 2 3#12 NEW PBX RECEPTACLE 79 80 SPACE SPACE 181 82 ISPACE SPACE 183 84 ISPACE TOTAL DEMAND LOAD: 11.24KVA + 2.88KVA(NEW LOAD ADDED) = 14.12KVA I = 14.12KVA = 39.22A ® 208V 0.360V NOTES: 1. ALL LOADS CONNECTED TO THIS PANEL SHALL BE TRANSFERRED FROM PANELS: LS2 PBX, LS1 & PBX1. 2. CONTRACTOR SHALL PROVIDE TRACING OF EACH ONE OF THE CIRCUITS BEING TRANSFERRED TO THIS PANEL & PROVIDE AN UPDATED PANEL SCHEDULE AND LABEL EACH RECEPTACLE TO MATCH CIRCUIT NUMBER AND PANEL NAME. O3 CONTRACTOR SHALL RUN NEW CONDUIT & WIRES FROM PDU PANEL TO NEW RECEPTACLE. 4. ALL CIRCUIT BREAKERS SHALL BE FACTORY SUPPLIED WITH UPS /PDU. PANEL SCHEDULE & FAULT CURRENT ANALYSIS 0 0 q 0 mp C E- @7 I N CV I a� x P 02 Pc+ C13 o p U c vi �'' w " c ti � O I PQ w Ld I CD CD Q z O H ca Z a U Z ° O EL U Lu W W o crf o .p V) Z zo D W 1- _ ck�Z U D 0 V) 0 UwN J >< ~ d� v) C:)� cnZ ~Q Z M M CL LL_�a W e c) m Q U O c W V) .p FILE: JOB NO.: 212 -1002 DATE : 03 -19 -12 PLOT SIZE: AS NOTED DESIGNED /DRAWN BY: A.V. CHECKED BY: F.A. SHEET No.: E -7 SHEET 8 OF 9 Z zo D W 1- _ ck�Z U D 0 V) 0 UwN J O �-- Lw 0 Z DUQ ~Q Z Q Z CL LL_�a 0 FILE: JOB NO.: 212 -1002 DATE : 03 -19 -12 PLOT SIZE: AS NOTED DESIGNED /DRAWN BY: A.V. CHECKED BY: F.A. SHEET No.: E -7 SHEET 8 OF 9