12-42-017ELECTRICAL SPECIFICATIONS 16010 - BASIC ELECTRICAL REQUIREMENTS 0. CONTRACTOR SHALL KEEP A CLEAN SET OF DRAWING AT THE SITE, A. THE SCOPE OF THE WORK SHALL INCLUDE THE FURNISHING AND LAMPS NOTING DAILY ALL CHANGES MADE IN THESE DRAWINGS IN CONNECTION y q' INSTALLATION OF THE NECESSARY MATERIAL AND LABOR TO ACCOMPLISH OF POWER CONNECTED TO, AND SOURCE OF POWER EQUIPMENT IS WITH THE FINAL INSTALLATION INCLUDING EXACT DIMENSIONED LOCATIONS 1. EACH LIGHTING FIXTURE SHALL BE FURNISHED WITH A NEW SET OF THE WORK INDICATED BY THE DRAWINGS AND HEREIN SPECIFIED, ALL OF ALL NEW AND UNCOVERED EXISTING UTILITIES TURN OVER A CLEAN, FED FROM. NAMEPLATES SHALL BE LAMINATED, WHITE CORE, PLASTIC WITH WORK BY CONTRACTOR SHALL CONFORM TO ALL APPLICABLE FEDERAL, LAMPS OF THE TYPES INDICATED ON THE DRAWINGS AND SPECIFIED NEATLY MARKED SET OF REPRODUCIBLE MYLARS SHOWING 'AS INSTALLED' 16140 - WIRING DEVICES STATE AND LOCAL BUILDING CODES AND STANDARDS INCLUDING BUT NOT BEVELED EDGES, MINIMUM 1/16' THICK, LETTERING SHALL BE MACHINE WORK TO THE ARCHITECT FOR SUBSEQUENT REVIEW AND TRANSMITTAL TO HEREIN. LAMPS SHALL BE MANUFACTURED BY GENERAL ELECTRIC, LIMITED TO: A. ALL WIRING DEVICES SHALL BE UL LISTED. THE OWNER, CONTRACTOR SHALL NOTE ALL CONSTRUCTION CHANGES, ENGRAVED, NOT LESS THAN 1/4" HIGH, CUT THROUGH THE SURFACE TO 1. STATE OF FLORIDA PHILIPS, OR OSRAM- SYLVANIA, EXCEPT WHERE SCHEDULED OTHERWISE. DATE EACH SHEET AND LABEL 'AS- BUILTS' IN THE REVISION BLOCK ON B. ACCEPTABLE MANUFACTURERS: PASS & SEYMOUR, HUBBEL, LEVITON, AND 2 CITY OF MIAMI THE WHITE (ARE. NAMEPLATES SHALL BE SECURELY ATTACHED THE DRAWINGS CONTRACTOR SHALL ALSO FURNISH ONE (1) SET OF 2. INCANDESCENT LAMPS: IN GENERAL, THEY SHALL INSIDE FROSTED, 3, LIFE SAFETY CODE - NFPA 101 (2006) COOPER. 'AS- BUILT' BLUEIJNE PRINTS. TO THE EQUIPMENT USING GALVANIZED SCREWS. ADHESIVES SHALL 4. UNDERWRITERS LABORATORIES, INC. PUBLICATIONS (UL) P. IN ADDITION TO THE ABOVE, CONTRACTOR SHALL ACCUMULATE DURING THE C. RECEPTACLES 5. NATIONAL FIRE PROTECTION ASSOCIATION. (NFPA) NOT BE USED. JOB'S PROGRESS, THE FOLLOWING DATA, IN TRIPLICATE, PREPARED IN A LIFE OF 2,500 HOURS (EXTENDED SERVICE), WHERE REFLECTOR STYLE 6. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) 1, RECEPTACLES SHALL BE HOSPITAL GRADE STANDARD STYLE THEY SHALL NEAT BROCHURE OR PACKET FOLDER AND TURNED OVER TO THE ARCHITECT IDENTIFICATION OF JUNCTION AND PULL BOXES SHALL BE WITH A BLACK 7, NATIONAL ELECTRICAL CODE - NFPA 70 (2008) LAMPS ARE SCHEDULED, FURNISH BEAM PATTERN INDICATED. FOR REVIEW AND SUBSEQUENT DELIVERY TO THE OWNER. BE 20A, 125V, 2 -POLE, 3 -WIRE, NEMA 5-20R CONFIGURATION, BACK BE SIDE WIRED WITH A GREEN EQUIPMENT GROUND SCREW OR AN 8. INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE) PERMANENT MARKING PEN ON THE TOP OF THE 4" X 4" JUNCTION BOX 1. ALL WARRANTIES AND GUARANTEES AND MANUFACTURER'S 3, FLUORESCENT LAMPS: IN GENERAL, THEY SHALL BE 3500K COLOR, 9. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (ISMO) AUTOMATIC GROUNDING SYSTEM) ATTACHED 70 THE STRAP U.N.O. DIRECTIONS ON EQUIPMENT AND MATERIAL COVERED BY THE COVER OR ON THE BACK OF THE OUTLET BOX COVER PLATE IDENTIFYING THE BRANCH CIRCUITS AND SYSTEMS WITHIN THE CONDUIT. PULL BOXES 10. INTERNATIONAL POWER CABLE ENGINEER'S ASSOCIATION (IPCEA) 48 -INCH LENGTH, T8, RAPID START, ENERGY SAVING LAMPS WITH AN INITIAL NOMINAL OUTPUT OF 2,850 LUMENS AT 32W, AND AN AVERAGE CONTRACT INCLUDING THE NAMES, ADDRESSES AND TELEPHONE 2. GFq RECEPTACLES SHALL BE A FEED THROUGH TYPE WIRED FOR SINGLE RECEPTACLE PROTECTION THUS NOT AFFECTING RECEPTACLES 11, NATIONAL ELECTRICAL SAFETY CODE (IBS Handbook $1) SI BE PROVIDED WITH A NAMEPLATE STATING VOLTAGE AND SYSTEM NUMBERS OF THE MANUFACTURER'S REPRESENTATIVE. RATED LIFE OF 24,004 HOURS. 12. REQUIREMENTS OF LOCAL UTILITY COMPANY DOWNSTREAM ON THE SAME CIRCUIT. THEY SHALL BE UL RATE) CLASS 1 2, APPROVED FIXTURE BROCHURES, WIRING DIAGRAMS AND RVE �' 13. FLORIDA ADMINISTRATIVE CODE 59A -3, (March 2003) 4, HIGH INTENSITY DISCHARGE (HID) LAMPS: SHALL BE OF THE TYPE AND CONTROL DIAGRAMS (ORIGINAL DATA, NO COPIES). DII WITH 5mA GROUND FAULT TRIP LEVEL AND A 20A FEED- THROUGH 14. NATIONAL FIRE PROTECTION ASSOCIATION 72 (2002) ON THE FACE OF THE WIRING DEVICE WALL PLATE, MACHINE ENGRAVE 3. COPIES OF APPROVED SHOP DRAWINGS. WATTAGES SCHEDULED. WHERE METAL HALIDE LAMPS ARE INDICATED, 15. NATIONAL FIRE PROTECTION ASSOCIATION 99 (2005) RATING AND HAVE A NEMA 5-20R CONFIGURATION, 4, OPERATING INSTRUCTIONS FOR ALL ELECTRICAL SYSTEM EQUIPMENT, OPERATING INSTRUCTIONS SHALL ALSO INCLUDE THERMOPLASTIC PLATES WITH THE PANELBOARD AND BRANCH CIRCUIT NUMBER THE DEVICE IS SERVED FROM. ADHESIVE LABELS ARE NOT 16. THE STATE FIRE PREVENTION CODE, 4A60 (2001) SELF - EXTINGUISHING LAMPS SHALL BE FURNISHED WHERE AVAILABLE IN RECOMMENDED MAINTENANCE PROCEDURES. 3. RECEPTACLE COLOR SHALL BE IVORY. THEY SHALL BE RED WHEN 17. BUILDING CODE. FLORIDA BUILDING CODE (2007) ALLOWED. 5. TEST REPORTS REQUIRED BY THESE SPECIFICATIONS. THAT WATTAGE RANGE. WITH 2008 AND 2009 REVISIONS CONNECTED TO AN EMERGENCY CIRCUIT. 6. ANY AND ALL OTHER DATA AND /OR DRAWINGS REQUIRED DURING RACEWAY IDENTIFICATION SHALL BE PROVIDED AT A MINIMUM OF EVERY 18. GUIDELINES (2406) FLUORESCENT BALLASTS SHALL BE EQUAL TO MOTOROLA LIGHTING INC. RAPID START HIGH PERFORMANCE ELECTRONIC TYPE. SMOKE, AND FUMES. FANG MATERIAL SHALL BE A UL 4. PEDIATRIC - ALL RECEPTA EDATRIC LOCAITGNNS CLES LOCATED IN PATIENT CARE NF 19. NFPA 110 (2005) , , 50 AT EACH END IF LESS THAN 50 AND A MINIMUM OF ONCE PER 7. REPAIR PARRTS LISTS OF ALL MAJOR ITEMS OF EQUIPMENT U V 20. FIRE MARSHALL'S RULE 4A3,012 F.A.C. adapted January 1, 2001 AREAS SHALL BE LISTED TAMPER RESISTANT. INCLUDING NAME, ADDRESS AND TELEPHONE NUMBERS OF LOCAL B. CODES AND STANDARDS REFERRED TO ARE MINIMUM, WHERE THE INSTALLATION - , L THE WEIGHT OF EACH FIXTURE SHALL REST ONLY ON THE FIXTURE SUPPLIER OR AGENT. D. SWITCHES I. REQUIREMENTS OF THE DRAWINGS OR SPECIFICATIONS EXCEED THOSE OF Q. ALL OF THE ABOVE DATA SHALL BE SUBMITTED TO THE ENGINEER FOR HIS SUPPORT SYSTEM AND ATTACHED TO CEILING CHANNELS, PROVIDE THE CODES AND REGULATIONS, THE DRAWINGS AND SPECIFICATIONS SWITCHES SHALL BE SPECIFICATION GRADE, 20A, 120/277V, REVIEW AT SUCH TIME AS THE CONTRACTOR SUBMITS HIS LAST ESTIMATE BE IDENTIFIED WITHIN 6 INCHES OF THE BOX OR ENCLOSURE. THE ENTIRE GOVERN, HANGERS, CABLES, SUPPORTS, CHANNELS, FRAMES AND BRACKETS OF PRIOR TO HIS FINAL PAYMENT, BUT IN NO CASE, LESS THAN TWO WEEKS C. THE CONTRACTOR SHALL OBTAIN AND PAY FOR PERMITS, PLAN CHECKS, BOX AND COVERPLATE SHALL BE PAINTED. USE THE FOLLOWING COLOR BEFORE FINAL INSPECTION. EACH KIND REQUIRED TO ERECT THIS EQUIPMENT SAFELY IN PLACE. INSPECTIONS, AND APPROVALS APPLICABLE TO THE WORK AS REQUIRED 16020 - ELECTRICAL WORK IN EXISTING FACILITIES BY THE REGULATORY AUTHORITIES. FEES AND COSTS OF ANY NATURE A. THE CONTRACT DOCUMENTS DO NOT PROPOSE TO SHOW ALL EXISTING BRANCH CIRCUIT HOMERUNS AND HOMERUNS OF WHATSOEVER INCIDENTAL TO THESE PERMITS, INSPECTIONS AND SYSTEMS MATERIAL OR EQUIPMENT. OBTAIN INFORMATION RELATED TO APPROVALS SHALL BE ASSUMED AND PAID BY THE CONTRACTOR. THE CONDUCTORS LARGER THAN NO. 12, INDIVIDUAL BRANCH EXISTING FACILITIES FROM EXISTING DOCUMENTS, MEASUREMENTS, PRO -RATA COSTS, IF ANY, FOR UTILITIES SERVING THIS PROPERTY WILL NOTATIONS, PHOTOGRAPHS, SURVEYS, AND OTHER OBSERVATIONS AT THE CIRCUIT WIRING FOR NO. 12 CONDUCTORS SHALL BE BE PAID FOR BY THE OWNER AND SHALL NOT BE INCLUDED AS PART OF SITE, THIS CONTRACT. B. SINCE THE BUILDING WILL CONTINUE IN USE THROUGHOUT THE D. SPACE ALLOCATIONS FOR MATERIALS, EQUIPMENT AND DEVICES HAVE CONSTRUCTION PERIOD, CARRY OUT THE WORK UNDER THIS DIVISION IN 7. INSTALLATION OF UNDERGROUND CONDUIT BEEN MADE ON THE BASIS OF PRESENT AND KNOWN FUTURE SUCH A MANNER AS TO MINIMIZE DISTURBANCE TO THE OCCUPANTS. REQUIREMENTS AND THE DIMENSIONS OF ITEMS OF EQUIPMENT OR C. REMOVE EXISTING WIRE, CONDUIT, EQUIPMENT, FIXTURES AND OTHER ITEMS DEVICES OF A PARTICULAR MANUFACTURER WHETHER INDICATED OR NOT. TO PROVIDE ACCESS FOR WORK IN EXISTING FACILITIES. REINSTALL AND NONMETALLIC CONDUIT (PVC), U.N.O. INSTALL AT LEAST 30 THE CONTRACTOR SHALL VERIFY THAT ALL MATERIALS, EQUIPMENT AND REFINISH ITEMS REMOVED, OR OTHERWISE DAMAGED, TO MATCH EXISTING DEVICES PROPOSED FOR USE ON THIS PROJECT ARE WITHIN THE INCHES BELOW FINISHED GRADE U.N.O. ON A BED OF SAND ADJACENT SURFACED UPON COMPLETION OF THE WORK, CONSTRAINTS OF THE ALLOCATED SPACE. INSTALLATION OR REMOVAL OF ADJACENT CEILING PANELS. E ALL EXISTING SYSTEMS, EQUIPMENT OR MATERIAL CONTRACTOR SHALL BE D. WHERE EXISTING FUNCTIONS TO REMAIN IN USE ARE DISRUPTED, THEY SHALL BE FULLY RESTORED AFTER DISRUPTION, IN FULL COMPLIANCE WITH b. INHERE CONDUIT ENTERS INTO PULL OR JUNCTION BOXES AND RESPONSIBLE FOR REVIEWING THE EXISTING CONDITIONS AT THE JOB SITE A. THIS DIVISION OF THE SPECIFICATIONS FOR NEW WORK. BEFORE SUBMITTING PROPOSALS. SUBMISSION OF PROPOSALS SHALL BE E MODIFY, REMOVE OR RELOCATE MATERIALS AND ITEMS INDICATED ON THE TAKEN AS EVIDENCE THAT SUCH INSPECTION HAS TAKEN PLACE THE DRAWINGS OR REQUIRED BY THE INSTALLATION OF NEW WORK. c, PROVIDE A PULL BOX OF APPROPRIATE SIZE EVERY 500 FEET CONTRACTOR SHALL BECOME FAMILIAR WITH THE COMPLETE SET OF INCLUDING GROUNDING AND NEUTRAL CONDUCTORS OF THE VARIOUS CONSTRUCTION DOCUMENTS, AND THE LACK OF SPECIFIC INFORMATION ON F. WORKING JOINTLY WITH THE ARCHITECT, ESTABLISH AND MARK SALVAGE THE DRAWINGS SHALL NOT RELIEVE THE AND DEMOLITION ITEMS BEFORE COMMENCING WORK; REPORT ITEMS B. COUPLINGS AND TERMINATORS CONTRACTOR OF ANY RESPONSIBILITY. SCHEDULE FOR RELOCATION, REINSTALLATION OR REUSE, WHICH ARE FOUND F EQUIPMENT SHALL BE NEW AND SHALL BEAR THE U.L LABEL WHERE 1. FOR RIGID STEEL OR INTERMEDIATE METAL CONDUIT; TO BE IN DAMAGED CONDITION; AWAIT FURTHER INSTRUCTIONS FROM THE ARCHITECT BEFORE COMMENCING WITH WORK. B. APPLICABLE, UNLESS NOTED OTHERWISE ALL WORK SHALL BE ELECTRICALLY CONTINUOUS, FACTORY -MADE THREADED COUPLINGS OF SAME MATERIAL GUARANTEED AGAINST DEFECTIVE MATERIALS AND WORKMANSHIP FORA G. DEMOLITION EQUIPMENT, DEVICES AND MATERIAL SHALL BE REMOVED FROM 16721 - FIRE PERIOD NOT LESS THAN ONE (1) YEAR AFTER COMPLETION AND AS THE CONDUIT. THE SITE AND DISPOSED OF BY THE CONTRACTOR. SALVAGED EQUIPMENT C. ACCEPTANCE BY THE OWNER. A. FURNISH AND INSTALL FIRE ALARM AND DETECTION SYSTEM ADDITIONS A AND DEVICES SHALL BE THE PROPERTY OF THE OWNER UNLESS NOTED G. CONTRACTOR SHALL INSTALL ELECTRICAL SYSTEMS WITHOUT JOINING OF GROUNDING ELECTRODE CONDUCTORS TO GROUND RODS, GROUNDING PLATES AND SPLICING OF CONDUCTORS, PROVIDE COMPRESSION OTHERWISE. AND RELOCATIONS AS INDICATED ON THE DRAWISYSTEM , COMPATIBLE AND INTERFERENCE AND IN STRICT COORDINATION WITH OTHER TRADES. H. MAKE MINOR RELOCATIONS NECESSITATED BY THE CONDITIONS AT THE SITE AND BOLTED TYPE CONNECTORS FOR JOINING OF GROUNDING ELECTRODE CONSISTENT WITH THE EXISTING SYSTEM. OR AS DIRECTED BY THE ARCHITECT, WITHOUT ADDITIONAL COST TO THE H. MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE CONTRACT CONDUCTORS TO GROUND BARS. OWNER. REPAIR AND RESTORE TO GOOD FUNCTIONAL CONDITION, EQUIPMENT, THE EXISTING SYSTEM OPERATION SHALL REMAIN UNCHANGED PROVIDING ?.... _ .,,- , DOCUMENTS AND APPLICABLE CODES AND STANDARDS. IN CASE OF PLATES SHALL BE OF SUITABLE CONFIGURATION FOR THE DEVICE FOR MATERIALS AND ITEMS SCHEDULED FOR RELOCATION, WHICH ARE DAMAGED PROVIDE MECHANICAL TYPE CONNECTORS FOR JOINING OF ALL EQUIPMENT DIFFERENCE BETWEEN APPLICABLE CODES AND STANDARDS AND THE CONTINUAL SERVICE DURING ALL PHASES OF THE RENOVATION AND /OR A 10'``' " DURING DISMANTLING OR REASSEMBLY OPERATIONS. NEW MATERIALS AND WHICH IT IS TO COVER WITH COLOR MATCHING MOUNTING SCREWS. CONTRACT DOCUMENTS, THE CONTRACTOR SHALL PROMPTLY NOTIFY AND ISOLATED GROUND CONDUCTORS, ITEMS OF SIMILAR DESIGN AND QUALITY MAY BE SUBSTITUTED FOR EXPANSION. i 11 THE ARCHITECT/ENGINEER IN WRITING OF SUCH DIFFERENCE. SHOULD COLOR OF THE WALL PLATES SHALL MATCH THE DEVICE, U.N.O. MATERIALS AND ITEMS INDICATED TO BE RELOCATED UPON APPROVAL OF SIZE GROUNDING CONDUCTORS IN ACCORDANCE WITH TABLES 250 -66 AND THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT COMPLY WITH IT IS THE RESPONSIBILITY OF THE ELECTRICAL. CONTRACTOR TO PROVOE , SHOP DRAWINGS, PRODUCT DATA AND SAMPLES. REMOVE CAREFULLY, IN 2. WALL PLATES SHALL BE THERMOPLASTIC, NON - COMBUSTIBLE, AND THE REQUIREMENTS OF APPLICABLE CODES AND STANDARDS, HE /SHE 250 -122 OF THE NEC, REVERSE ORDER TO ORIGINAL ASSEMBLY OR PLACEMENT, ITEMS WHICH ARE EXPANDABLE MODULES, POWER SUPIR= HARDWARE; SOFTWARE, ETC, SHALL BEAR ALL COSTS ARISING IN CORRECTING SUCH DEFECTS. HIGH- IMPACT RESISTANT. THEY SHALL BE P -LINE SMOOTH PLATES, TO BE RELOCATED. PROTECT ITEMS UNTIL RELOCATION IS COMPLETE CLEAN PROVIDE GROUNDING BUSHINGS ON ALL RACEWAYS TERMINATING WITHIN ALL APPLICABLE CODES AND STANDARDS SHALL INCLUDE ALL ORDINANCES, TO THE FIRE ALARM SYSTEM N ORDER TO ACCOMMODATE THE AND REPAIR ITEMS TO BE RELOCATED, AND PROVIDE NEW MATERIALS, THEY SHALL BE OF THE SAME MANUFACTURER AS THE WIRING DEVICE UTILITY COMPANY REGULATIONS, AND APPLICABLE REQUIREMENTS OF ELECTRICAL ENCLOSURES CONSTRUCTED OF SEPARATE ENCLOSURE PANELS FITTINGS AND APPURTENANCES REQUIRED TO COMPLETE THE RELOCATIONS ADDITIONAL FIRE ALARM DEVICES NATIONALLY ACCEPTED CODES AND STANDARDS. SHOULD THE IT IS TO COVER. AND TO RESTORE TO GOOD OPERATING ORDER. PERFORM THE RELOCATION WHICH ARE NOT INTEGRALLY WELDED TOGETHER, PROVIDE GROUNDING CONTRACTOR SUPPLY EQUIPMENT DIFFERING FROM THE SPECIFIED ITEMS CONTRACTOR SHALL PROVIDE SENSITIVITY TEST REPORT FOR ALL NEW WORK IN ACCORDANCE WITH APPLICABLE PORTIONS OF THESE 3. WEATHERPROOF, WIRING DEVICE IN WET LOCATIONS SHALL BE INSTALLED IN THE CONTRACT DOCUMENTS WITHOUT NOTIFICATION TO THE CONDUCTORS FROM SUCH BUSHINGS TO THE FRAME OF THE ENCLOSURE, SPECIFICATIONS, UTILIZING SKILLED WORKERS. SMOKE DETECTORS. ENGINEER, HE SHALL BEAR ALL COSTS TO UPGRADE DEFICIENCIES ARISING FROM SUCH. I. RELOCATING DEVICES: REMOVE AND REINSTALL IN LOCATIONS DESIGNATED GROUND BUS AND EQUIPMENT GROUNDING STRAP WHERE ONE OCCURS. E THE ENTIRE SYSTEM SHALL BE TESTED TO THE OWNER'S SATISFACTION. BY THE ARCHITECT TEMPERATURE CONTROL SYSTEM DEVICES, RELAYS, WIRE, I. WHERE ONLY ONE MANUFACTURER'S NAME IS LISTED IN THE EQUIPMENT PROVIDE A SEPARATE GREEN- INSULATED EQUIPMENT GROUNDING CONDUCTOR, CONDUIT, FIXTURES, EQUIPMENT AND OTHER DEVICES REQUIRED FOR THE CONTRACTOR SHALL PROVIDE A COMPLETE FIRE ALARM CERTIFICATION SPECIFICATION, OTHER MANUFACTURERS OF SIMILAR CHARACTERISTICS AND A GASKET BETWEEN THE COVER/iENCLOSURE AND THE MOUNTING OPERATION OF THE VARIOUS SYSTEMS THAT ARE INSTALLED IN WITH INSULATION OF THE SAME RATING AS THE PHASE CONDUCTORS, FOR OF EQUAL OR BETTER PERFORMANCE CAPACITIES MAY BE CONSIDERED FOR AND A SENSITIVITY TEST REPORT FOR ALL NEW, AND EXISTING SMOKE, EXISTING- TO -BE- REMOVED CONSTRUCTION. SURFACE, AND BETWEEN THE HINGED COVER AND MOUNTING PLATE/BASE 'OR EQUAL' ACCEPTANCE BY THE ENGINEER. SUBSTITUTION REQUESTS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL WHERE MORE THAN ONE 16084 _ THROUGH- PENETRATION FIRESTOPPING FOR ELECTRICAL SYSTEMS DUCT AND HEAT DETECTORS. CONTRACTOR SHALL REPLACE ANY MANUFACTURER IS LISTED IN THE NOTES AND EQUIPMENT SPECIFICATIONS, A. ONLY TESTED FIRESTOP SYSTEMS SHALL BE USED IN SPECIFIC LOCATIONS IM THE RACEWAY WITH RELATED PHASE AND NEUTRAL CONDUCTORS. WHERE ONLY THOSE NAMED MANUFACTURERS WILL BE CONSIDERED FOR DETECTOR THAT DOMES NOT MEET THE ALLOWABLE SENSITIVITY VALUES. AS FOLLOWS: SPECIFICATION GRADE AS MANUFACTURED BY TAYMAC CORPORATION OR ACCEPTANCE. SHOULD A SUBSTITUTION BE ACCEPTED, AND SHOULD THE PARALLEL CONDUCTORS IN SEPARATE RACEWAYS OCCUR, PROVIDE A 1. PENETRATIONS FOR THE PASSAGE OF CONDUIT AND OTHER ELECTRICAL WHERE REQUIRED, THE FIRE ALARM SYSTEM SHALL BE INTERFACED WITH SUBSTITUTE MATERIAL PROVE DEFECTIVE, OR OTHERWISE UNSATISFACTORY EQUAL EQUIPMENT THROUGH FIRE -RATED VERTICAL BARRIERS (WALLS AND GROUNDING CONDUCTOR IN EACH RACEWAY. CONNECT ALL GROUNDING FOR THE SERVICE INTENDED WITHIN THE GUARANTEE PERIOD, THIS MATERIAL THE BUILDING AUTOMATION SYSTEM IN ORDER TO SEND/RECEIVE PARTITIONS), HORIZONTAL BARRIERS (FLOOR /CEILING ASSEMBLIES), G. INSTALLATION OF TIRING DEVICES OR EQUIPMENT SHALL BE REPLACED WITH THE MATERIAL OR EQUIPMENT CONDUCTORS TO GROUND TERMINALS AT EACH END OF THE RUN, TO THE AND VERTICAL SERVICE SHAFT WALLS AND PARTITIONS. SWITCHES SIGNALS FROM ALARM INITIATING DEVICES AND H -O-A SWITCHES FOR SPECIFIED AT NO COST TO THE OWNER. L EACH WIRING DEVICE SHALL BE MOUNTED IN A METALLIC OUTLET BOX. 2, COMPLETION OF FIRESTOP INSTALLATIONS TO MAINTAIN THE RATING J. PROVIDE ACCESS, INCLUDING NECESSARY ACCESS DOORS, FOR NEW AND THE OPERATION OF SMOKE CONTROL SYSTEMS, FAN SHUTDOWN AND INTEGRITY OF THE BARRIER PENETRATED. IN GENERAL, DEVICES IN FINISHED SPACES SHALL BE FLUSH MOUNTED EXISTING EQUIPMENT REQUIRING OPERATION AND/011 MAINTENANCE B. INSTALLER SHALL CONSULT THE STRUCTURAL ENGINEER PRIOR TO COMMUNICATIONS. COORDINATE ALL REQUIREMENTS WITH DIVISION 15, RELOCATE EXISTING AND LOCATE ALL NEW EQUIPMENT SUCH THAT DEVICES AND DEVICES IN UNFINISHED SPACES SUCH AS ELECTRICAL PENETRATING ANY LOAD BEARING ASSEMBLY. OPERATION OR MAINTENANCE IS NOT RESTRICTED. C. ACCEPTABLE MANUFACTURERS. HILTI INC., TREMCO SEALANTS & COATINGS, K. INSTALL EQUIPMENT WITH WORKING CLEARANCES COMPLYING WITH NEC ENCLOSURE EACH CONNECT THE SECONDARY NEUTRAL POINT AND THE ENCLOSURE IN EACH 3M FIRE PROTECTION PRODUCTS, JOHN- MANVILLE FIREIEMP, OR OTHER FF�A. 110 -26 AND 110 -34. REQUIREMENTS OF ALL SPACES WITH ARCHITECT. MANUFACTURERS LISTED IN THE U.L FIRE RESISTANCE DIRECTORY - L SHOP DRAWING SUBMITTALS AUDIBLE DEVICES IN PUBLIC AND STAFF AREAS SHALL BE SPEAKERS VOLUME 2. 2, MOUNT RECEPTACLES A.F.F. TO THE DEVICE CENTERLINE, U.N.O. MOUNT 1, CONTRACTOR SHALL PREPARE AND SUBMIT SEVEN COPIES OF D. CONTRACTOR IS RESPONSIBLE FOR PROVIDING FIRESTOPPING BARRIER AT WITH A PEAK OUTPUT OF 96dB AT 10'-0'. ALL SUBMITTALS FOR ALL PERTINENT ELECTRICAL EQUIPMENT AND SWITCHES A,F.F. TO THE DEVICE CENTERLINE AND 6 FROM A DOOR ALL ELECTRICAL BOXES (FISTING AND NEW) AND PENETRATIONS FOR ANY GROUNDING ELECTRODE SYSTEM. STEM. DEVICES INDICATED IN THE SCOPE OF WORK, ALL WIRING SHALL BE STRANDED AND IN CONDUIT. COLOR SHALL BE THE EXISTING FIRE WALLS IN THE SCOPE OF WORK AREA AND /OR FOR ANY STRIKE, U.N.O. 2, COMPLETE LIST OF MATERIALS TO BE FURNISHED UNDER EACH PERFORM THE FOLLOWING NEW FIRE WALLS. FOR NEW FIRE WALLS IN WHICH ONE SIDE OF THE WALL FACILITY'S STANDARD OR RED. SPECIFIC SECTION. 3. MAINTAIN GROUNDING CONTINUITY BETWEEN DEVICES AND METALLIC RACEWAY SYSTEM IN ADDITION TO PROVIDING A GREEN EQUIPMENT FALLS OUTSIDE OF THE SCOPE OF WORK AREA AND OTHER DOES NOT, 1, TEST THE CONTINUITY OF AND THE PROPER CONNECTION OF EACH GROUND CONDUCTOR AND SYSTEM, TO ASSURE THAT THE GROUNDING 3. MANUFACTURERS' SPECIFICATIONS AND OTHER DATA REQUIRED PROVIDE NEW CONDUIT AND WIRING AS REQUIRED FOR NEW FIRE ALARM CONTRACTOR SHALL PROVIDE FlRSTOPPING BARRIER FOR ALL GROUNDING CONDUCTOR RUN WITH ALL CIRCUIT CONDUCTORS AS TO ASSURE SPECIFICATION COMPLIANCE SYSTEM IS COMPLETE AND UNINTERRUPTED. TESTING SHALL BE PENETRATIONS AND ELECTRICAL BOXES ON THE WALL SIDE NOT IN THE DEVICES. CONNECT AND PROGRAM DEVICES IN EXISTING FIRE ALARM CONTROL PANEL COORDINATE EXACT LOCATION OF EXISTING FIRE CONTROL PANEL WITH 4. CATALOG SWEETS, CLEARLY MARKED FOR IDENTIFICATION OF INDICATED ON THE DRAWINGS. 4. MOUNT RECEPTACLES THROUGHOUT THE PROJECT WITH GROUND POLE SCOPE OF WORK AREA. PERFORMED USING LABORATORY-ACCURACY TEST INSTRUMENTS OF SUITABLE DESIGN FOR THE TESTS TO BE PERFORMED. TEST INSTRUMENTS ITEMS M BE PROVIDED, INCLUDING DISCONNECT SWITCHES, 16110 - SYSTEMS OF RACEWAYS b. ON CONCEALED CONDUIT SYSTEMS WHERE BOXES ARE NOT OTHERWISE ACCESSIBLE, SET BOXES FLUSH WITH BREAKERS, FUSES, STARTERS, LIGHTING FIXTURES, SHALL BE PROVIDED UNDER DIVISION 16. TRANSFORMERS, OR OTHER MATERIAL NOT REQUIRING SPECIALLY A. CONDUIT PREPARED SHOP DRAWINGS. 1, RIGID STEEL CONDUIT (GRC - GALVANIZED RIGID CONDUIT): OVERLAPPING COVERS. 5, ALL SHOP DRAWING CUT SHEETS SHALL CLEARLY IDENTIFY THE CONSTRUCTED OF MILD STEEL PIPING, GALVANIZED INSIDE AND OUTSIDE, SPECIFIC PRODUCT TO BE REVIEWED AND APPROVED, INCLUDING C. ALL WIRING DEVICES FACEPLATES SHALL BE ENGRAVED CONFORMING WITH FED. SPEC, WW- C -581E, ANSI 080.1 AND UL 6, MANUFACTURER. GENERIC CUT SHEETS, INCOMPLETE CUT K. 2, INTERMEDIATE METAL CONDUIT (IMC): CONSTRUCTED OF ZINC COATED WITH THE PANELBOARD DESIGNATION AND CIRCUIT NUMBER SHEETS AND CUT SHEETS SUBMITTED WITHOUT IDENTIFYING THE STEEL TUBING MANUFACTURED IN ACCORDANCE WITH FED. SPEC. SPECIFIC PRODUCT PROVIDED, WILL BE AUTOMATICALLY SERVING THE OUTLET, LABEL TAPE WILL NOT BE WW-C- 581 -E, UL -1242 AND MEETING THE REQUIREMENTS OF THE NEC. REJECTED. 6. AS PART OF EQUIPMENT SHOP DRAWINGS, PROVIDE DETAILED L 3. ELECTRIC METALLIC TUBING (EMT): CONSTRUCTED OF HIGH GRADE ACCEPTABLE DIMENSIONED LAYOUT DRAWINGS FOR ALL LARGE ELECTRICAL SQL MANUFACTURED SPECIFICALLY TO STANDARDS ASSURING MAXIMUM M. EQUIPMENT AND ELECTRICAL ROOMS WHERE NEW EQUIPMENT IS D. OUTLET BOXES WELDING CHARACTERISTICS AND DUCTILITY, AND SHALL CONFORM TO BEING INSTALLED. FED, SPEC, WW-C- 563 -A, ANSI 080-3, AND UL 797, M. CONCRETE HOUSEKEEPING PADS SHALL BE PROVIDED FOR ALL FLOOR 4• LIQUIDTIGHT FLEXIBLE IBLE CONDUIT FLEXIBLE METAL CONDUIT AS SPECIFIED N. MOUNTED EQUIPMENT, UNLESS NOTED OR REQUIRED OTHERWISE ALL PADS REQUIRED FOR THE APPLICATION, OUTLET BOXES SHALL BE SHEET HEREIN WITH A COPPER GROUNDING STRAND AND FACTORY -APPLIED NEOPRENE JACKET. LIQUID TIGHT FLEXIBLE CONDUIT SHALL BE UL SHALL BE NOT LESS THAN 3-1/2' HIGH AND EXTEND A MAXIMUM 3" 0. LISTED, EQUIVALENT TO ANACONDA "SEALTITE', TYPE UA. STEEL, NO LIGHTER THAN 14 GAUGE, GALVANIZED AFTER FABRICATION. SET BOX SO FACE OF BOX WILL FINISH FLUSH WITH BUILDING SURFACE. BEYOND THE ACTUAL EQUIPMENT SIZE. COORDINATE THE PROPER SIZE OF WORK AREA BY VOLTAGE AND IMPEDANCE MEASUREMENTS AS INDICATED N NFPA 99, 4,3,3!1.3 & 43,3,1.4 RESPECTIVELY. THE RESULTS SHALL BE P. THE PAD WITH HE EQUIPMENT FURNISHED. PADS SHALL BE POURED IN a. FOR LIGHTING FIXTURE OUTLETS: 4 INCH SQUARE BY 1- 5, CONTRACTOR SHALL SUPPLY TRENCH DUCT AS REQUIRED IN RADIOLOGY FORMS BUILT OF NEW DRESSED LUMBER WITH CORNERS CHAMFERED USING ROOMS IN ACCORDANCE WITH THE RADIOLOGY VENDOR'S DRAWINGS, 1/2 INCHES DEEP WITH RAISED FIXTURE RING. SHEET METAL OR TRIANGULAR WOOD STRIPS NAILED TO THE FORM. USE DUCT SHALL BE AS REQUIRED BY VENDOR WITH A MINIMUM 1/4' THICK 6X6 No. 3 MESH FOR REINFORCING. INSTALL HEAVY DUTY ADJUSTABLE b, FOR WALL SWITCHES, RECEPTACLES. AND COMMUNICATION REMOVABLE COVER PLATES. DUCT SHALL HAVE A SINGLE REVERSIBLE ANCHOR BOLTS, SET IN THE FORM AND POSITIONED USING TEMPLATES, ALUMINUM TRIM WITH A SURFACE EXPOSURE THROUGH THE FLOOR TO USE: 4 INCH SQUARE, BY 1 -1/2 INCHES DEEP, USE BOXES PRIOR TO POURING CONCRETE. AFTER THE EQUIPMENT IS SET ON THE J. RECEIVE FLOOR COVERING. TRENCH DUCT SHALL BE MANUFACTURED BY 16741 - TELEPHONE AND DATA COMMUNICATIONS PAD, THE EQUIPMENT SHALL BE ALIGNED, LEVELED AND FULLY GROUTED A. ACCEPTABLE MANUFACTURERS: UNISTRUT CORP., B -LINE SYSTEMS, INC., AND MIDLAND ROSS- KINDORF. SQUARE D. WALKER, OR GENERAL ELECTRIC. ESSENTIAL BRANCH - CIRCUIT PANELBOARDS SERVING THE SAME TO THE PAD AND ALL VOID SPACES SHALL BE FILLED WITH A AT ALL WALL DATA/VOICE OUTLET LOCATIONS, PROVIDE A 4 11/16' SQUARE 6. INSTALLATION OF BUILDING CONDUIT B. FURNISH AND INSTALL ALL HANGERS AND SUPPORTS REQUIRE) BY NON - SHRINKING GROUT. PERFORM ALL CONCRETE WORK SPECIFIED TO BE PROVIDED UNDER THIS DIVISION IN STRICT ACCORDANCE WITH THE INDIVIDUAL PATIENT VICINITY SHALL BE BONDS) TOGETHER WITH AN a, ALL INTERIOR RACEWAYS SHALL BE EMT. RACEWAYS IN DAMP BOX WITH SINGLE -GANG ADAPTER AND BLANK COVER PLATE. 1" MIN. EMPTY APPLICABLE PROVISIONS OF DIVISION 3, CONCRETE. RACEWAY SYSTEMS. OR WET LOCATIONS, OR IN HAZARDOUS LOCATIONS, SHALL BE INSULATED CONTINUOUS COPPER CONDUCTOR NOT SMALLER THAN 10 CONDUIT SHALL RUN WITH PULL CORD TO 6' ABOVE NEAREST ACCESSIBLE GRC OR IMC. N. EACH CONDUIT, REGARDLESS OF MATERIAL, WHICH PASSES THROUGH A AWG. WHERE TWO OR MORE PANELBOARDS SERVING THE SAME INDIVIDUAL b, CONDUITS SHALL BE OF SUCH SIZE AND SO INSTALLED THAT CORRIDOR CEILING SPACE WHERE CORRIDORS DO NOT HAVE ACCESSIBLE CONCRETE SLAB, MASONRY WALL, OR ROOF OR PORTION OF THE BUILDING RODS WHICH ARE THREADED TO ALLOW VERTICAL ADJUSTMENTS. LOCK THE CONDUCTORS MAY BE DRAWN THROUGH WITHOUT INJURY PATIENT VICINITY ARE SERVED FROM SEPARATE TRANSFER SWITCHES ON STRUCTURE SHALL BE FREE FROM THE STRUCTURE AND SHALL PASS CEILINGS, PROVIDE CONDUIT SLEEVES AS A MINIMUM ONE PER SYSTEM OR EXCESSIVE STRAIN, SHALL BE SECURED AT CABINETS AND NUTS SHALL BE PROVIDED IN SUFFICIENT NUMBER AND LOCATION TO LOCK THROUGH A SLEEVE. ALL SLEEVES SHALL BE CONSTRUCTED FROM THE EMERGENCY SYSTEM, THE EQUIPMENT GROUNDING TERMINAL BUSES BOXES WITH GALVANIZED LOCKNUTS, BOTH INSIDE AND OUTSIDE, COVERING THE ENTIRE LENGTH OF NON - ACCESSIBLE (FILING CAVITY, NUMBER ELECTRIC-METALLIC TUBING OR EQUIVALENT WEIGHT GALVANIZED STEEL ALL ROD ADJUSTMENTS PERMANENTLY AT THE ADJUSTED HEIGHT. TWO AND SHALL HAVE APPROPRIATE BUSHINGS INSIDE, BUSHINGS OF THOSE PANELBOARDS SHALL BE BONDED TOGETHER WITH AN TUBING AND SHALL BE FLUSH ON BOTH SIDES OF THE SURFACE AND SIZE OF CONDUIT/SLEEVES SHALL BE PER MANUFACTURER'S CABLING SHALL BE INSULATING TYPE WITH BOND GROUND CLAMPS. LOA( NUTS SHALL BE USED UNLESS THE NUT TIGHTENS AGAINST A PENETRATED, U.N.O. ALL SLEEVES PENETRATING THE ROOF AREAS SHALL INSULATED CONTINUOUS COPPER CONDUCTOR NOT SMALLER THAN 10 REQUIREMENTS, EXTEND A MINIMUM 10 INCHES ABOVE THE ROOF WITH APPROVED THREADED SOCKET. MINIMUM ROD DIAMETERS SHALL BE AS FOLLOWS: c. USE LENGTHS OF FLEXIBLE METAL CONDUIT NOT LESS THAN AWG, THIS CONDUCTOR SMALL BE PERMITTED TO BE BROKEN IN ORDER TO TERMINATE ON THE EQUIPMENT GROUNDING TERMINAL BUS IN EACH WEATHERPROOF COUNTERFLASHING ATTACHED TO THE CONDUIT ABOVE PROVIDE A MINIMUM OF A 3 /16' DIAMETER, TWISTED NYLON PLASTIC CORD 12 INCHES LONG AT FINAL CONNECTIONS TO ALL MOTORS, NOMINAL CONDUIT SIZE ROD DIAMETER THE ROOF, ALL SLEEVES PENETRATING FLOORS SHALL EXTEND A MINIMUM PANELBOARD, TRANSFORMERS AND SIMILAR DEVICES SUBJECT TO MOVEMENT IN ALL EMPTY RACEWAYS. PROVIDE A IDENTIFICATION TAG ON EACH END OF 6 INCHES A.F.F. THE SLEEVES SHALL BE SIZED TO ALLOW FREE 1/2' THROUGH 2' 1/4' 16475 - OVERCURRENT PROTECTIVE DEVICES BECAUSE OF VIBRATION OR MECHANICAL ADJUSTMENT. USE INDICATING THE LOCATION OF THE OTHER END, PASSAGE OF THE CONDUIT TO BE INSERTED. SLEEVES PASSING THROUGH 2 -1/2' THROUGH 3' 3/8" FLEXIBLE METAL CONDUITS TO EFFECT FINAL CONNECTIONS PROVIDE DATA SHEETS SHOWING ELECTRICAL CHARACTERISTICS INCLUDING WALLS OR FLOORS ON OR BELOW GRADE OR IN MOIST AREAS SHALL BE INSTALL DATA /COMMUNICATIONS OUTLETS AT SAME HEIGHT SPECIFIED FOR TO RECESSED LIGHTING FIXTURES (6FT MAX). USE LIQUID 4' AND 5" 1/2' CONSTRUCTED OF GALVANIZED RIGID STEEL AND SHALL BE DESIGNED WITH TIME-CURRENT CURVES AS PART OF THE SHOP DRAWING SUBMITTAL TIGHT FLEXIBLE METAL CONDUIT, WITH APPROPRIATE CONVENIENCE OUTLETS U.N.O. GROUP TELEPHONE AND DATA COMMUNICATIONS OUTLETS WITH RELATED RECEPTACLE OUTLETS U.N.O. A SUITABLE FLANGE INT HE CENTER TO FORM A WATERPROOF PASSAGE, D. HANGER SPACING SHALL BE AS REQUIRED FOR PROPER SUPPORT OF CONNECTIONS, IN DAMP OR WET LOCATIONS, AT MOTOR OR FAULT CURRENT VALUES INDICATED ON THE DRAWINGS ARE BASED ON ACTUAL AVAILABLE FAULT VALUES AT EACH SWITCHBOARD, PANELBOARD AFTER THE CONDUIT HAS BEEN INSTALLED IN SLEEVES, THE VOID SPACE WHERE PLYWOOD BACKBOARDS ARE INDICATED, PROVIDE A 3/4' THICK APA EQUIPMENT LOCATIONS IN MECHANICAL EQUIPMENT ROOMS. RACEWAY, BUT IN NO CASE SHALL BE LESS THAN ONE HANGER PER W -0' AROUND THE CONDUIT SHALL BE CAULKED AND FILLED WITH AN AND ANY OTHER SIMILAR EQUIPMENT. EQUIPMENT MANUFACTURERS SHALL AT OR NEAR PUMPS, AND WHEN INSTALLED OUTDOORS. A/D GRADE PLYWOOD, TREATED WITH FIRE RETARDANT, MINIMUM TWO (2) ASPHALT -BASE COMPOUND TO INSURE A WATERPROOF PENETRATION. OF RACEWAY LENGTH EXCEPT THAT CONDUIT LESS THAN 1" DIAMETER PROVIDE EQUIPMENT AND PROTECTIVE DEVICES SUITABLY RATED FOR THE JUTE TWINE CAULKING SHALL NOT BE USED. COATS OF LIGHT GRAY PAINT. BACKBOARDS SHALL BE MOUNTED SIX (6') PANELBOARD SHALL BE A SEPARATE SYSTEM COMPLETELY FAULT ISOLATED FROM ALL OTHER RACEWAY SYSTEMS. ME ARCH TECT z, , ,, ,,A 160 Alhambra Circle, Suite 700 Coral Gables, Florida 38134 7.306.444.0413 F.306.441.6404 www.mgearchiteoi<s.corrt1' AA- FF000121 >1_ in association with ­1_1,412 III 0 EN WILMOT SANZ A R C H I T E C T U R E 16310 Man Avanua slaiahr0 �; iMsoe� Sri- 6�lo-�00 � 3Cn- i5eo -ateo Phi 906 DOD. M F&V M. S, M ® 2121 Ponce de Leon Blvd., Suite 350 Coral Gables, FL 33134 ionalConsultingEngineers phone: 305.569.1692 .. fax: 305.569.1693 Dallas . Houston . Nashville . Miami . Richmond " Austin . Denver . Phoenix . Washington D.C. ccrd project number: 41 1442.000 " EB00007658 Baptist N i , SOUTH f ti TOWER EAST F11- ST FLOOR RENOVA71ONS FOR O OFFICES AT THE CENTER _. FOR • AND INFANTS , lliz. =i 1r - !� • ' 1 # 100% CONSTRUCTION IOCUAENT SUBMTTAL SEAL I N (. ►J i I I i ,#4'-, . w ;� . 11 ,r q`, %I 1<111111iijill,7 f � , cq� I `'_111 y, �a - IV •10 �,� r .I , flir a t' a ` _ i a,l Ar vJ 1. � p➢..� w % 'ELf,6TRICAL ENGIi2ER . w. a'.5 °7:8.'x.• , t s,,, A ' :` .11!11100 I NOV el 2011 1 1 1 ��ELECTRICAL ­--, SPECIFICA11ONS., 0,1� .1-144 DRAWING NO i E ■ 0 () 1, !. - I D. ALL NAMEPLATES SHALL INCLUDE VOLTAGE, PHASE, WIRE, BRANCH E LAMPS '� y q' OF POWER CONNECTED TO, AND SOURCE OF POWER EQUIPMENT IS 1. EACH LIGHTING FIXTURE SHALL BE FURNISHED WITH A NEW SET OF FED FROM. NAMEPLATES SHALL BE LAMINATED, WHITE CORE, PLASTIC WITH LAMPS OF THE TYPES INDICATED ON THE DRAWINGS AND SPECIFIED d. GROUND METALLIC CONDUITS AS REQUIRED BY NEC, 16140 - WIRING DEVICES BEVELED EDGES, MINIMUM 1/16' THICK, LETTERING SHALL BE MACHINE HEREIN. LAMPS SHALL BE MANUFACTURED BY GENERAL ELECTRIC, e. INSTALL RACEWAYS CONTINUOUS FROM OUTLET TO OUTLET A. ALL WIRING DEVICES SHALL BE UL LISTED. ENGRAVED, NOT LESS THAN 1/4" HIGH, CUT THROUGH THE SURFACE TO V VF +UV PHILIPS, OR OSRAM- SYLVANIA, EXCEPT WHERE SCHEDULED OTHERWISE. BOX, OR CABINET, WITH A MAXIMUM OF 150 FEET BETWEEN B. ACCEPTABLE MANUFACTURERS: PASS & SEYMOUR, HUBBEL, LEVITON, AND V THE WHITE (ARE. NAMEPLATES SHALL BE SECURELY ATTACHED UV 2. INCANDESCENT LAMPS: IN GENERAL, THEY SHALL INSIDE FROSTED, PULLS, IN AREAS WHERE THERE ARE NO SUSPENDED COOPER. TO THE EQUIPMENT USING GALVANIZED SCREWS. ADHESIVES SHALL U ENERGY SAVING STYLE DESIGNED FOR 130V OPERATION WITH A RATED CEILINGS, RUN ALL CONDUITS PARALLEL/PERPENDICULAR TO C. RECEPTACLES NOT BE USED. LIFE OF 2,500 HOURS (EXTENDED SERVICE), WHERE REFLECTOR STYLE BUILDING SURFACE. 1, RECEPTACLES SHALL BE HOSPITAL GRADE STANDARD STYLE THEY SHALL E. IDENTIFICATION OF JUNCTION AND PULL BOXES SHALL BE WITH A BLACK J LAMPS ARE SCHEDULED, FURNISH BEAM PATTERN INDICATED. f• IN SYSTEMS OPERATING AT MORE THAN 300 VOLTS BETWEEN BE 20A, 125V, 2 -POLE, 3 -WIRE, NEMA 5-20R CONFIGURATION, BACK BE SIDE WIRED WITH A GREEN EQUIPMENT GROUND SCREW OR AN U PERMANENT MARKING PEN ON THE TOP OF THE 4" X 4" JUNCTION BOX U 3, FLUORESCENT LAMPS: IN GENERAL, THEY SHALL BE 3500K COLOR, PHASE CONDUCTORS, AND WHERE DIFFERENT PHASE CONDUCTORS ARE TO BE RUN TO A COMMON GANG WALL AUTOMATIC GROUNDING SYSTEM) ATTACHED 70 THE STRAP U.N.O. COVER OR ON THE BACK OF THE OUTLET BOX COVER PLATE IDENTIFYING THE BRANCH CIRCUITS AND SYSTEMS WITHIN THE CONDUIT. PULL BOXES V, 48 -INCH LENGTH, T8, RAPID START, ENERGY SAVING LAMPS WITH AN INITIAL NOMINAL OUTPUT OF 2,850 LUMENS AT 32W, AND AN AVERAGE SWITCH BOX, PROVIDE SUBSTANTIAL BARRIERS BETWEEN 2. GFq RECEPTACLES SHALL BE A FEED THROUGH TYPE WIRED FOR SINGLE RECEPTACLE PROTECTION THUS NOT AFFECTING RECEPTACLES )VU SI BE PROVIDED WITH A NAMEPLATE STATING VOLTAGE AND SYSTEM V RATED LIFE OF 24,004 HOURS. ADJACENT SWITCHES IN THE BOX SO THAT TWO DIFFERENT DOWNSTREAM ON THE SAME CIRCUIT. THEY SHALL BE UL RATE) CLASS 1 F. RVE �' V , V 4, HIGH INTENSITY DISCHARGE (HID) LAMPS: SHALL BE OF THE TYPE AND PHASE WIRES WILL NOT BE IN THE SAME COMPARTMENT. WITH 5mA GROUND FAULT TRIP LEVEL AND A 20A FEED- THROUGH V l v V V ON THE FACE OF THE WIRING DEVICE WALL PLATE, MACHINE ENGRAVE WATTAGES SCHEDULED. WHERE METAL HALIDE LAMPS ARE INDICATED, g. WHEREVER RACEWAYS PASS THROUGH FLOORS, WALLS, RATING AND HAVE A NEMA 5-20R CONFIGURATION, THERMOPLASTIC PLATES WITH THE PANELBOARD AND BRANCH CIRCUIT NUMBER THE DEVICE IS SERVED FROM. ADHESIVE LABELS ARE NOT SELF - EXTINGUISHING LAMPS SHALL BE FURNISHED WHERE AVAILABLE IN PENETRATIONS, OR OTHER PARTITIONS, CAREFULLY FILL ANY 3. RECEPTACLE COLOR SHALL BE IVORY. THEY SHALL BE RED WHEN I I - ALLOWED. THAT WATTAGE RANGE. SPACE BETWEEN THE OUTSIDE OF THE RACEWAY AND THE BUILDING MATERIAL TO PREVENT PASSAGE OF AIR, WATER, CONNECTED TO AN EMERGENCY CIRCUIT. G. RACEWAY IDENTIFICATION SHALL BE PROVIDED AT A MINIMUM OF EVERY F. FLUORESCENT BALLASTS SHALL BE EQUAL TO MOTOROLA LIGHTING INC. RAPID START HIGH PERFORMANCE ELECTRONIC TYPE. SMOKE, AND FUMES. FANG MATERIAL SHALL BE A UL 4. PEDIATRIC - ALL RECEPTA EDATRIC LOCAITGNNS CLES LOCATED IN PATIENT CARE , , 50 AT EACH END IF LESS THAN 50 AND A MINIMUM OF ONCE PER U V LISTED, INTUMESCENT SEALING HAVING FIRE /SMOKE / AREAS SHALL BE LISTED TAMPER RESISTANT. ROOM OR SPACE THROUGH WHICH IT PASSES. G. INSTALLATION - , L THE WEIGHT OF EACH FIXTURE SHALL REST ONLY ON THE FIXTURE RESISTIVE RATING EQUAL TO THE BUILDING MATERIAL D. SWITCHES I. H. CONDUIT, RACEWAYS AND BOXES SHALL BE SPOT PAINTED, CONDUIT SHALL SUPPORT SYSTEM AND ATTACHED TO CEILING CHANNELS, PROVIDE PENETRATED. SWITCHES SHALL BE SPECIFICATION GRADE, 20A, 120/277V, BE IDENTIFIED WITHIN 6 INCHES OF THE BOX OR ENCLOSURE. THE ENTIRE HANGERS, CABLES, SUPPORTS, CHANNELS, FRAMES AND BRACKETS OF h• CONDUITS UTILIZED THROUGHOUT THE PROJECT SHALL NOT HORSEPOWER RATED, BACK AND SIDE WIRED. SWITCHES SHALL INCLUDE I BOX AND COVERPLATE SHALL BE PAINTED. USE THE FOLLOWING COLOR EACH KIND REQUIRED TO ERECT THIS EQUIPMENT SAFELY IN PLACE. BE SMALLER THAN 3/4 INCH FOR FEEDERS, MULTIPLE A GREEN GROUND SCREW ATTACHED TO THE MOUNTING STRAP. CODING SCHEME: . 2, THE WEIGHT OF EACH FIXTURE SHALL REST ONLY ON THE FIXTURE BRANCH CIRCUIT HOMERUNS AND HOMERUNS OF 2. WHERE LIGHTING CIRCUITS ARE SHOWN TO BE LINE VOLTAGE SWITCHED, NORMAL SYSTEM - WHITE FIRE ALARM - RED SUPPORT SYSTEM AND ATTACHED TO CEILING CHANNELS. PROVIDE CONDUCTORS LARGER THAN NO. 12, INDIVIDUAL BRANCH PROVIDE WITH SPECIFICATION (MADE, HORSEPOWER RATED, UL LISTED, CRITICAL BRANCH - BRIGHT ORANGE COMMUNICATIONS - BROWN HANGERS, CABLES, SUPPORTS, CHANNELS, FRAMES AND BRACKETS OF CIRCUIT WIRING FOR NO. 12 CONDUCTORS SHALL BE BACK- AND SIDE- WIRED, TOGGLE SWITCHES RATED 20A, 120V OR 277 LIFE SAFETY BRANCH - BRIGHT YELLOW TELEPHONE /COMPUTER - BLACK EACH KIND REQUIRED TO ERECT THIS EQUIPMENT SAFELY IN PLACE, ACCEPTABLE IN 3/4' CONDUIT, I.E. 2#12, 1#12G, 3/4 "C. VOLTS. SWITCHES SHALL BE SPST, DPST, 3-WAY OR 4-WAY, WITH OR EQUIPMENT SYSTEM - KELLY GREEN NURSE CALL -ROYAL BLUE 3, THE MOUNTING BRACKETS SHALL BE INSTALLED TO OVERLAP THE CEILING 7. INSTALLATION OF UNDERGROUND CONDUIT WITHOUT PILOT LIGHT AS INDICATED ON THE DRAWINGS, TV - LIGHT PINK SUPPORT CHANNELS IN ORDER TO PREVENT THE CHANNELS FROM a, INSTALL UNDERGROUND FEEDER CONDUCTORS IN RIGID 3. SWITCH COLOR SHALL BE IVORY OR RED WHEN CONNECTED TO AN EMERGENCY CIRCUIT. IN EVENT THAT THERE IS A DISCREPANCY BETWEEN THESE COLORS AND SHIFTING FROM UNDERNEATH THE FIXTURES. NONMETALLIC CONDUIT (PVC), U.N.O. INSTALL AT LEAST 30 THE FACILITY STANDARD, CONTRACTOR SHALL SUBMIT AN RFI REQUESTING 4. THE LIGHTING FIXTURE INSTALLATION SHALL NOT INTERFERE WITH THE INCHES BELOW FINISHED GRADE U.N.O. ON A BED OF SAND E DIMMER SWITCHES CLARIFICATION. INSTALLATION OR REMOVAL OF ADJACENT CEILING PANELS. BEFORE CONTINUING @Aq(FlLL 1. DIMMER SWITCHES SHALL BE MANUFACTURED BY LUTRON, 2, ALL DEVICES SHALL BE CAPABLE OF OPERATING AT RATED CAPACITY 16450 - GROUNDING 5. RECESSED FIXTURES IN DROPPED CEILING AREAS SHALL BE b. INHERE CONDUIT ENTERS INTO PULL OR JUNCTION BOXES AND WITHOUT ADVERSELY AFFECTING DESIGN LIFETIME. A. EXPOSED METALLIC PARTS OF THE ELECTRICAL SYSTEM WHICH ARE NOT CONNECTED USING FLEXIBLE CONDUIT. CONDUIT SHALL BE CONNECTED TO FIXTURE AND OUTLET BOX. EACH PIECE SHALL AT ALL BENDS, CHANGE FROM PVC TO RIGID GALVANIZED STEEL. CONDUIT BELOW GRADE. 3. DIMMER CONTROL OF LIGHT INTENSITY SHALL BE VIA LINEAR SLIDE 4. LINEAR SLIDE DIMMER SHALL PROVIDE INTENSITY AND ON /OFF CONTROL INTENDED TO CARRY CURRENT, INCLUDING SYSTEM COMPONENTS SUCH AS BUSDUCTS, SWITCHBOARDS, PANELBOARDS AND RACEWAY SYSTEMS, AND HAVE A SEPARATE INSULATED GREEN GROUNDING CONDUCTOR c, PROVIDE A PULL BOX OF APPROPRIATE SIZE EVERY 500 FEET WITH MOVEMENT OF SLIDER. THIS SHALL APPLY TO SINGLE POLE AND INCLUDING GROUNDING AND NEUTRAL CONDUCTORS OF THE VARIOUS .#14 MIN. FOR GROUNDING CONTINUITY BETWEEN THE FIXTURE AND THE CONDUIT SYSTEM. GROUNDING CONDUCTOR SHALL BE OF STRAIGHT RUN AND AT EVERY 90 DESIREE BEND, 2- LOCATION DIMMERS, 6. TIRING SYSTEMS, SHALL BE GROUNDED IN ACCORDANCE WITH NEC REQUIREMENTS,, MECHANICALLY CONNECTED IN A PERMANENT AND EFFECTIVE B. COUPLINGS AND TERMINATORS SWITCH RATING�SHNl BE 24A. 12OVACE FOR TUNGSTEN OR OR INDUCTIVE MANNER TO FIXTURE AND CONDUIT SYSTEM AND BE 1. FOR RIGID STEEL OR INTERMEDIATE METAL CONDUIT; LOADS, B. PROVIDE COPPER CLAD STEEL GROUND RODS 3 4 INCH DIAMETER 10 FEET / ELECTRICALLY CONTINUOUS, FACTORY -MADE THREADED COUPLINGS OF SAME MATERIAL 7. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A DIMMER SWITCH LONG DESIGNED FOR DRIVEN INSTALLATION. 16721 - FIRE ALARM SYSTEM MODIFICATION ) AS THE CONDUIT. AND WIRING COMPATIBLE WITH LIGHT FIXTURE SPECIFICED IN ORDER TO C. PROVIDE EXOTHERMIC TYPE CHEMICAL WELDED TYPE CONNECTORS FOR A. FURNISH AND INSTALL FIRE ALARM AND DETECTION SYSTEM ADDITIONS A 2, FOR ELECTRICAL METALLIC TUBING, USE STEEL COMPRESSION PIRMADE A COMPLETE AND FUNCTIONAL SYSTEM, F. WALL PLATES JOINING OF GROUNDING ELECTRODE CONDUCTORS TO GROUND RODS, GROUNDING PLATES AND SPLICING OF CONDUCTORS, PROVIDE COMPRESSION AND RELOCATIONS AS INDICATED ON THE DRAWISYSTEM , COMPATIBLE AND COUPLINGS AND NYLON INSULATED GROUNDING BUSHINGS, 1. WALL PLATES SHALL BE PROVIDED FOR ALL SWITCHES, RECIEPTACLES, AND BOLTED TYPE CONNECTORS FOR JOINING OF GROUNDING ELECTRODE CONSISTENT WITH THE EXISTING SYSTEM. 3. FOR FLEXIBLE METAL CONDUIT: COUPLINGS AT CONNECTIONS BLANKS, TELEPHONE/DATA, AND SPECIAL PURPOSE OUTLETS, THE WALL CONDUCTORS TO GROUND BARS. B. THE EXISTING SYSTEM OPERATION SHALL REMAIN UNCHANGED PROVIDING ?.... _ .,,- , BETWEEN FLDI @LE CONDUIT AND EMT, AND NYLON INSULATED PLATES SHALL BE OF SUITABLE CONFIGURATION FOR THE DEVICE FOR D. PROVIDE MECHANICAL TYPE CONNECTORS FOR JOINING OF ALL EQUIPMENT CONTINUAL SERVICE DURING ALL PHASES OF THE RENOVATION AND /OR A 10'``' " THROAT STEEL CONNECTORS AT BOX OR CABINET TERMINATIONS. WHICH IT IS TO COVER WITH COLOR MATCHING MOUNTING SCREWS. AND ISOLATED GROUND CONDUCTORS, EXPANSION. i 11 4. SCREW COUPLINGS; STEEL SET SCREW BOX CONNECTORS COLOR OF THE WALL PLATES SHALL MATCH THE DEVICE, U.N.O. E SIZE GROUNDING CONDUCTORS IN ACCORDANCE WITH TABLES 250 -66 AND C. IT IS THE RESPONSIBILITY OF THE ELECTRICAL. CONTRACTOR TO PROVOE , WITH NYLON INSULATED THROAT AND LOCKNUTS AT ALL 2. WALL PLATES SHALL BE THERMOPLASTIC, NON - COMBUSTIBLE, AND 250 -122 OF THE NEC, EXPANDABLE MODULES, POWER SUPIR= HARDWARE; SOFTWARE, ETC, BOXES AND CABINET TERMINATIONS OR NON- INSULATE) BOX HIGH- IMPACT RESISTANT. THEY SHALL BE P -LINE SMOOTH PLATES, F. PROVIDE GROUNDING BUSHINGS ON ALL RACEWAYS TERMINATING WITHIN ALL TO THE FIRE ALARM SYSTEM N ORDER TO ACCOMMODATE THE CONNECTOR, LOCKNUT AND NYLON - INSULATED GROUNDING THEY SHALL BE OF THE SAME MANUFACTURER AS THE WIRING DEVICE ELECTRICAL ENCLOSURES CONSTRUCTED OF SEPARATE ENCLOSURE PANELS ADDITIONAL FIRE ALARM DEVICES BUSHING ON ALL TUBING WHERE GROUNDING BUSHINGS ARE IT IS TO COVER. WHICH ARE NOT INTEGRALLY WELDED TOGETHER, PROVIDE GROUNDING D. CONTRACTOR SHALL PROVIDE SENSITIVITY TEST REPORT FOR ALL NEW REQUIRED. 3. WEATHERPROOF, WIRING DEVICE IN WET LOCATIONS SHALL BE INSTALLED CONDUCTORS FROM SUCH BUSHINGS TO THE FRAME OF THE ENCLOSURE, SMOKE DETECTORS. C. JUNCTION AND PULL BOXES WITH A HINGED OUTLET COVER/ENCLOSURE CLEARLY MARKED 'SUITABLE GROUND BUS AND EQUIPMENT GROUNDING STRAP WHERE ONE OCCURS. E THE ENTIRE SYSTEM SHALL BE TESTED TO THE OWNER'S SATISFACTION. 1. SIZE BOXES IN ACCORDANCE WITH THE REQUIREMENTS OF THE NEC, FOR WET LOCATIONS WHILE IN USE' AND 'UL LISTED', THERE SHALL BE G. PROVIDE A SEPARATE GREEN- INSULATED EQUIPMENT GROUNDING CONDUCTOR, CONTRACTOR SHALL PROVIDE A COMPLETE FIRE ALARM CERTIFICATION BOXES SHALL BE UL LISTED AND NO SMALLER THAN 4 INCHES A GASKET BETWEEN THE COVER/iENCLOSURE AND THE MOUNTING WITH INSULATION OF THE SAME RATING AS THE PHASE CONDUCTORS, FOR AND A SENSITIVITY TEST REPORT FOR ALL NEW, AND EXISTING SMOKE, SQUARE BY 1 -1/2 INCHES DEEP WITH COVERS ACCESSIBLE AT ALL SURFACE, AND BETWEEN THE HINGED COVER AND MOUNTING PLATE/BASE ALL FEEDERS AND BRANCH CIRCUITS. INSTALL THE GROUNDING CONDUCTORS DUCT AND HEAT DETECTORS. CONTRACTOR SHALL REPLACE ANY TIMES, SET BOXES ON CONCEALED CONDUITS WITH COVERS FLUSH TO ASSURE PROPER SEAL THE COVER/tNCLOSURE SHALL BE IM THE RACEWAY WITH RELATED PHASE AND NEUTRAL CONDUCTORS. WHERE DETECTOR THAT DOMES NOT MEET THE ALLOWABLE SENSITIVITY VALUES. WITH THE FINISHED WALL OR OILING LINE PROVIDE JUNCTION AND SPECIFICATION GRADE AS MANUFACTURED BY TAYMAC CORPORATION OR PARALLEL CONDUCTORS IN SEPARATE RACEWAYS OCCUR, PROVIDE A F. WHERE REQUIRED, THE FIRE ALARM SYSTEM SHALL BE INTERFACED WITH PULL BOXES OF APPROPRIATE DIMENSIONS FOR CONDUITS AND EQUAL GROUNDING CONDUCTOR IN EACH RACEWAY. CONNECT ALL GROUNDING THE BUILDING AUTOMATION SYSTEM IN ORDER TO SEND/RECEIVE CONDUCTORS NOTED, WHERE SOWN AND WHERE NECESSARY FOR G. INSTALLATION OF TIRING DEVICES CONDUCTORS TO GROUND TERMINALS AT EACH END OF THE RUN, TO THE SWITCHES SIGNALS FROM ALARM INITIATING DEVICES AND H -O-A SWITCHES FOR THE INSTALLATION AND PULLING OF CABLES AND WIRES. INSTALL COVERS ON JUNCTION BOXES AND CONDULETS AFTER WIRING AND L EACH WIRING DEVICE SHALL BE MOUNTED IN A METALLIC OUTLET BOX. END THAT THERE WILL BE NO UNINTERRUPTED GROUNDING CIRCUIT FROM THE POINT OF GROUND FAULT BACK TO A POINT OF CONNECTION OF THE THE OPERATION OF SMOKE CONTROL SYSTEMS, FAN SHUTDOWN AND CONNECTIONS ARE COMPLETED. IN GENERAL, DEVICES IN FINISHED SPACES SHALL BE FLUSH MOUNTED EQUIPMENT GROUND AND SYSTEM NEUTRAL COMMUNICATIONS. COORDINATE ALL REQUIREMENTS WITH DIVISION 15, DEVICES AND DEVICES IN UNFINISHED SPACES SUCH AS ELECTRICAL G. VISUAL OBE DEVICES SHALL MEET THE REQUIREMENTS OF ADO, UL, 2. ALL JUNCTION AND PULL BOXES FOR EMERGENCY SYSTEMS AND LOW AND MECHANICAL ROOMS SHALL BE SURFACE MOUNTED. VERIFY THE H. ENCLOSURE EACH CONNECT THE SECONDARY NEUTRAL POINT AND THE ENCLOSURE IN EACH FF�A. VOLTAGE SYSTEMS SHALL HAVE COVER PLATES PAINTED. COLORS FOR REQUIREMENTS OF ALL SPACES WITH ARCHITECT. DRY TYPE TRANSFORMER TOGETHER AND RUN A GROUNDING H. AUDIBLE DEVICES IN PUBLIC AND STAFF AREAS SHALL BE SPEAKERS COVERS SHALL BE YELLOW (LIFE SAFETY BRANCH), ORANGE (CRITICAL 2, MOUNT RECEPTACLES A.F.F. TO THE DEVICE CENTERLINE, U.N.O. MOUNT CONDUCTOR FROM THEIR COMMON POINT OF CONNECTION TO THE BUILDING WITH A PEAK OUTPUT OF 96dB AT 10'-0'. BRANCH), GREEN (EQUIPMENT SYSTEM), RED (FIRE ALARM), AND BROWN SWITCHES A,F.F. TO THE DEVICE CENTERLINE AND 6 FROM A DOOR GROUNDING ELECTRODE SYSTEM. STEM. 1. ALL WIRING SHALL BE STRANDED AND IN CONDUIT. COLOR SHALL BE THE (DATA/rELEPHONE), STRIKE, U.N.O. I. PERFORM THE FOLLOWING FACILITY'S STANDARD OR RED. 3. INSTALLATION OF PULL AND JUNCTION BOXES 3. MAINTAIN GROUNDING CONTINUITY BETWEEN DEVICES AND METALLIC RACEWAY SYSTEM IN ADDITION TO PROVIDING A GREEN EQUIPMENT 1, TEST THE CONTINUITY OF AND THE PROPER CONNECTION OF EACH GROUND CONDUCTOR AND SYSTEM, TO ASSURE THAT THE GROUNDING J. PROVIDE NEW CONDUIT AND WIRING AS REQUIRED FOR NEW FIRE ALARM a. FASTEN ALL BOXES SECURELY TO THE BUILDING GROUNDING CONDUCTOR RUN WITH ALL CIRCUIT CONDUCTORS AS SYSTEM IS COMPLETE AND UNINTERRUPTED. TESTING SHALL BE DEVICES. CONNECT AND PROGRAM DEVICES IN EXISTING FIRE ALARM CONTROL PANEL COORDINATE EXACT LOCATION OF EXISTING FIRE CONTROL PANEL WITH CONSTRUCTION. INDEPENDENT OF CONDUIT SYSTEMS. INDICATED ON THE DRAWINGS. 4. MOUNT RECEPTACLES THROUGHOUT THE PROJECT WITH GROUND POLE PERFORMED USING LABORATORY-ACCURACY TEST INSTRUMENTS OF SUITABLE DESIGN FOR THE TESTS TO BE PERFORMED. TEST INSTRUMENTS OWNER, NEW DEVICES ARE TO MATCH EXISTING ONES AND BE UL LISTED WITH b. ON CONCEALED CONDUIT SYSTEMS WHERE BOXES ARE NOT OTHERWISE ACCESSIBLE, SET BOXES FLUSH WITH AT THE TOP OF THE CONFIGURATION WHEN MOUNTED VERTICALLY AND SHALL BE PROVIDED UNDER DIVISION 16. EXISTING FIRE ALARM SYSTEM, PROVIDE NEW POWER SUPPLIES AS NECESSARY INCLUDING EXPANSION MODULES OR ANY SOFTWARE OR HARDWARE FINISHED SURFACES FOR ACCESS, AND PROVIDE ON THE RIGHT WHEN MOUNTED HORIZONTALLY. 2, TEST GROUNDING CONDUCTORS, PHASE CONDUCTORS AND NEUTRAL ACCESSORIES REQUIRED FOR A COMPLETE AND FUNCTIONAL INSTALLATION. ALL OVERLAPPING COVERS. 5, ALL EXTERIOR RECEPTACLES SHALL BE GFC1 WITH A WEATHERPROOF CONDUCTORS FOR CONTINUITY AND FOR POSSIBLE DAMAGE TO DEVICES SHALL MEET ADA REQUIREMENTS, C. ALL WIRING DEVICES FACEPLATES SHALL BE ENGRAVED COVER/ENCLOSURE. INSULATION. EACH CONDUCTOR SHALL BE TESTED FOR INSULATION FROM K. CONTRACTOR SHALL SUBMIT SIGNED AND SEALED PLANS INDICATING EXACT WITH THE PANELBOARD DESIGNATION AND CIRCUIT NUMBER 1616E - CABINETS AND ENCLOSURES GROUND AND FROM OTHER CONDUCTORS. LOCATION, TYPE, CABLING, AND BATTERY CALCULATIONS, SERVING THE OUTLET, LABEL TAPE WILL NOT BE A. CABINETS SHALL BE GALVANIZED STEEL WITH GRAY BAKED ENAMEL FINISH 3, ANY PORTIONS OF THE INSTALLATIONS WHICH FAIL TO PASS THESE L ALL WIRING SHALL BE IN 314•X. MINIMUM. ACCEPTABLE AND SHALL BE SIZED AS REQUIRED OR INDICATED. FRONTS SHALL BE TESTS SHALL BE REPLACED, REPAIRED OR OTHERWISE CORRECTED TO THE SATISFACTION OF THE OWNER'S REPRESENTATIVE, AND COMPLETELY M. VENDOR �� � -�M � SYSTEM � �� CfRTiFRCI►TION D. OUTLET BOXES STEEL, FLUSH OR SURFACE TYPE INDICATED WITH CONCEALED HINGE, AND FLUSH LOCK KEYED TO MATCH BRANCH CIRCUIT PANELBOARD. FINISH WITH RETESTED TO SHOW PROPER CONFORMITY. AND SMOKE DETECTOR SENSITIVITY FEW PRIOR TO ANY NSPECTION. 1. OUTLET BOXES SHALL BE UL LISTED, AND OF SIZES AND TYPES GRAY BAKED ENAMEL. 4. CONTRACTOR IS RESFONSELIE FOR TESTNG THE EFFECTIVENESS OF THE N. SYNCHRONIZE ALL AUDIOVISUAL DEVICES. REQUIRED FOR THE APPLICATION, OUTLET BOXES SHALL BE SHEET B. ENCLOSURES SHALL BE NEMA 250, TYPE 1 OR 3R. AS INDICATED ON GROUNDING SYSTEM FOR ALL ELECTRICAL DEICES N THE SCOPE OF 0. AUDIBLE DEVICES SHALL BE ON SEPARATE CIRCUITS THAN VISUAL DEVICES. STEEL, NO LIGHTER THAN 14 GAUGE, GALVANIZED AFTER FABRICATION. SET BOX SO FACE OF BOX WILL FINISH FLUSH WITH BUILDING SURFACE. DRAWINGS, THEY SHALL HAVE CONTINUOS HINGED COVERS. PROVIDE WORK AREA BY VOLTAGE AND IMPEDANCE MEASUREMENTS AS INDICATED N NFPA 99, 4,3,3!1.3 & 43,3,1.4 RESPECTIVELY. THE RESULTS SHALL BE P. UPON ACTIVATION OF THE FIRE ALARM SYSTEM, THE AHU SHALL SHUT DOWN a. FOR LIGHTING FIXTURE OUTLETS: 4 INCH SQUARE BY 1- INTERIOR METAL PANEL FOR MOUNTING TERMINAL BLOCKS AND ELECTRICAL COMPONENTS; FINISH WITH WHITE ENAMEL ENCLOSURE FINISH SHALL BE RECORDED 07H A ME-IER THAT HAS BEN CALERATED WITHIN THE LAST WHEN IN MANUAL OR AUTOMATIC POSITION. EXHAUST FAN SHALL BE INTERLOCKED WITH THE AHU STARTER. LOCATE FIRE ALARM RELAY WITHIN 1/2 INCHES DEEP WITH RAISED FIXTURE RING. MANUFACTURER'S STANDARD ENAMEL 12 MONTHS. THE METER AND TYPED OR PRNTFD RECORDED RESULTS 3' -0' OF STARTER, b, FOR WALL SWITCHES, RECEPTACLES. AND COMMUNICATION SHALL BE MADE AVAILABLE AT TIME OF FINAL INSPECTION. USE: 4 INCH SQUARE, BY 1 -1/2 INCHES DEEP, USE BOXES 16190 - SUPPORTING DEVICES J. THE EQUIPMENT GROUNDING TERMINAL BUSES OF THE NORMAL AND 16741 - TELEPHONE AND DATA COMMUNICATIONS WITH PLASTER RINGS IN ALL PLASTERED WALLS WHERE A. ACCEPTABLE MANUFACTURERS: UNISTRUT CORP., B -LINE SYSTEMS, INC., AND MIDLAND ROSS- KINDORF. ESSENTIAL BRANCH - CIRCUIT PANELBOARDS SERVING THE SAME A. AT ALL WALL DATA/VOICE OUTLET LOCATIONS, PROVIDE A 4 11/16' SQUARE WALL THICKNESS PERMITS. USE BOXES LESS THAN 1-1/2 / INCH DEEP ONLY IN LOCATIONS WHERE DEEP BOXES B. FURNISH AND INSTALL ALL HANGERS AND SUPPORTS REQUIRE) BY INDIVIDUAL PATIENT VICINITY SHALL BE BONDS) TOGETHER WITH AN BOX WITH SINGLE -GANG ADAPTER AND BLANK COVER PLATE. 1" MIN. EMPTY CANNOT BE ACCOMMODATED BY CONSTRUCTION. RACEWAY SYSTEMS. INSULATED CONTINUOUS COPPER CONDUCTOR NOT SMALLER THAN 10 CONDUIT SHALL RUN WITH PULL CORD TO 6' ABOVE NEAREST ACCESSIBLE C. HANGERS SHALL BE SUPPORTED BY MEANS OF UNCOATED SOLID STEEL AWG. WHERE TWO OR MORE PANELBOARDS SERVING THE SAME INDIVIDUAL CORRIDOR CEILING SPACE WHERE CORRIDORS DO NOT HAVE ACCESSIBLE E PULL CORDS RODS WHICH ARE THREADED TO ALLOW VERTICAL ADJUSTMENTS. LOCK PATIENT VICINITY ARE SERVED FROM SEPARATE TRANSFER SWITCHES ON CEILINGS, PROVIDE CONDUIT SLEEVES AS A MINIMUM ONE PER SYSTEM 1. PROVIDE A NYLON POLYETHYLENE CORD, WITH A TENSILE STRENGTH OF NUTS SHALL BE PROVIDED IN SUFFICIENT NUMBER AND LOCATION TO LOCK THE EMERGENCY SYSTEM, THE EQUIPMENT GROUNDING TERMINAL BUSES COVERING THE ENTIRE LENGTH OF NON - ACCESSIBLE (FILING CAVITY, NUMBER NOT LESS THAN 200 POUNDS, IN EACH EMPTY CONDUIT TO FACILITATE ALL ROD ADJUSTMENTS PERMANENTLY AT THE ADJUSTED HEIGHT. TWO OF THOSE PANELBOARDS SHALL BE BONDED TOGETHER WITH AN AND SIZE OF CONDUIT/SLEEVES SHALL BE PER MANUFACTURER'S CABLING THE FUTURE INSTALLATION OF CONDUCTORS. INCORPORATE PLASTIC TAGS LOA( NUTS SHALL BE USED UNLESS THE NUT TIGHTENS AGAINST A INSULATED CONTINUOUS COPPER CONDUCTOR NOT SMALLER THAN 10 REQUIREMENTS, FOR IDENTIFICATION. THREADED SOCKET. MINIMUM ROD DIAMETERS SHALL BE AS FOLLOWS: AWG, THIS CONDUCTOR SMALL BE PERMITTED TO BE BROKEN IN ORDER TO TERMINATE ON THE EQUIPMENT GROUNDING TERMINAL BUS IN EACH B. PROVIDE A MINIMUM OF A 3 /16' DIAMETER, TWISTED NYLON PLASTIC CORD F. SEGREGATION OF WIRING SYSTEMS NOMINAL CONDUIT SIZE ROD DIAMETER PANELBOARD, IN ALL EMPTY RACEWAYS. PROVIDE A IDENTIFICATION TAG ON EACH END 1. SEGREGATION OF WIRING SYSTEMS SHALL NOT BE COMPROMISED BY 1/2' THROUGH 2' 1/4' 16475 - OVERCURRENT PROTECTIVE DEVICES INDICATING THE LOCATION OF THE OTHER END, THE USE OF COMMON PULLBOXES, WIREWAYS, CABINETS OR ANY 2 -1/2' THROUGH 3' 3/8" A. PROVIDE DATA SHEETS SHOWING ELECTRICAL CHARACTERISTICS INCLUDING C. INSTALL DATA /COMMUNICATIONS OUTLETS AT SAME HEIGHT SPECIFIED FOR OTHER TYPE OF ENCLOSURE 2. THE RACEWAY SYSTEM FOR EACH FEEDER SHALL BE A SEPARATE 4' AND 5" 1/2' TIME-CURRENT CURVES AS PART OF THE SHOP DRAWING SUBMITTAL CONVENIENCE OUTLETS U.N.O. GROUP TELEPHONE AND DATA COMMUNICATIONS OUTLETS WITH RELATED RECEPTACLE OUTLETS U.N.O. SYSTEM COMPLETELY FAULT ISOLATED FROM ALL OTHER RACEWAY SYSTEMS. D. HANGER SPACING SHALL BE AS REQUIRED FOR PROPER SUPPORT OF B. FAULT CURRENT VALUES INDICATED ON THE DRAWINGS ARE BASED ON ACTUAL AVAILABLE FAULT VALUES AT EACH SWITCHBOARD, PANELBOARD D. WHERE PLYWOOD BACKBOARDS ARE INDICATED, PROVIDE A 3/4' THICK APA RACEWAY, BUT IN NO CASE SHALL BE LESS THAN ONE HANGER PER W -0' AND ANY OTHER SIMILAR EQUIPMENT. EQUIPMENT MANUFACTURERS SHALL A/D GRADE PLYWOOD, TREATED WITH FIRE RETARDANT, MINIMUM TWO (2) 3. THE RACEWAY SYSTEM FOR THE BRANCH CIRCUITS OF EACH OF RACEWAY LENGTH EXCEPT THAT CONDUIT LESS THAN 1" DIAMETER PROVIDE EQUIPMENT AND PROTECTIVE DEVICES SUITABLY RATED FOR THE COATS OF LIGHT GRAY PAINT. BACKBOARDS SHALL BE MOUNTED SIX (6') PANELBOARD SHALL BE A SEPARATE SYSTEM COMPLETELY FAULT ISOLATED FROM ALL OTHER RACEWAY SYSTEMS. SHALL BE SUPPORTED AT LEAST EVERY 6' -0', CONFIGURATIONS INDICATED RATED FOR THE AVAILABLE FAULT CURRENT INCHES A.F.F. AND EXTEND UPWARD A FULL EIGHT 8' -0' FEET OR TO THE EIGHT ( 8'-O') E WHERE NUMEROUS CONDUITS ARE RUN PARALLEL TO ONE ANOTHER, THEY INDICATED. SERIES RATING OF DEVICES IS NOT ACCEPTABLE. CEILING GRID IF LESS THAN 8'-0", 16120 - SYSTEM OF CONDUCTORS MAY BE SUPPORTED FROM A TRAPEZE TYPE HANGER ARRANGEMENT WITH C, CIRCUIT BREAKERS A. CONDUCTORS SHALL BE 98% CONDUCTIVITY SOFT DRAWN ANNEALED STRUT BOTTOM. 1. CIRCUIT BREAKER MANUFACTURER SHALL BE THE SAME AS THE 16900 - EQUIPMENT CONNECTIONS AND CONTROL WIRING COPPER, 600 VOLT, THHN/THWN INSULATION, #10 AND SMALLER - SOLID, F. SUPPORT OF HANGERS SHALL BE BY MEANS OF SUFFICIENT QUANTITIES OF SWITCHBOARD/PANELBOARD/MOTOR CONTROL CENTER MANUFACTURER, A. THE FURNISHING AND INSTALLATION OF CONTROL POWER WIRING REQUIRED FOR #8 AND LARGER - STRANDED, INDIVIDUAL AFTER SET STEEL EXPANSION SHIELDS, OR BEAM CLAMPS D. FUSES EQUIPMENT FURNISHED UNDER DIVISION 15 AND NOT SHOWN ON THE B. NO CONDUCTORS SHALL BE SMALLER THAN NO. 12, EXCEPT FOR SIGNAL ATTACHED TO STRUCTURAL STEEL, 1. ACCEPTABLE MANUFACTURERS: BUSSMAN, GOUL SHAWMUT, OR ELECTRICAL DRAWINGS SHALL BE FURNISHED UNDER DIVISION 15. CONTROL OR CONTROL CIRCUITS AND FOR INDIVIDUAL LIGHTING FIXTURE TAPS AS G. STIFF --LEGS SHALL BE FURNISHED AND INSTALLED IN CASES WHERE UTTLEFUSE POWER WIRING IS DEFINED AS THE LINE VOLTAGE (120V) POWER WIRING FOR PERMITTED BY NEC. SUPPORT FROM OVERHEAD STRUCTURE IS NOT POSSIBLE 2, FUSES SHALL HAVE 200,000 RMS SYMMETRICAL AMPERE INTERRUPTING EQUIPMENT CONTROL CABINETS. TEMPERATURE CONTROL, ENERGY MANAGEMENT, C. FOR HOME RUNS ON 120 -VOLT, 20- AMPERE BRANCH CROATS, WHERE H. CEILING MOUNTED LIGHT FIXTURES SHALL BE SUPPORTED FROM THE CAPACITY AT 600V OR LESS, CURRENT LIMITING TYPE; TIME DELAY OR BUILDING AUTOMATION SYSTEM PANELS AND LINE VOLTAGE SMOKE/FIRE LENGTH OF RUN FROM PANELBOARD TO FIRST OUTLET EXCEEDS 100 BUILDING STRUCTURE AT TWO OPPOSITE CORNERS. THE CONTRACTOR CHARACTERISTICS - 10 SECONDS (MINIMUM) AT 500% RATED CURRENT, DAMPERS. LINEAR FEET, USE N0, 10 CONDUCTORS WHERE LENGTH OF RUN IS 100 SHALL PROVIDE FIXTURE HANGERS TO PROPERLY INTERFACE WITH THE UL CLASS RK1. B. THE FURNISHING AND INSTALLATION OF THE TEMPERATURE CONTROL WIRING. LINEAR FEET OR LESS, USE NO. 12 CONDUCTORS. CEILING SYSTEM. E SELF- CONTAINED CIRCUIT BREAKER ENCLOSURES SHALL BE PADLOCKABLE ENERGY MANAGEMENT SYSTEM OR BUILDING AUTOMATION MIRING NOT SHOWN D. FOR HOME RUNS ON 277 -VOLT, 20- AMPERE BRANCH CIRCUITS, WHERE 1• FURNISH AND INSTALL COMPLETE ANY ADDITIONAL STRUCTURAL SUPPORT NEMA 1, EXCEPT FOR UNITS IN DAMP OR WET AREAS WHICH SHALL BE A ON THE ELECTRICAL DRAWINGS SHALL BE FURNISHED UNDER DIVISION 15. LENGTH OF RUN FROM PANELBOARD TO FIRST OUTLET EXCEEDS 200 STEEL BRACKETS, FASTENERS, ETC. AS REQUIRED TO ADEQUATELY NEMA 3R ENCLOSURE WITH CONDUIT HUBS TEMPERATURE CONTROL. ENERGY MANAGEMENT SYSTEM AND BUILDING LINEAR FEET, USE NO. 10 CONDUCTORS. WHERE LENGTH OF RUN IS 140 SUPPORT ALL RACEWAY AND EQUIPMENT . J. SUPPORT OF HANGERS FROM CONCRETE SLABS SHALL BE BY MEANS OF F. ENCLOSURES FOR SEE- CONTAINED UNITS SHALL BE SECURELY MOUNTED TO AUTOMATION SYSTEM WIRING IS DEFINED AS THE INTERLOCK OR INTERCONNECTING WIRING REQUIRED BETWEEN SYSTEM CONTROL DEVICES, LINEAR FEET OR LESS, USE NO. 12 CONDUCTORS. SUFFICIENT QUANTITY OF U BRACKETS ATTACHED WITH AFTER SET WALL AND SHALL BE LEVEL AND TRUE. MOUNTING HEIGHT SHALL BE PLUS 54' A.F.F. TO CENTER OF BREAKER U.N.O. APPURTENANCES AND CONTROL PANELS TO ALLOW THE SYSTEM TO FUNCTION . E MORE THAN FIVE CONDUCTORS (3 PHASE, 1 NEUTRAL, AND 1 MOUND) EXPANSION SHIELDS AND BOLTS. AUTOMATICALLY. THIS INCLUDES WIRING BETWEEN THE FIRE ALARM SYSTEM, SH SH ALL BE INSTALLED IN A COMMON BRANCH CIRCUIT CONDUIT. S FURNISH A NUMBER OF SPARE FUSES EQUALING 10% OF QUANTITY SMOKE EXHAUST SYSTEMS, DOOR ENTRY SYSTEMS AND ANY OTHER SYSTEM F. PROVIDE COLOR CODED CABLE SYSTEM APPROVED BY OWNER. 16195 - ELECTRICAL IDENTIFICATION INSTALLED BUT NOT LESS THAN THREE (3) FUSES OF EACH TYPE AND REQUIRING INTERFACE WITH THE TEMPERATURE CONTROL, ENERGY MANAGEMENT IF NONE IS REQUIRED BY OWNER, PROVIDE THE FOLLOWING A. PROVIDE ELECTRICAL IDENTIFICATION FOR THE FOLLOWING: RATING. AND BUILDING AUTOMATION SYSTEM. COLOR CODING- 1. SWITCHGEARS, SWITCHBOARDS, MOTOR CONTROL CENTERS, PANELBOARDS, H. INSTALL FUSES WITH LABEL ORIENTED SUCH THAT THE MANUFACTURER, TYPE C. PROVIDE POWER WIRING TO EACH MOTOR -DRIVE AND /OR ELECTRICALLY - MOTOR STARTERS, CONTACTORS, DISCONNECT SWITCHES, CIRCUIT AND SIZE ARE EASILY READ. OPERATED SYSTEM OR UNIT OF EQUIPMENT. THE WIRING SHALL ALLOW a, 48OV/277 b. 208V/120 BREAKERS. AND OTHER ELECTRICAL EQUIPMENT WITH NAMEPLATE 16500 - LIGHTING FIXTURES THE MOTOR(S) OR EQUIPMENT TO OPERATE IN A MANUAL MODE. A PHASE -BROWN A PHASE -BLACK IDENTIFYING THE ITEM OF EQUIPMENT SERVING THE SAME. A. CONTRACTOR SHALL QUOTE THE SPECIFIED LIGHT FIXTURES IN BASE BID. D. CONTROL WIRING WILT., UNLESS SPECIFICALLY NOTED OTHERWISE, WILL BE B PHASE - ORANGE B PHASE - RED 2. RACEWAYS, JUNCTION BOXES, AND PULL BOXES, ANY PROPOSED ALTERNATES MUST BE SHOWN AS AN EXCEPTION TO BASE FURNISHED AND INSTALLED UNDER OTHER DIVISIONS OF THE SPECIFICATIONS. C PHASE - YELLOW C PHASE - BLUE 3• WIRING DEVICES, WIRING, AND THREE PHASE MOTOR ROTATION, BID AND MUST BE ACCOMPANIED BY UNIT PRICES AND TOTAL DOLLAR E. EXCEPT FOR ITEMS THAT ARE FURNISHED WITH FACTORY- INSTALLED, INTEGRAL NEUTRAL - GREY NEUTRAL - WHITE B. PROVIDE THE FOLLOWING COLOR CODING FOR ALL EQUIPMENT NAMEPLATES: DEDUCT FROM THE BASE BID, ANY PROPOSED ALTERNATE FIXTURES SHALL MOTORS, AN ELECTRIC MOTOR OF REQUIRED SIZE AND ELECTRICAL GROUND - GREEN GROUND - GREEN NORMAL SYSTEM - BLACK W/ WHITE LETTERS MATCH THE FOLLOWING SPECIFIED LIGHTING FIXTURE CHARACTERISTICS: CHARACTERISTICS WILL BE PROVIDED AND INSTALLED UNDER OTHER DIVISIONS CRITICAL BRANCH - RED W/ WHITE LETTERS PHYSICAL SIZE AND DIMENSIONS, CONSTRUCTION, MATERIAL, LAMP AND FOR EACH ITEM OF MOTOR- DRIVEN EQUIPMENT. COMPLETE THE ELECTRICAL COLOR CODING SHALL BE CONTINUOUS ON INSULATION FOR LIFE SAFETY BRANCH - YELLOW W/ WHITE LETTERS BALLAST TYPE, LENS AND REFLECTOR TYPE, PAINT APPLICATION PROCESS, INSTALLATION OF THESE MOTORS IN ACCORDANCE WITH APPROVED WIRING #6 AWWG OR SMALLER AND CONTINUOUS OR MARKED WITH EQUIPMENT SYSTEM GREEN W/ WHITE LETTERS AND PHOTOMETRIC CHARACTERISTICS. ALL RATINGS INCLUDING, BUT NOT DIAGRAMS AND INSTRUCTIONS. COLOR TAPE AT ALL CONNECTIONS FOR CONDUCTORS LARGER LIMITED TO WATTAGE, FIRE RATINGS, AND SPECIAL LOCATION RATINGS SHALL F. INHERE DISCONNECT SWITCHES OR CIRCUIT BREAKERS ARE MOfi PROVIDED THAN AWpWG, i� C. ALL NAMEPLATES SHALL INCLUDE VOLTAGE, PHASE, WIRE, BRANCH ALSO MATCH. ANY PROPOSED ALTERNATES NOT MEETING ANY OF THESE INTEGRAL WITH CONTROL EQUIPMENT FOR MOTORS AND OTHER ELECTRICAL G. INSTALLATION OF CONDUCTORS OF POWER CONNECTED TO, AND SOURCE OF POWER EQUIPMENT IS CHARACTERISTICS SHALL BE REJECTED. APPURTENANCES, PROVIDE AND INSTALL ALL DISCONNECT SWITCHES 1. PULL NO CONDUCTORS INTO CONDUITS UNTIL ALL WORK OF A NATURE FED FROM, NAMEPLATES SHALL BE LAMINATED, WHITE CORE, PLASTIC WITH B. FIXTURES SHALL BE COMPLETE WITH LAMPS, BALLASTS AND RELATED REQUIRED BY THE NATIONAL ELECTRICAL CODE AND /OR INDICATED, WHICH MAY CAUSE INJURY TO CONDUCTORS IS COMPLETED. BEVELED EDGES, MINIMUM 1/16 THICK. LETTERING SHALL BE MACHINE ENGRAVED, NOT LESS THAN 1/4' HIGH, CUT THROUGH THE SURFACE TO AUXILIARY EQUIPMENT AND ACCESSORIES NECESSARY TO THE INTENDED OPERATION, INCLUDING MOUNTING DEVICES REQUIRED FOR EACH TYPE OF S WHERE POSSIBLE, TERMINATE CONDUITS IN CONDUIT BOXES ON MOTORS 2, RUN FEEDERS IN CONTINUOUS LENGTHS, WITHOUT JOINTS OR SPLICES, THE WHITE CORE NAMEPLATES SHALL BE SECURELY ATTACHED INSTALLATION. WHERE MOTORS ARE NOT PROVIDED WI TERMINATE WITH CONDUIT BOX S, INSOFAR AS PRACTICABLE 3. RUN CONDUITS FOR EMERGENCY POWER CONDUCTORS SEPARATE FROM TO THE EQUIPMENT USING GALVANIZED SCREWS. ADHESIVES SHALL C. ALL LIGHTING FIXTURES SHALL BEAR THE UL LABEL THE CONDUITS IN CONDUIT FITTINGS THE MOTORS, ALL OTHER WIRING, NOT BE USED. D. WHERE LIGHTING FIXTURES ARE SCHEDULED WITH PLASTIC LENSES, PROVIDE ACRYLIC LENSES HAVING A THICKNESS OF 0.125 INCHES, 4. CABLE TYPE AC OR MC IS NOT ALLOWED FOR HOMERUN AND FEEDER I INSTALLATIONS ME ARCH TECT z, , ,, ,,A 160 Alhambra Circle, Suite 700 Coral Gables, Florida 38134 7.306.444.0413 F.306.441.6404 www.mgearchiteoi<s.corrt1' AA- FF000121 >1_ in association with ­1_1,412 III 0 EN WILMOT SANZ A R C H I T E C T U R E 16310 Man Avanua slaiahr0 �; iMsoe� Sri- 6�lo-�00 � 3Cn- i5eo -ateo Phi 906 DOD. M F&V M. S, M ® 2121 Ponce de Leon Blvd., Suite 350 Coral Gables, FL 33134 ionalConsultingEngineers phone: 305.569.1692 .. fax: 305.569.1693 Dallas . Houston . Nashville . Miami . Richmond " Austin . Denver . Phoenix . Washington D.C. ccrd project number: 41 1442.000 " EB00007658 Baptist N i , SOUTH f ti TOWER EAST F11- ST FLOOR RENOVA71ONS FOR O OFFICES AT THE CENTER _. FOR • AND INFANTS , lliz. =i 1r - !� • ' 1 # 100% CONSTRUCTION IOCUAENT SUBMTTAL SEAL I N (. ►J i I I i ,#4'-, . w ;� . 11 ,r q`, %I 1<111111iijill,7 f � , cq� I `'_111 y, �a - IV •10 �,� r .I , flir a t' a ` _ i a,l Ar vJ 1. � p➢..� w % 'ELf,6TRICAL ENGIi2ER . w. a'.5 °7:8.'x.• , t s,,, A ' :` .11!11100 I NOV el 2011 1 1 1 ��ELECTRICAL ­--, SPECIFICA11ONS., 0,1� .1-144 DRAWING NO i E ■ 0 () 1, !. - I '� y q' UJUU VVV U V VF +UV UV' J V UV ,U U J J J U U U U V ': J V V V J U J V V U I , J U U J U U U U ­u V, V V U )VU U U V V V v V V J U V , V , v L, V l v V V I U V V V V u I I - v JUf VUV V, .uV VVUV , U V v U JVV V V V V u I I u �. � , . v � ,�� v., ME ARCH TECT z, , ,, ,,A 160 Alhambra Circle, Suite 700 Coral Gables, Florida 38134 7.306.444.0413 F.306.441.6404 www.mgearchiteoi<s.corrt1' AA- FF000121 >1_ in association with ­1_1,412 III 0 EN WILMOT SANZ A R C H I T E C T U R E 16310 Man Avanua slaiahr0 �; iMsoe� Sri- 6�lo-�00 � 3Cn- i5eo -ateo Phi 906 DOD. M F&V M. S, M ® 2121 Ponce de Leon Blvd., Suite 350 Coral Gables, FL 33134 ionalConsultingEngineers phone: 305.569.1692 .. fax: 305.569.1693 Dallas . Houston . Nashville . Miami . Richmond " Austin . Denver . Phoenix . Washington D.C. ccrd project number: 41 1442.000 " EB00007658 Baptist N i , SOUTH f ti TOWER EAST F11- ST FLOOR RENOVA71ONS FOR O OFFICES AT THE CENTER _. FOR • AND INFANTS , lliz. =i 1r - !� • ' 1 # 100% CONSTRUCTION IOCUAENT SUBMTTAL SEAL I N (. ►J i I I i ,#4'-, . w ;� . 11 ,r q`, %I 1<111111iijill,7 f � , cq� I `'_111 y, �a - IV •10 �,� r .I , flir a t' a ` _ i a,l Ar vJ 1. � p➢..� w % 'ELf,6TRICAL ENGIi2ER . w. a'.5 °7:8.'x.• , t s,,, A ' :` .11!11100 I NOV el 2011 1 1 1 ��ELECTRICAL ­--, SPECIFICA11ONS., 0,1� .1-144 DRAWING NO i E ■ 0 () 1, !. - I