12-42-015FEEDER INPUT DATA
A. REFER TO FLOOR PLANS FOR LOCATIONS AND QUANTITIES OF ALL DEVICES.
B. PROVIDE NEW WIRING IN 3/4' CONDUIT MiNIMUM AS REQUIRED FOR ALL NEW FIRE ALARM DEVICES.
C. ALL NEW FIRE ALARM DEVICES SHALL BE PROGRAMMED INTO EXISTING FIRE ALARM CONTROL PANEL AND BE FULLY COMPATIBLE
WITH EXISTING FIRE ALARM SYSTEM.
D. PROVIDE NEW POWER SUPPLIES AS NECESSARY INCLUDING EXPANSION MODULES AND ANY NECESSARY ACCESSORIES REQUIRED
FOR A COMPLETE AND FULLY FUNCTIONAL INSTALLATION.
E. ALL NEW DEVICES SHALL MEET ALL ADA REQUIREMENTS.
F. FURNISH AND INSTALL ALL SOFTWARE AND HARDWARE NECCSSSARY FOR A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
SECOND FLOOR G. ALL AUDIO AND VISUAL DEVICES SHALL BE SYNCHRONIZED.
H. FIRE ALARM VENDOR SHALL RE- CERTIFY EXISTING SYSTEM.
D I. THE ENTIRE SYSTEM SHALL BE TESTED TO THE OWNER'S SATISFACTION. CONTRACTOR SHALL PROVIDE A COMPLETE FIRE ALARM
CERTIFICATION AND A SENSITIVITY TEST REPORT FOR ALL NEW, AND E)OSTiNG SMOKE. DUCT AND HEAT DETECTORS. CONTRACTOR
FIRE FIRE SHALL REPLACE ANY DETECTOR THAT DOES NOT MEET THE ALLOWABLE SENSITIVITY VALUES.
ALARM ALARM J. FIRE ALARM VENDOR SHALL PROVIDE SIGNED AND SEALED SHOP DRAWINGS INCLUDING:
CONT. TERM. a. LOCATIONS OF DEVICES.
PANEL ABINE b. TYPE OF DEVICES.
c. CABLING.
FIRST FLOOR d. BATTERY CALCULTATiONS.
K. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
L CONTRACTOR SHALL MAINTAIN THE INTEGRITY OF THE FIRE ALARM SYSTEM DURING CONSTRUCTION.
M. WHERE REQUIRED, THE FIRE ALARM SYSTEM SHALL BE INTERFACED WITH THE BUILDING AUTOMATION SYSTEM IN ORDER TO
SEND/RECEIVE SIGNALS FROM ALARM INITIATING DEVICES AND H -O-A SWITCHES FOR THE OPERATION OF SMOKE CONTROL
SYSTEMS, FAN SHUTDOWN AND COMMUNICATIONS. COORDINATE ALL REQUIREMENTS WiTH DIVISION 15.
PARTIAL FIRE ALARM RISER DIAGRAM
SCALE: NTS
MSB1
3,000A BUS
l 208/120V
3�, 4W
65kAIC
I
I
I
I
I
3,OOOAF
3,OOOAT
3,000A
BUS STAB
TO FPL VAULT
***** F A U L T A N A L Y S I S SUM M A R Y ****"******
BUS NAME
CABLE
FEEDER FROM FEEDER TO
QTY VOLTS LENGTH FEEDER
NAME
NAME NAME
/PH L -L
SIZE
TYPE
208.
7283.9
FDR 1CL1
BUS 2CLD1 BUS 1CL1
1 208 85.0
FEET 1/0
Copper
5788.4
0.7
Duct Material: Magnetic
Insulation Type:
PVC Insulation Class:
THWN
7120.6
+/- Impedance: 0.1280+ J
0.0540 Ohms /1000 it
25.15 + J
10.61 PU
208.
20186.1
ZO Impedance: 0.4034+ J
0.1329 Ohms /1000 ft
79.26 + J
26.11 PU
2011
FDR 1LSL1
BUS 2LSLD1 BUS 1LSL1
1 208 50.0 FEET 2
Copper
BUS 2NLD1
206.
Duct Material: Magnetic
Insulation Type:
PVC Insulation Class:
THYM
BUS 2NLD2
+/- Impedance: 0.2020 + J
0.0585 Ohms /1000 ft
23.35 + J
6.76 PU
2.2
BUS ATS -CR1 L
ZO Impedance: 0.6366 + J
0.1440 Ohms /1000 ft
73.57 + J
16.64 PU
3.8
FDR 1NL3
BUS 2NLD2 BUS 1NL3
1 208 150.0
FEET 4/0
Copper
24
BUS EDP
Duct Material: Magnetic
Insulation Type:
PVC Insulation Class:
THWN
16.6
+/- Impedance: 0.0640 + J
0.0497 Ohms /1000 ft
2219 + J
17.23 PU
51627.00
110
ZO Impedance: 0.2017 + J
0.1224 Ohms /1000 ft
69.93 + J
42,44 PU
12321.15
FOR 1NLD1
BUS 2NLD1 BUS 2NLD2
1 208 35.0
FEET 600
Copper
50758.39
6.7
Duct Material: Magnetic
Insulation Type:
PVC Insulation Class:
THWN
+/- Impedance: 0.0257 + J
0.0463 Ohms /1000 ft
2.08 + J
3.75 PU
ZO Impedance: 0.0809 + J
0.1140 Ohms/1000 ft
6.54 + J
9.22 PU
FDR 2CLD1
BUS ATS -CR1 L BUS 2CLD1
2 208 120.0
FEET 6 00
Copper
Duct Material: Magnetic
Insulation Type:
PVC Insulation Clasen
THWN
+/- Impedance: 0.0257 + J
0.0463 Ohms /1000 it
3.56 + J
6.42 PU
ZO Impedance: 0.0809 + J
0.1140 Ohms /1000 ft
11.22 + J
15.81 PU
FDR 2LSLD1
BUS ATS -LS1 L BUS 2LSLD1
1 208 115.0
FEET 250
Copper
Duct Material: Magnetic
Insulation Type:
PVC Insulation Class:
THWN
+/- Impedance. 0.0552 + J
0.0495 Ohms /1000 ft
14.67 + J
13.16 PU
ZO Impedance: 0.1739 + J
0.1219 Ohms /1000 it
46.22 + J
3240 PU
FDR 2NLD1
BUS MSB1 BUS 2NLD1
2 208 45.0
FEET 600
Copper
Duct Material: Magnetic
Insulation Type:
PVC Insulation Class:
THWN
+/- Impedance: 0.0257 + J
0.0463 Ohms /1000 it
1.34 + J
2.41 PU
ZO Impedance: 0.0809 + J
0.1140 Ohms /1000 ft
4.21 + J
5.93 PU
FDR ATS -CR1
E BUS EDP BUS ATS -CRI E 2 208 20.0 FEET 600
Copper
Duct Material: Magnetic
Insulation Types
PVC Insulation Class:
THWN
+/- Impedance: 0.0257 + J
0.0463 Ohms /1000 ft
0.5940 + J
1.07 PU
ZO Impedance. 0.0809 + J
0.1140 Ohms/1000 ft
1.87 + J
2.63 PU
FDR ATS -CR1
N BUS MSB1 BUS ATS -CR1 N 2 208 20.0 FEET 600
Copper
Duct Material: Magnetic
Insulation Type:
PVC Insulation Class:
THWN
+/- Impedance: 0.0257 + J
0.0463 Ohms /1000 ft
0.5940 + J
1.07 PU
ZO Impedance: 0.0809 + J
0.1140 Ohms/1000 ft
1.87 + J
2.63 PU
FDR ATS -LS1
E BUS EDP BUS ATS -LS1 E 1 208 20.0
FEET 250
Copper
Duct Material: Magnetic
Insulation Type:
PVC Insulation Class:
THWN
+/- Impedance: 0.0552 + J
0.0495 Ohms/1000 it
2.55 + J
229 PU
ZO Impedance: 0.1739 + J
0.1219 Ohms /1000 ft
1104 + J
5.64 PU
FDR ATS -LS1
N BUS MSB1 BUS ATS -LS1 N 1 208 10.0
FEET 250
Copper
Duct Material: Magnetic
Insulation Type:
PVC Insulation Class:
THWN
+/- Impedance: 0.0552 + J
0.0495 Ohms /1000 It
1.28 + J
1.14 PU
ZO Impedance: 0.1739 + J
0.1219 Ohms /1000 it
4.02 + J
282 PU
FDR EDP
BUS GENERATOR BUS EDP
6 208 15.0 FEET 600
Copper
Duct Material: Magnetic
Insulation Type:
PVC Insulation Class:
THWN
+/- Impedance: 0.0257 + J
0.0463 Ohms /1000 ft
0.1485 + J
0.2675 PU
ZO impedance: 0.0809 + J
0.1140 Ohms /1000 ft
0.4675 + J
0.6587 PU
FDR MSB1
BUS FPL BUS MSB1
1 208 5.0
FEET 3000
Copper
Duct Material: Busway
Insulation Type:
Epoxy Insulation Class:
Class B
+/ Impedance: 0.0046 + J
0.0026 Ohms /1000 It
0.0532 + J
0.0300 PU
ZO Impedance: 0.0273 + J
0.0139 Ohms /1000 ft
0.3155 + J
0.1606 PU
GENERATION CONTRIBUTION DATA
BUS CONTRIBUTION VOLTAGE
NAME ----
NAME---- - -____ L_ L___
MVA X"d X/R
------------------------ - - - - -- ------------------
FPL FPL 201100 11160
Three Phase Contribution: 51627.0 AMPS 8.00
Single Line to Ground Contribution: 51627.0 AMPS 8.00
Pas Sequence Impedance
(100 MVA Base) Q6669
+ J 5.33 PU
Zero Sequence Impedance
(100 MVA Base) 0.6669
+ J 5.33 PU
A. REFER TO FLOOR PLANS FOR LOCATIONS AND QUANTITIES OF ALL DEVICES.
B. PROVIDE NEW WIRING IN 3/4' CONDUIT MiNIMUM AS REQUIRED FOR ALL NEW FIRE ALARM DEVICES.
C. ALL NEW FIRE ALARM DEVICES SHALL BE PROGRAMMED INTO EXISTING FIRE ALARM CONTROL PANEL AND BE FULLY COMPATIBLE
WITH EXISTING FIRE ALARM SYSTEM.
D. PROVIDE NEW POWER SUPPLIES AS NECESSARY INCLUDING EXPANSION MODULES AND ANY NECESSARY ACCESSORIES REQUIRED
FOR A COMPLETE AND FULLY FUNCTIONAL INSTALLATION.
E. ALL NEW DEVICES SHALL MEET ALL ADA REQUIREMENTS.
F. FURNISH AND INSTALL ALL SOFTWARE AND HARDWARE NECCSSSARY FOR A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
SECOND FLOOR G. ALL AUDIO AND VISUAL DEVICES SHALL BE SYNCHRONIZED.
H. FIRE ALARM VENDOR SHALL RE- CERTIFY EXISTING SYSTEM.
D I. THE ENTIRE SYSTEM SHALL BE TESTED TO THE OWNER'S SATISFACTION. CONTRACTOR SHALL PROVIDE A COMPLETE FIRE ALARM
CERTIFICATION AND A SENSITIVITY TEST REPORT FOR ALL NEW, AND E)OSTiNG SMOKE. DUCT AND HEAT DETECTORS. CONTRACTOR
FIRE FIRE SHALL REPLACE ANY DETECTOR THAT DOES NOT MEET THE ALLOWABLE SENSITIVITY VALUES.
ALARM ALARM J. FIRE ALARM VENDOR SHALL PROVIDE SIGNED AND SEALED SHOP DRAWINGS INCLUDING:
CONT. TERM. a. LOCATIONS OF DEVICES.
PANEL ABINE b. TYPE OF DEVICES.
c. CABLING.
FIRST FLOOR d. BATTERY CALCULTATiONS.
K. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
L CONTRACTOR SHALL MAINTAIN THE INTEGRITY OF THE FIRE ALARM SYSTEM DURING CONSTRUCTION.
M. WHERE REQUIRED, THE FIRE ALARM SYSTEM SHALL BE INTERFACED WITH THE BUILDING AUTOMATION SYSTEM IN ORDER TO
SEND/RECEIVE SIGNALS FROM ALARM INITIATING DEVICES AND H -O-A SWITCHES FOR THE OPERATION OF SMOKE CONTROL
SYSTEMS, FAN SHUTDOWN AND COMMUNICATIONS. COORDINATE ALL REQUIREMENTS WiTH DIVISION 15.
PARTIAL FIRE ALARM RISER DIAGRAM
SCALE: NTS
MSB1
3,000A BUS
l 208/120V
3�, 4W
65kAIC
I
I
I
I
I
3,OOOAF
3,OOOAT
3,000A
BUS STAB
TO FPL VAULT
***** F A U L T A N A L Y S I S SUM M A R Y ****"******
BUS NAME
VOLTAGE
AVAILABLE FAULT CURRENT
EXISTING
TO REMAIN
L -L
3 PHASE
X/R LINE /GRND
X/R
BUS 1 CL1
208.
7283.9
0.8
4588.77
0.6
BUS 1 LS1.1
208.
5788.4
0.7
3580.12
0.5
BUS 1NL3
208.
7120.6
1.1
4613.33
0.9
BUS 2CLD1
208.
20186.1
2.6
15119.80
2.1
BUS 2LSLD1
2011
10766.8
1.2
7151.32
0.9
BUS 2NLD1
206.
345223
3.8
29187.90
29
BUS 2NLD2
2011
22680.3
2.8
17331.32
2.2
BUS ATS -CR1 L
208.
42261.3
4.9
38366.37
3.8
BUS ATS -LS1 L
208,
40769.6
3.3
35970.47
24
BUS EDP
208,
121725
17.9
12100.20
16.6
BUS FPL
208.
51627.0
8.0
51627.00
110
BUS GENERATOR
208.
12321.2
20.0
12321.15
20.0
BUS MSB1
208.
51277.6
7.5
50758.39
6.7
FAULT ANALYSIS REPORT COMPLETED *a°p*
'*
GENERAL NOTES:
A. NOT USED..
KEYED NOTES:
QEXISTING PANEL MODIFIED UNDER THIS PROJECT. PROVIDE NEW PANEL DIRECTORY.
2ND FLOOR NORMAL ELECTRICAL ROOM 2ND FLOOR EMERGENCY ELECTRICAL ROOM
I I
I I
I
I I
I
2 SETS EACH OF
[4 #600KCM, 1 #1/¢ G, 4" C]
I
I
SODA � 250A � 400A
I
l
I
I
•
I
I
ATS -CR1
l 800A
50kAIC
FPL VAULT i1ST FLOOR GENERATOR ROOM
2 SETS EACH OF �
[4 #600KCM, 1 #1/0 G, 4" C]
l EDP
2,500A BUS
l 208/120V
3�, 4W
1 65kAIC
I
I
I
I
I
I
l
I
I
I
I
na ELECTRIC
V I SCALE. NTS
• •
ATS -LS1
260A
4 #250KCM,1 #4 G, 2-1/2" C
800A v 250A
� 0
i
S1i!7rS]P;iU1M', 1. S TA�
4 #250KCM,
1 #4 G, 2-1/2 C
2CLD1
CRITICAL
BRANCH
4#1/0, 1 #6G,
IN 2 "C
I
I
I
I
I
I
I
I
I
6 SETS EACH OF
[4 #600KCM,
1 #600KCM G, 4" C] i
GEN -1
600kW /75OkVA
208/120V
Flodd€r Pnwor & L,IOhkCor jTFany, 6 larnI, FL, 1 1179
rebruary C, 2008
l e�rr riti oler,
F' `~ti�lttt� � i;fFrl�ri �1ras��ill�:l
'400 RV, 72nd S1'
Nffi�tnl, FL 33 t
'.T "Earl. vour lair conturcGrrL,, lP'T., abotut ftii dlv{rilrukrl i;l ult cu:rrenL at Sarullx '17urrrr Ilu ir1L rl.
r
3
l�raactT �rt'tlWir:� pltariW ,� -c,r_r I�r7.a =c pr��'a�1dWd �drEte��1 ��Irrnf�rgr' :� �, �.LML!8, tk valuLtlalA available T,larl:s�
l guilt current at liar. 500,k� +'.A. tnur .former second wrarr n ufir; 9r, r slime cd to be, 2'j",757
�rzr-,rn. to d aru�rl;�uLts at 1291! till volt , ` 13i� cal�ulafud syn rri:.tu.1 i1 ^: z 1d cua:TT r1G j, not
int n ed for use, as the awta,� fo. inot %ar starfing nnhctk iorw and doc.,s iaot inclti le:
* Car µ,id! rafiorr for w.iymutur v , nt bution o r
Bccatse; of potmatletl inspect on size and fault current omy^ ch�mges in er{uipin(w
or lour] will be need to be courrrnim, sated in vnitimr=z' Tkult current infiar cation is based
013.. lbe 1` 111.. distri%rulji ba sy,,,,Icr'rr now in place and ith:c cerstr ina :'v8tem represented is tl ^
Plans,
tile: cort trueflon lrr>wi. %eel p,ro. tcssej } t111 .y ajlw"aions or lnforrnat on Aoki u:ri,s,wr need c aln be
cornniu.n cated tht- naglr Inc, 11 leave vnlck see xnry b sitvr ss card for easy loo
'rr° 'rlyd to houring trorm � o° i is r the rlea,r 1t e,
1VILInoz
an FF1 GrOup C10111 any
I 1:7A r�l tkvl
THE LOAD DELETED AND THE LOAD ADDED iS
EQUIVALENT. THEREFORE THERE IS NO NET
CHANGE TO EXISTING LOAD.
2ND FLOOR ELECTRICAL ROOM
2LSLD1
LIFE SAFETY
BRANCH
CF-4 #3, 1 #8G, IN
1 -1/4 "C
1CL1 I SECTION 2
CRITICAL CRITICAL
BRANCH BRANCH
1 LSLi
LIFE SAFETY
BRANCH
LINETYPE LEGEND
D1581�d11710N
LI�YPE
EXISTING
TO REMAIN
NEW
CONSTRUCTION
THIRD FLOOR
I
I
I
2 SETS EACH OF
[4 #600KCM, 1 #1/0 G,
4" C] l
2NLD1
NORMAL '
BRANCH
C�_4 #600KCM, 1 #3G,
IN 4 "C I
SECOND FLOOR
4 #4/0, 1#40 IN 2-1/2"C
I
I
I
I
I
I
I
1NLD1
1NL3
I
I
I
I
I
NORMAL
NORMAL BRANCH
BRANCH
I
I
I
V U U U
J
0
U VU VU S+VU
V Us/ U
J
U U
U
V
✓ V
U J V
U U
J iJ V
V
V
J
U
U
U
JV� U V
u V
I MGEARCHITECTS
160 Alhambra Circle, Suite 700
Coral Gables, Florida 33134
T.306.444.0413 F.306.441.6404
www.mgearchitecte.com
AA- F000121
in 8H0dd#0fl with
r
W LM OT SAN Z
A R C H I T E C T U R E
P L A N N I N G
10310 Moritoorriery Villow Avenw kkr*W 206711
M-000-MW (F 301 - 0150
MmMiNNHIM
f BLU M AND A090CIA70
=800111111111AL 1210 1 1*ATTOM DiiM
FM/MK A IR tAM
Fhon.8111111.3111110 Flea1III11111.WO.M
smugam
PlltrOM AID ALAAM CO WL7Na EM24M MM
M RK N 01M1 FO UM FU)CR
MIAMI M ORDA SM
Ph , a06 . t19R . D00 FI>M:Ji06 M. M. 2M
1!
7LO B # FIOR AR0HREMUR111
= SOM ORR= AVEW t1t M =0
CR01, R.W1 t#R01
Ph 14 9 GM. SM FI0 40X Q40 . t'1A94
FLOW M R11KEM710N 10 1# CA 00000
TOM GRAM MtI A11118WAM M
41lI4D PONCE DE I 60LI1 WAM RAiM 401 CORAL
GA0.0 FLICIRDA 110M0
Ph 1 000 AM 2111111110 F" M. am EMQ
V 2121 Ponce de Leon Blvd., Suite 350
Coral Gables. FL 33134
,ofessiona �conluwng Engineers phone: 305.569.1692
fax: 305.569.1693
Dallas • Houston . Nashville . Miami . Richmond
Austin • Denver . Phoenix . Washington D.C.
cord project number: 411442.000
EB00007658
1111- 1 E ' nil
South Florida
SOUTH HOSPITAL-
EAST
FLOOR RENOVATIONS
THE • i • O
OFFICES AT THE CENTER
FOR WOMEN AND INFANTS
BE:AL ' ► I t
�' F�CEt10 G
'sr• «.
NOV %2 t 2011
DRAVVING TITLEPARTIAL
ELECTRICAL