12-42-015FEEDER INPUT DATA A. REFER TO FLOOR PLANS FOR LOCATIONS AND QUANTITIES OF ALL DEVICES. B. PROVIDE NEW WIRING IN 3/4' CONDUIT MiNIMUM AS REQUIRED FOR ALL NEW FIRE ALARM DEVICES. C. ALL NEW FIRE ALARM DEVICES SHALL BE PROGRAMMED INTO EXISTING FIRE ALARM CONTROL PANEL AND BE FULLY COMPATIBLE WITH EXISTING FIRE ALARM SYSTEM. D. PROVIDE NEW POWER SUPPLIES AS NECESSARY INCLUDING EXPANSION MODULES AND ANY NECESSARY ACCESSORIES REQUIRED FOR A COMPLETE AND FULLY FUNCTIONAL INSTALLATION. E. ALL NEW DEVICES SHALL MEET ALL ADA REQUIREMENTS. F. FURNISH AND INSTALL ALL SOFTWARE AND HARDWARE NECCSSSARY FOR A COMPLETE AND FULLY FUNCTIONAL SYSTEM. SECOND FLOOR G. ALL AUDIO AND VISUAL DEVICES SHALL BE SYNCHRONIZED. H. FIRE ALARM VENDOR SHALL RE- CERTIFY EXISTING SYSTEM. D I. THE ENTIRE SYSTEM SHALL BE TESTED TO THE OWNER'S SATISFACTION. CONTRACTOR SHALL PROVIDE A COMPLETE FIRE ALARM CERTIFICATION AND A SENSITIVITY TEST REPORT FOR ALL NEW, AND E)OSTiNG SMOKE. DUCT AND HEAT DETECTORS. CONTRACTOR FIRE FIRE SHALL REPLACE ANY DETECTOR THAT DOES NOT MEET THE ALLOWABLE SENSITIVITY VALUES. ALARM ALARM J. FIRE ALARM VENDOR SHALL PROVIDE SIGNED AND SEALED SHOP DRAWINGS INCLUDING: CONT. TERM. a. LOCATIONS OF DEVICES. PANEL ABINE b. TYPE OF DEVICES. c. CABLING. FIRST FLOOR d. BATTERY CALCULTATiONS. K. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. L CONTRACTOR SHALL MAINTAIN THE INTEGRITY OF THE FIRE ALARM SYSTEM DURING CONSTRUCTION. M. WHERE REQUIRED, THE FIRE ALARM SYSTEM SHALL BE INTERFACED WITH THE BUILDING AUTOMATION SYSTEM IN ORDER TO SEND/RECEIVE SIGNALS FROM ALARM INITIATING DEVICES AND H -O-A SWITCHES FOR THE OPERATION OF SMOKE CONTROL SYSTEMS, FAN SHUTDOWN AND COMMUNICATIONS. COORDINATE ALL REQUIREMENTS WiTH DIVISION 15. PARTIAL FIRE ALARM RISER DIAGRAM SCALE: NTS MSB1 3,000A BUS l 208/120V 3�, 4W 65kAIC I I I I I 3,OOOAF 3,OOOAT 3,000A BUS STAB TO FPL VAULT ***** F A U L T A N A L Y S I S SUM M A R Y ****"****** BUS NAME CABLE FEEDER FROM FEEDER TO QTY VOLTS LENGTH FEEDER NAME NAME NAME /PH L -L SIZE TYPE 208. 7283.9 FDR 1CL1 BUS 2CLD1 BUS 1CL1 1 208 85.0 FEET 1/0 Copper 5788.4 0.7 Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN 7120.6 +/- Impedance: 0.1280+ J 0.0540 Ohms /1000 it 25.15 + J 10.61 PU 208. 20186.1 ZO Impedance: 0.4034+ J 0.1329 Ohms /1000 ft 79.26 + J 26.11 PU 2011 FDR 1LSL1 BUS 2LSLD1 BUS 1LSL1 1 208 50.0 FEET 2 Copper BUS 2NLD1 206. Duct Material: Magnetic Insulation Type: PVC Insulation Class: THYM BUS 2NLD2 +/- Impedance: 0.2020 + J 0.0585 Ohms /1000 ft 23.35 + J 6.76 PU 2.2 BUS ATS -CR1 L ZO Impedance: 0.6366 + J 0.1440 Ohms /1000 ft 73.57 + J 16.64 PU 3.8 FDR 1NL3 BUS 2NLD2 BUS 1NL3 1 208 150.0 FEET 4/0 Copper 24 BUS EDP Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN 16.6 +/- Impedance: 0.0640 + J 0.0497 Ohms /1000 ft 2219 + J 17.23 PU 51627.00 110 ZO Impedance: 0.2017 + J 0.1224 Ohms /1000 ft 69.93 + J 42,44 PU 12321.15 FOR 1NLD1 BUS 2NLD1 BUS 2NLD2 1 208 35.0 FEET 600 Copper 50758.39 6.7 Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0257 + J 0.0463 Ohms /1000 ft 2.08 + J 3.75 PU ZO Impedance: 0.0809 + J 0.1140 Ohms/1000 ft 6.54 + J 9.22 PU FDR 2CLD1 BUS ATS -CR1 L BUS 2CLD1 2 208 120.0 FEET 6 00 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Clasen THWN +/- Impedance: 0.0257 + J 0.0463 Ohms /1000 it 3.56 + J 6.42 PU ZO Impedance: 0.0809 + J 0.1140 Ohms /1000 ft 11.22 + J 15.81 PU FDR 2LSLD1 BUS ATS -LS1 L BUS 2LSLD1 1 208 115.0 FEET 250 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance. 0.0552 + J 0.0495 Ohms /1000 ft 14.67 + J 13.16 PU ZO Impedance: 0.1739 + J 0.1219 Ohms /1000 it 46.22 + J 3240 PU FDR 2NLD1 BUS MSB1 BUS 2NLD1 2 208 45.0 FEET 600 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0257 + J 0.0463 Ohms /1000 it 1.34 + J 2.41 PU ZO Impedance: 0.0809 + J 0.1140 Ohms /1000 ft 4.21 + J 5.93 PU FDR ATS -CR1 E BUS EDP BUS ATS -CRI E 2 208 20.0 FEET 600 Copper Duct Material: Magnetic Insulation Types PVC Insulation Class: THWN +/- Impedance: 0.0257 + J 0.0463 Ohms /1000 ft 0.5940 + J 1.07 PU ZO Impedance. 0.0809 + J 0.1140 Ohms/1000 ft 1.87 + J 2.63 PU FDR ATS -CR1 N BUS MSB1 BUS ATS -CR1 N 2 208 20.0 FEET 600 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0257 + J 0.0463 Ohms /1000 ft 0.5940 + J 1.07 PU ZO Impedance: 0.0809 + J 0.1140 Ohms/1000 ft 1.87 + J 2.63 PU FDR ATS -LS1 E BUS EDP BUS ATS -LS1 E 1 208 20.0 FEET 250 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0552 + J 0.0495 Ohms/1000 it 2.55 + J 229 PU ZO Impedance: 0.1739 + J 0.1219 Ohms /1000 ft 1104 + J 5.64 PU FDR ATS -LS1 N BUS MSB1 BUS ATS -LS1 N 1 208 10.0 FEET 250 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0552 + J 0.0495 Ohms /1000 It 1.28 + J 1.14 PU ZO Impedance: 0.1739 + J 0.1219 Ohms /1000 it 4.02 + J 282 PU FDR EDP BUS GENERATOR BUS EDP 6 208 15.0 FEET 600 Copper Duct Material: Magnetic Insulation Type: PVC Insulation Class: THWN +/- Impedance: 0.0257 + J 0.0463 Ohms /1000 ft 0.1485 + J 0.2675 PU ZO impedance: 0.0809 + J 0.1140 Ohms /1000 ft 0.4675 + J 0.6587 PU FDR MSB1 BUS FPL BUS MSB1 1 208 5.0 FEET 3000 Copper Duct Material: Busway Insulation Type: Epoxy Insulation Class: Class B +/ Impedance: 0.0046 + J 0.0026 Ohms /1000 It 0.0532 + J 0.0300 PU ZO Impedance: 0.0273 + J 0.0139 Ohms /1000 ft 0.3155 + J 0.1606 PU GENERATION CONTRIBUTION DATA BUS CONTRIBUTION VOLTAGE NAME ---- NAME---- - -____ L_ L___ MVA X"d X/R ------------------------ - - - - -- ------------------ FPL FPL 201100 11160 Three Phase Contribution: 51627.0 AMPS 8.00 Single Line to Ground Contribution: 51627.0 AMPS 8.00 Pas Sequence Impedance (100 MVA Base) Q6669 + J 5.33 PU Zero Sequence Impedance (100 MVA Base) 0.6669 + J 5.33 PU A. REFER TO FLOOR PLANS FOR LOCATIONS AND QUANTITIES OF ALL DEVICES. B. PROVIDE NEW WIRING IN 3/4' CONDUIT MiNIMUM AS REQUIRED FOR ALL NEW FIRE ALARM DEVICES. C. ALL NEW FIRE ALARM DEVICES SHALL BE PROGRAMMED INTO EXISTING FIRE ALARM CONTROL PANEL AND BE FULLY COMPATIBLE WITH EXISTING FIRE ALARM SYSTEM. D. PROVIDE NEW POWER SUPPLIES AS NECESSARY INCLUDING EXPANSION MODULES AND ANY NECESSARY ACCESSORIES REQUIRED FOR A COMPLETE AND FULLY FUNCTIONAL INSTALLATION. E. ALL NEW DEVICES SHALL MEET ALL ADA REQUIREMENTS. F. FURNISH AND INSTALL ALL SOFTWARE AND HARDWARE NECCSSSARY FOR A COMPLETE AND FULLY FUNCTIONAL SYSTEM. SECOND FLOOR G. ALL AUDIO AND VISUAL DEVICES SHALL BE SYNCHRONIZED. H. FIRE ALARM VENDOR SHALL RE- CERTIFY EXISTING SYSTEM. D I. THE ENTIRE SYSTEM SHALL BE TESTED TO THE OWNER'S SATISFACTION. CONTRACTOR SHALL PROVIDE A COMPLETE FIRE ALARM CERTIFICATION AND A SENSITIVITY TEST REPORT FOR ALL NEW, AND E)OSTiNG SMOKE. DUCT AND HEAT DETECTORS. CONTRACTOR FIRE FIRE SHALL REPLACE ANY DETECTOR THAT DOES NOT MEET THE ALLOWABLE SENSITIVITY VALUES. ALARM ALARM J. FIRE ALARM VENDOR SHALL PROVIDE SIGNED AND SEALED SHOP DRAWINGS INCLUDING: CONT. TERM. a. LOCATIONS OF DEVICES. PANEL ABINE b. TYPE OF DEVICES. c. CABLING. FIRST FLOOR d. BATTERY CALCULTATiONS. K. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. L CONTRACTOR SHALL MAINTAIN THE INTEGRITY OF THE FIRE ALARM SYSTEM DURING CONSTRUCTION. M. WHERE REQUIRED, THE FIRE ALARM SYSTEM SHALL BE INTERFACED WITH THE BUILDING AUTOMATION SYSTEM IN ORDER TO SEND/RECEIVE SIGNALS FROM ALARM INITIATING DEVICES AND H -O-A SWITCHES FOR THE OPERATION OF SMOKE CONTROL SYSTEMS, FAN SHUTDOWN AND COMMUNICATIONS. COORDINATE ALL REQUIREMENTS WiTH DIVISION 15. PARTIAL FIRE ALARM RISER DIAGRAM SCALE: NTS MSB1 3,000A BUS l 208/120V 3�, 4W 65kAIC I I I I I 3,OOOAF 3,OOOAT 3,000A BUS STAB TO FPL VAULT ***** F A U L T A N A L Y S I S SUM M A R Y ****"****** BUS NAME VOLTAGE AVAILABLE FAULT CURRENT EXISTING TO REMAIN L -L 3 PHASE X/R LINE /GRND X/R BUS 1 CL1 208. 7283.9 0.8 4588.77 0.6 BUS 1 LS1.1 208. 5788.4 0.7 3580.12 0.5 BUS 1NL3 208. 7120.6 1.1 4613.33 0.9 BUS 2CLD1 208. 20186.1 2.6 15119.80 2.1 BUS 2LSLD1 2011 10766.8 1.2 7151.32 0.9 BUS 2NLD1 206. 345223 3.8 29187.90 29 BUS 2NLD2 2011 22680.3 2.8 17331.32 2.2 BUS ATS -CR1 L 208. 42261.3 4.9 38366.37 3.8 BUS ATS -LS1 L 208, 40769.6 3.3 35970.47 24 BUS EDP 208, 121725 17.9 12100.20 16.6 BUS FPL 208. 51627.0 8.0 51627.00 110 BUS GENERATOR 208. 12321.2 20.0 12321.15 20.0 BUS MSB1 208. 51277.6 7.5 50758.39 6.7 FAULT ANALYSIS REPORT COMPLETED *a°p* '* GENERAL NOTES: A. NOT USED.. KEYED NOTES: QEXISTING PANEL MODIFIED UNDER THIS PROJECT. PROVIDE NEW PANEL DIRECTORY. 2ND FLOOR NORMAL ELECTRICAL ROOM 2ND FLOOR EMERGENCY ELECTRICAL ROOM I I I I I I I I 2 SETS EACH OF [4 #600KCM, 1 #1/¢ G, 4" C] I I SODA � 250A � 400A I l I I • I I ATS -CR1 l 800A 50kAIC FPL VAULT i1ST FLOOR GENERATOR ROOM 2 SETS EACH OF � [4 #600KCM, 1 #1/0 G, 4" C] l EDP 2,500A BUS l 208/120V 3�, 4W 1 65kAIC I I I I I I l I I I I na ELECTRIC V I SCALE. NTS • • ATS -LS1 260A 4 #250KCM,1 #4 G, 2-1/2" C 800A v 250A � 0 i S1i!7rS]P;iU1M', 1. S TA� 4 #250KCM, 1 #4 G, 2-1/2 C 2CLD1 CRITICAL BRANCH 4#1/0, 1 #6G, IN 2 "C I I I I I I I I I 6 SETS EACH OF [4 #600KCM, 1 #600KCM G, 4" C] i GEN -1 600kW /75OkVA 208/120V Flodd€r Pnwor & L,IOhkCor jTFany, 6 larnI, FL, 1 1179 rebruary C, 2008 l e�rr riti oler, F' `~ti�lttt� � i;fFrl�ri �1ras��ill�:l '400 RV, 72nd S1' Nffi�tnl, FL 33 t '.T "Earl. vour lair conturcGrrL,, lP'T., abotut ftii dlv{rilrukrl i;l ult cu:rrenL at Sarullx '17urrrr Ilu ir1L rl. r 3 l�raactT �rt'tlWir:� pltariW ,� -c,r_r I�r7.a =c pr��'a�1dWd �drEte��1 ��Irrnf�rgr' :� �, �.LML!8, tk valuLtlalA available T,larl:s� l guilt current at liar. 500,k� +'.A. tnur .former second wrarr n ufir; 9r, r slime cd to be, 2'j",757 �rzr-,rn. to d aru�rl;�uLts at 1291! till volt , ` 13i� cal�ulafud syn rri:.tu.1 i1 ^: z 1d cua:TT r1G j, not int n ed for use, as the awta,� fo. inot %ar starfing nnhctk iorw and doc.,s iaot inclti le: * Car µ,id! rafiorr for w.iymutur v , nt bution o r Bccatse; of potmatletl inspect on size and fault current omy^ ch�mges in er{uipin(w or lour] will be need to be courrrnim, sated in vnitimr=z' Tkult current infiar cation is based 013.. lbe 1` 111.. distri%rulji ba sy,,,,Icr'rr now in place and ith:c cerstr ina :'v8tem represented is tl ^ Plans, tile: cort trueflon lrr>wi. %eel p,ro. tcssej } t111 .y ajlw"aions or lnforrnat on Aoki u:ri,s,wr need c aln be cornniu.n cated tht- naglr Inc, 11 leave vnlck see xnry b sitvr ss card for easy loo 'rr° 'rlyd to houring trorm � o° i is r the rlea,r 1t e, 1VILInoz an FF1 GrOup C10111 any I 1:7A r�l tkvl THE LOAD DELETED AND THE LOAD ADDED iS EQUIVALENT. THEREFORE THERE IS NO NET CHANGE TO EXISTING LOAD. 2ND FLOOR ELECTRICAL ROOM 2LSLD1 LIFE SAFETY BRANCH CF-4 #3, 1 #8G, IN 1 -1/4 "C 1CL1 I SECTION 2 CRITICAL CRITICAL BRANCH BRANCH 1 LSLi LIFE SAFETY BRANCH LINETYPE LEGEND D1581�d11710N LI�YPE EXISTING TO REMAIN NEW CONSTRUCTION THIRD FLOOR I I I 2 SETS EACH OF [4 #600KCM, 1 #1/0 G, 4" C] l 2NLD1 NORMAL ' BRANCH C�_4 #600KCM, 1 #3G, IN 4 "C I SECOND FLOOR 4 #4/0, 1#40 IN 2-1/2"C I I I I I I I 1NLD1 1NL3 I I I I I NORMAL NORMAL BRANCH BRANCH I I I V U U U J 0 U VU VU S+VU V Us/ U J U U U V ✓ V U J V U U J iJ V V V J U U U JV� U V u V I MGEARCHITECTS 160 Alhambra Circle, Suite 700 Coral Gables, Florida 33134 T.306.444.0413 F.306.441.6404 www.mgearchitecte.com AA- F000121 in 8H0dd#0fl with r W LM OT SAN Z A R C H I T E C T U R E P L A N N I N G 10310 Moritoorriery Villow Avenw kkr*W 206711 M-000-MW (F 301 - 0150 MmMiNNHIM f BLU M AND A090CIA70 =800111111111AL 1210 1 1*ATTOM DiiM FM/MK A IR tAM Fhon.8111111.3111110 Flea1III11111.WO.M smugam PlltrOM AID ALAAM CO WL7Na EM24M MM M RK N 01M1 FO UM FU)CR MIAMI M ORDA SM Ph , a06 . t19R . D00 FI>M:Ji06 M. M. 2M 1! 7LO B # FIOR AR0HREMUR111 = SOM ORR= AVEW t1t M =0 CR01, R.W1 t#R01 Ph 14 9 GM. SM FI0 40X Q40 . t'1A94 FLOW M R11KEM710N 10 1# CA 00000 TOM GRAM MtI A11118WAM M 41lI4D PONCE DE I 60LI1 WAM RAiM 401 CORAL GA0.0 FLICIRDA 110M0 Ph 1 000 AM 2111111110 F" M. am EMQ V 2121 Ponce de Leon Blvd., Suite 350 Coral Gables. FL 33134 ,ofessiona �conluwng Engineers phone: 305.569.1692 fax: 305.569.1693 Dallas • Houston . Nashville . Miami . Richmond Austin • Denver . Phoenix . Washington D.C. cord project number: 411442.000 EB00007658 1111- 1 E ' nil South Florida SOUTH HOSPITAL- EAST FLOOR RENOVATIONS THE • i • O OFFICES AT THE CENTER FOR WOMEN AND INFANTS BE:AL ' ► I t �' F�CEt10 G 'sr• «. NOV %2 t 2011 DRAVVING TITLEPARTIAL ELECTRICAL 1 22MM DRAVWINQ NO E3,00 I I n I