12-42-013i
ol FIRST FLOOR DEMOLITION PLAN - ELECTRIC
SCALE V<' • 1' -0'
`\
L ,} \ \\
\
\
\
\
\
DEMOLITION NOTES:
A. CONTRACTOR SHALL UPDATE ALL ELECTRICAL PANEL SCHEDULES AFFECTED BY THIS DEMOLITION. HAND WRITTEN SCHEDULES ARE NOT ACCEPTED.
SCHEDULES SHALL BE TYPED OR COMPUTER GENERATED.
B. ALL CIRCUITS SHOWN ARE FOR REFERENCE PURPOSES ONLY. CONTRACTOR SHALL VERIFY ALL CIRCUITS TO BE REMOVED PRIOR TO COMMENCEMENT
OF WORK.
C. THE CONTRACT DOCUMENTS DO NOT PROPOSE TO SHOW ALL EXISTING SYSTEMS, MATERIAL OR EQUIPMENT. IT IS THE RESPONSIBILITY OF THE
ELECTRICAL CONTRACTOR TO OBTAIN DATA RELATED TO EXISTING CONDITIONS FROM EXISTING DOCUMENTS, NOTATIONS, PHOTOGRAPHS, SURVEYS
AND OTHER OBSERVATIONS AT THE SITE.
D. REMOVE EXISTING WIRE, CONDUIT, EQUIPMENT, FIXTURES AND OTHER ITEMS TO PROVIDE ACCESS FOR WORK IN EXISTING FACILITIES. REINSTALL AND
REFINISH ITEMS REMOVED, OR OTHERWISE DAMAGED, TO MATCH EXISTING AT NO ADDITIONAL COST TO OWNER.
E. WHERE EXISTING FUNCTIONS TO REMAIN IN USE ARE DISRUPTED, THEY SHALL BE FULLY RESTORED AFTER DISRUPTION, IN FULL COMPLIANCE WITH
APPLICABLE CODES AND STANDARDS.
F. MODIFY , REMOVE, OR RELOCATE MATERIALS AND ITEMS INDICATED ON THE DRAWINGS OR REQUIRED DUE TO THE DEMOLITION WORK.
G. WORK JOINTLY WITH THE ARCHITECT, ESTABLISH AND MARK SALVAGE AND DEMOLITION ITEMS BEFORE COMMENCING WORK; REPORT ITEMS SCHEDULE
FOR RELOCATION, REINSTALLATION OR REUSE, WHICH ARE FOUND TO BE IN DAMAGED CONDITION; AWAIT FURTHER INSTRUCTIONS FROM THE
ARCHITECT BEFORE COMMENCING WITH WORK.
H. DEMOLITION EQUIPMENT, DEVICES AND MATERIAL SHALL BE REMOVED FROM THE SITE AND DISPOSED OF BY THE CONTRACTOR. SALVAGED EQUIPMENT
AND DEVICES SHALL BE THE PROPERTY OF THE OWNER UNLESS NOTED OTHERWISE.
I. MAKE RELOCATION NECESSITATED BY THE CONDITIONS AT THE SITE OR AS DIRECTED BY THE ARCHITECT, WITHOUT ADDITIONAL COST TO THE OWNER.
REPAIR, REPLACE AND /OR RESTORE TO GOOD FUNCTIONAL CONDITION, EQUIPMENT, MATERIAL AND ITEMS SCHEDULE FOR RELOCATION, WHICH ARE
DAMAGED DURING DISMANTLING OR REASSEMBLE OPERATIONS. PROVIDE NEW MATERIALS, FITTINGS AND APPURTENANCES REQUIRED TO COMPLETE THE
RELOCATION AND TO RESTORE TO GOOD OPERATING ORDER. PERFORM THE RELOCATION WORK IN ACCORDANCE TO APPLICABLE CODES ASD
STANDARDS, USING SKILLED WORKERS.
J. RELOCATING DEVICES: REMOVE AND REINSTALL IN LOCATIONS DESIGNATED BY THE ARCHITECT, TEMPERATURE CONTROL SYSTEM DEVICES, RELAYS,
WIRE CONDUIT, FIXTURES, EQUIPMENT AND OTHER DEVICES REQUIRED FOR THE OPERATION OF THE VARIOUS SYSTEMS THAT ARE INSTALLED IN
EXISTING TO BE REMOVED CONSTRUCTION.
K. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE SUPPORTING OF EXISTING CONDUITS AND WIRING ABOVE CEILING SPACES WITHIN THE SCOPE OF
THE PROJECT TO COMPLY WITH CURRENT CODES. PROVIDE AN ALLOWANCE FOR 110,000.00 FOR SUCH RESUPPORTING. ALL LABOR AND MATERIALS
TO BE CHARGED TO ALLOWANCE SHALL BE DOCUMENTED AND APPROVED BY ENGINEER OR ARCHITECT PRIOR TO WORK. ANY ALLOWANCE NOT USED
SHALL BE CREDITED TO OWNER.
L ANY EXISTING JUNCTION BOXES OR RACEWAYS WHICH WILL REMAIN AFTER DEMOLITION, SHALL IDENTIFY CIRCUIT AND BE COLOR CODED PER
SPECIFICATIONS. PROVIDE COVER PLATED AS REQUIRED THROUGHOUT.
M. ALL EXISTING COVER PLATES FOR RECEPTACLES AND SWITCHES REMAINING IN THE SCOPE OF WORK AREA AFTER DEMOLITION SHALL BE REPLACED
WITH THE SAME COVER PLATES BEING USED FOR NEW WORK. PROVIDE ENGRAVING PER SPECIFICATIONS.
N. CONTRACTOR SHALL MAINTAIN THE INTEGRITY OF THE EXISTING FIRE ALARM SYSTEM DURING CONSTRUCTION.
0. ANY DATA/TELEPHONE OUTLET THAT WILL REMAIN AFTER DEMOLITION IN THE SCOPE OF WORK AREA SHALL BE REPLACED NTH TYPE USED FOR
NEW WORK. REFER TO SPECIFICATIONS.
P. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISITING CONDITIONS WITHIN THE DEMOLITION AREAS DEPICTED IN THE DEMOLITION DRAWINGS AND
SHALL ASCERTAIN THE EXTENT OF WORK REQUIRED WITHIN THE DEMOLITION AND E)4STING TO REMAIN AREAS PRIOR TO PRICING AND
COMMENCEMENT OF WORK.
Q. THE CONTRACTOR SHALL REMOVE ALL ELECTRICAL APPURTENANCES, DEVICES AND ACCESSORIES (POWER, LIGHTING, COMMUNICATIONS, AND
SYSTEMS) WITHIN THE DEMOLITION AREAS (FLOORS, WALL AND CEILINGS) AS DEPICTED/NOTED ON THE DRAWINGS (ARCHITECTURAL., HVAC, PLUMBING,
STRUCTURAL AND ELECTRICAL). ALL OTHER AREAS SHALL REMAIN -AS IS- AND ALL ELECTRICAL APPURTENANCES, DEVICES AND ACCESSORIES SHALL
REMAIN OPERATIONAL
R. THE CONTRACTOR SHALL VERIFY THAT EXISTING CIRCUIT WIRING TO BE REMOVED DO NOT DISRUPT SERVICE TO EXISTING ELECTRICAL
APPURTENANCES AND DEVICES TO REMAIN. THE CONTRACTOR SHALL PROVIDE AND INSTALL ALL NECESSARY DEVICES. EQUIPMENT AND ACCESSORIES
REQUIRED TO MAINTAIN SERVICE TO ALL E)ISTING TO REMAIN ELECTRICAL APPURTENANCES, DEVICES AND EQUIPMENT.
S. THE CONTRACTOR SHALL REMOVE ALL CONDUIT AND WIRES ASSOCIATED WITH DEVICES AND EQUIPMENT TO BE REMOVED, BACK TO SOURCE.
GENERALNOTES:
A. CONTRACTOR SHALL ENSURE THE FIRE ALARM SYSTEM REMAINS FULLY
OPERATIONAL DURING AND AFTER CONSTRUCTION.
KEYED NOTES:
QDISCONNECT AND REMOVE ALL ELECTRICAL EQUIPMENT, DEVICES, CONDUITS AND
WIRING BACK TO SOURCE; INCLUDING POWER AND SYSTEMS DEVICES IN THIS
AREA U.N.O. ALL EXISTING RACEWAYS PASSING THROUGH THIS AREA THAT
SERVE AREAS OUTSIDE THE SCOPE OF WORK SHALL REMAIN. PROVIDE
SUPPORTS FOR THESE RACEWAYS IF THEY ARE NOT PROPERLY SUPPORTED.
ALL OTHER RACEWAYS SHALL BE REMOVED.
OEXISTING LIGHT FIXTURES TO BE RELOCATED. REFER TO
SHEET 02/E2.01 FOR FINAL LOCATION. EXTEND CONDUIT AND
WIRE AS REQUIRED TO ENSURE A FULLY FUNCTIONAL AND
OPERATIONAL SYSTEM.
EXISTING LIGHT SWITCH TO BE RELOCATED. REFER TO SHEET
02/E2.01 FOR FINAL LOCATION. EXTEND CONDUIT AND WIRE
AS REQUIRED TO ENSURE A FULLY FUNCTIONAL AND
OPERA11ONAL SYSTEM.
LEGEND
alNa►rloN
UNMIlim
EXISTING TO
BE REMOVED
------------------------
EXISTING
TO REMAIN
FIR PH04T
yyyJ VV V V vVUUV U
V V VV VU VU uv VU
V V U V U V v u
V U /'1U U VvuVj
4 V U V V V
VUV VUV V U U V V V V V
V t-11, V U V V V V V V u 4U V V V V V V V V l V V
MGEARCHITECTS
150 Alhambra Circle, Suite 700
Coral Gables, Florida 33134
T.305.444.0413 F.305.441.5404
www.mgearchitecte.com
AA- F000121
in association with
3TA 0
N
WILMOT SANZ
A R C H I T E C T U R E
P L A N N I N G
14310 Av
calthalbdrs 206n
301- 500-=W (F 301 - 390 -Mao
w 2121 Ponce de Leon Blvd., Suite 35D
Coral Gables, FL 33134
Tonal Consulting Engi phone: 305.569.1692
ne s
fax: 305.569,1693
Dallas . Houston . Nashville • Miami . Richmond
Austin . Denver . Phoenix . Washington D.C.
cord project number: 411442.000
EB00007658
+ *, . 4
.� A
BEAL�
� t
�v
A„ ELECTRICAL ENGINEER ,
V)°° .
NOV 21 goil
DRAWING TrrLE
PARTIAL FIRST
FLOOR DEMO.
PLAN- ELEC.
DRAVIAWN011 ED2,01