12-42-011FIRE PROTECTION NOTES 1. PROVIDE WORKING DRAWINGS FROM THE ENGINEERED CONTRACT DRAWINGS AND SPECIFICATIONS. THE DRAWINGS SHALL MEET ALL OF THE REQUIREMENTS FOR WORKING DRAWINGS PER NFPA 13. PROVIDE SPRINKLERS AND PIPING IN LOCATIONS AND CONFIGURATION INDICATED; HOWEVER, THE CONTRACTOR SHALL COORDINATE THE LOCATION AND ELEVATION OF ALL SPRINKLERS AND PIPING WITH ALL BUILDING COMPONENTS AND SYSTEMS, PIPE SIZES SHALL NOT BE LESS THAN INDICATED ON THE DRAWINGS. 2, OBTAIN A PERMIT FOR THE WORKING DRAWINGS IN ACCORDANCE WITH LOCAL DRAWINGS AND STATE REQUIREMENTS. 3. PROVIDE WET -PIPE SPRINKLER SYSTEMS IN ACCORDANCE WITH 2004 FLORIDA BUILDING CODE, 2004 FLORIDA FIRE PREVENTION CODE, 2002 NFPA 13, AND LOCAL REQUIREMENTS. ALL PIPING, SPRINKLERS, AND COMPONENTS TO BE UL LISTED AND FM APPROVED FOR AUTOMATIC SPRINKLER SYSTEMS. 4. STORAGE ROOMS, EQUIPMENT ROOMS, AND SIMILAR AREAS ARE ORDINARY HAZARD, GROUP 1; AND EXAM ROOM, PROCEDURE ROOMS, LOBBY AREAS AND RESTROOMS ARE LIGHT HAZARD. THE SYSTEM IS DESIGNED IN ACCORDANCE WITH NFPA 13. THE SYSTEM ARE DESIGNED TO PROVIDE 0.10 AND 0,15 GPM /SQ. FT. FOR LIGHT AND ORDINARY GROUP 1 AREAS, RESPECTIVELY. 5. THE SPRINKLER SPACING SHALL BE AS INDICATED ON THE DRAWINGS BUT SHALL NOT EXCEED 225 SQ. FT AND 130 SQ. FT. FOR LIGHT AND ORDINARY HAZARD, RESPECTIVELY, EXCEPT WHERE EXTENDED COVERAGE SPRINKLERS ARE SHOWN, 6. COORDINATE ROUTING OF PIPING, ETC. WITH PLUMBING AND MECHANICAL (HVAC) ROUTING, PIPING SHALL NOT BE LOCATED ABOVE ELECTRICAL PANELS, ETC. PER NFPA 70. 7. ALL TEST/DRAIN LINES (MORE THAN 5 GALLONS) SHALL DISCHARGE DIRECTLY TO THE EXTERIOR WITH THE APPROPRIATE SPLASH PROTECTION. AUXILIARY DRAINS MAY DISCHARGE INTO MECHANICAL ROOM FLOOR DRAINS. DRAINS SHALL BE SIZED IN ACCORDANCE WITH NFPA 13 AND NFPA 14. WORKING DRAWINGS SHALL INDICATE THE LOCATION OF ALL TEST/DRAIN VALVES AND DISCHARGE POINTS. 8. ALL PIPES SERVING A SINGLE SPRINKLER ARE 1 INCH MINIMUM. PROVIDE ASTM A 53 SCHEDULE 40 STEEL PIPE FOR WELDED, THREADED, AND GROOVED FITTINGS ONLY. PROVIDE ASTM A135 OR A795 SCHEDULE 10 STEEL PIPE FOR WELDED OR ROLLED- GROOVE FITTINGS ONLY. 9. PROVIDE 1/2 -INCH RECESSED PENDENT OR CONCEALED SPRINKLERS (ORDINARY TEMPERATURE) IN INTERIOR SPACES WITH FINISHED CEILINGS, AS INDICATED ON THE DRAWINGS. SPRINKLERS SHALL BE CENTERED IN CEILING TILE (BOTH DIRECTIONS). SPRINKLERS IN GYPSUM BOARD CEILINGS SHALL BE INSTALLED UNIFORMLY AND CENTERED WITH RESPECT TO LIGHTS, ETC. SPRINKLERS IN AREAS WITHOUT CEILINGS SHALL BE PENDENT OR UPRIGHTS IN ACCORDANCE WITH NFPA 13. PROVIDE OTHER SPRINKLERS AS INDICATED ON THE DRAWINGS, COORDINATE THE LOCATION AND ELEVATION OF SPRINKLERS WITH RESPECT TO STRUCTURAL MEMBERS AND OTHER OBSTRUCTIONS IN ACCORDANCE WITH NFPA 13. 10. PROVIDE HANGERS IN ACCORDANCE WITH NFPA 13. HANGERS TYPES AND LOCATIONS IN THE CONCRETE MEMBERS MUST BE SUBMITTED TO AND APPROVED BY THE STRUCTURAL ENGINEER. 11. IN THE SMOKE COMPARTMENTS CONTAINING THE RENOVATED AREAS ALL EXISTING SPRINKLERS SHALL BE REPLACED WITH NEW SIMILAR BUILDING STANDARD QUICK RESPONSE SPRINKLERS. •l 1. FLORIDA BUILDING CODE 2007 EDITION W/ 2008 AND 2009 REVISIONS 2. FLORIDA MECHANICAL CODE, 2007 EDITION W/ 2008 AND 2009 REVISIONS 3, FLORIDA PLUMBING CODE, 2007 EDITION W/ 2008 AND 2009 REVISIONS 4. GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITAL AND HEALTH CARE FACILITIES (GUIDELINES 2006 EDITION) 5. NFPA 101 (2006) 6, FLORIDA ADMINISTRATIVE CODE 59A -3, (MARCH 2003) 7. NFPA 99 (2005) 8. STATE FIRE PREVENTION CODE 4A60 (2001) 9. AIA GUIDELINES (2006) 10, NFPA 13 (2002) FIRE PROTECTION SYMBOLS ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS. SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE. SYMBOL DESCRIPTION EX EXISTING PIPING TO REMAIN fd'. EXISTING PIPING TO BE REMOVED CONNECT NEW TO EXISTING F FIRE PROTECTION (STANDPIPE, SPRINKLER, SERVICE) DFS — DRY FIRE STANDPIPE PIPING SP — SPRINKLER PIPING (SPRK.) SDR -- SPRINKLER DRAIN RISER PIPING pSP— DRY SPRINKLER PIPING — PAP PRE - ACTION SPRINKLER PIPING -&- -10- GATE VALVE GLOBE VALVE PRESSURE REGULATION VALVE (PRV) CHECK VALVE WITH AUTOMATIC BALL DRIP 01:* D VALVE IN VERTICAL OS & Y VALVE SUPERVISED (HORIZ. POSITION/VERT. POSITION) INDICATING BUTTERFLY VALVE SUPERVISED (HORIZ. POSITION/VERT. POSITION) FCA SPRINKLER SYSTEM FLOOR CONTROL ASSEMBLY - 911204- DOUBLE CHECK VALVE ASSEMBLY (D.C.V.A.) WITH OS & Y VALVES SUPERVISED - FLOW SWITCH FIRE HOSE VALVE amain FIRE HOSE CABINET (SURFACE MOUNTED) __== FIRE HOSE CABINET (RECESSED) o-q; - 2 -WAY SIAMESE FIRE DEPARTMENT CONNECTION DIRECTION OF SLOPE DIRECTION OF FLOW CAP OUTLET OR PLUGGED OUTLET —sin UNION • QUICK RESPONSE CONCEALED SPRINKLER Q QUICK RESPONSE RECESSED PENDENT SPRINKLER O QUICK RESPONSE UPRIGHT SPRINKLER ► QUICK RESPONSE SIDEWALL SPRINKLER AFF ABOVE FINISH FLOOR AFG ABOVE FINISH GRADE A/C ABOVE HUNG CEILING AP ACCESS PANEL OR DOOR BFF BELOW FINISH FLOOR B/F BELOW FLOOR B/G BELOW GRADE GC GENERAL CONTRACTOR INV INVERT I.E. INVERT ELEVATION MH MANHOLE PRV PRESSURE REDUCING VALVE � ^i' s,l> c �� kit �`t OIL 0 I'lo� �a, .1 : N.> _• t<f1C'tUi� �£� FQFt t�l'1'1 ()VEZI• �U . °rJl�E- T V\k1'V1�41,171 ki t co) �J Su �h�rC 1 U > .t.v • pAU CU 15 IN F1CtE ��04t R(�10ll ` MIN ull 5 CALL.GU AN Y SYS'CEm uuJU uuv V I vV'vU V V V V V V V vVUJV LVU J u V V J V V U V J V L V V V v vvv a 'J U V V V V V V u V V V 1V t' V V V V V L V V iJ V L J V V v V VvV V V V V ` Vuv J c�uv vvvvU 11�1 'vu v v v JV U V U V V V V V v V v U V UVV V MGEARCHITECTS 160 Alhambra Circle, Suite 700 Coral Gables, Florida 33134 T.305.444.0413 F.305.441A404 www.mgearchitects.com AA- F000121 in association W& ail M VWILMOT SANZ A R C H I T E C T U R E P L A N N I N G 18310 Mmtgwmy Village Avam Oaillimiburg, 20979 3111 –M-20W (F 301 –= -8150 2121 Ponce; de Leon Blvd., Suite 350 Coral Gables, FL 33134 ord Consulting Engineers phone: 305.569.1692 fax: 305.569.1693 Dallas - Houston . Nashville - Miami . Richmond Austin . Denver . Phoenix . Washington D.C. ccrd project number: 411442.000 EB00007658 Baptist Health South Florida •. • w oto. 100% CONSTRUCTION IOCUMENT SURNTTAL SEAL_ 9 1 I 0 fd'. i �J A of �EyHeI ­ NEE'..'`�'�� DRAWING nn-E 1 aENERAL DRAWING NO i FO,00