12-42-011FIRE PROTECTION NOTES
1. PROVIDE WORKING DRAWINGS FROM THE ENGINEERED CONTRACT DRAWINGS AND SPECIFICATIONS. THE DRAWINGS
SHALL MEET ALL OF THE REQUIREMENTS FOR WORKING DRAWINGS PER NFPA 13. PROVIDE SPRINKLERS AND PIPING
IN LOCATIONS AND CONFIGURATION INDICATED; HOWEVER, THE CONTRACTOR SHALL COORDINATE THE LOCATION AND
ELEVATION OF ALL SPRINKLERS AND PIPING WITH ALL BUILDING COMPONENTS AND SYSTEMS, PIPE SIZES SHALL NOT
BE LESS THAN INDICATED ON THE DRAWINGS.
2, OBTAIN A PERMIT FOR THE WORKING DRAWINGS IN ACCORDANCE WITH LOCAL DRAWINGS AND STATE
REQUIREMENTS.
3. PROVIDE WET -PIPE SPRINKLER SYSTEMS IN ACCORDANCE WITH 2004 FLORIDA BUILDING CODE, 2004 FLORIDA FIRE
PREVENTION CODE, 2002 NFPA 13, AND LOCAL REQUIREMENTS. ALL PIPING, SPRINKLERS, AND COMPONENTS TO BE
UL LISTED AND FM APPROVED FOR AUTOMATIC SPRINKLER SYSTEMS.
4. STORAGE ROOMS, EQUIPMENT ROOMS, AND SIMILAR AREAS ARE ORDINARY HAZARD, GROUP 1; AND EXAM ROOM,
PROCEDURE ROOMS, LOBBY AREAS AND RESTROOMS ARE LIGHT HAZARD. THE SYSTEM IS DESIGNED IN ACCORDANCE
WITH NFPA 13. THE SYSTEM ARE DESIGNED TO PROVIDE 0.10 AND 0,15 GPM /SQ. FT. FOR LIGHT AND ORDINARY
GROUP 1 AREAS, RESPECTIVELY.
5. THE SPRINKLER SPACING SHALL BE AS INDICATED ON THE DRAWINGS BUT SHALL NOT EXCEED 225 SQ. FT AND
130 SQ. FT. FOR LIGHT AND ORDINARY HAZARD, RESPECTIVELY, EXCEPT WHERE EXTENDED COVERAGE SPRINKLERS
ARE SHOWN,
6. COORDINATE ROUTING OF PIPING, ETC. WITH PLUMBING AND MECHANICAL (HVAC) ROUTING, PIPING SHALL NOT BE
LOCATED ABOVE ELECTRICAL PANELS, ETC. PER NFPA 70.
7. ALL TEST/DRAIN LINES (MORE THAN 5 GALLONS) SHALL DISCHARGE DIRECTLY TO THE EXTERIOR WITH THE
APPROPRIATE SPLASH PROTECTION. AUXILIARY DRAINS MAY DISCHARGE INTO MECHANICAL ROOM FLOOR DRAINS.
DRAINS SHALL BE SIZED IN ACCORDANCE WITH NFPA 13 AND NFPA 14. WORKING DRAWINGS SHALL INDICATE THE
LOCATION OF ALL TEST/DRAIN VALVES AND DISCHARGE POINTS.
8. ALL PIPES SERVING A SINGLE SPRINKLER ARE 1 INCH MINIMUM. PROVIDE ASTM A 53 SCHEDULE 40 STEEL PIPE
FOR WELDED, THREADED, AND GROOVED FITTINGS ONLY. PROVIDE ASTM A135 OR A795 SCHEDULE 10 STEEL PIPE FOR
WELDED OR ROLLED- GROOVE FITTINGS ONLY.
9. PROVIDE 1/2 -INCH RECESSED PENDENT OR CONCEALED SPRINKLERS (ORDINARY TEMPERATURE) IN INTERIOR
SPACES WITH FINISHED CEILINGS, AS INDICATED ON THE DRAWINGS. SPRINKLERS SHALL BE CENTERED IN CEILING
TILE (BOTH DIRECTIONS). SPRINKLERS IN GYPSUM BOARD CEILINGS SHALL BE INSTALLED UNIFORMLY AND CENTERED
WITH RESPECT TO LIGHTS, ETC. SPRINKLERS IN AREAS WITHOUT CEILINGS SHALL BE PENDENT OR UPRIGHTS IN
ACCORDANCE WITH NFPA 13. PROVIDE OTHER SPRINKLERS AS INDICATED ON THE DRAWINGS, COORDINATE THE
LOCATION AND ELEVATION OF SPRINKLERS WITH RESPECT TO STRUCTURAL MEMBERS AND OTHER OBSTRUCTIONS IN
ACCORDANCE WITH NFPA 13.
10. PROVIDE HANGERS IN ACCORDANCE WITH NFPA 13. HANGERS TYPES AND LOCATIONS IN THE CONCRETE
MEMBERS MUST BE SUBMITTED TO AND APPROVED BY THE STRUCTURAL ENGINEER.
11. IN THE SMOKE COMPARTMENTS CONTAINING THE RENOVATED AREAS ALL EXISTING SPRINKLERS SHALL BE
REPLACED WITH NEW SIMILAR BUILDING STANDARD QUICK RESPONSE SPRINKLERS.
•l
1. FLORIDA BUILDING CODE 2007 EDITION W/ 2008 AND 2009 REVISIONS
2. FLORIDA MECHANICAL CODE, 2007 EDITION W/ 2008 AND 2009 REVISIONS
3, FLORIDA PLUMBING CODE, 2007 EDITION W/ 2008 AND 2009 REVISIONS
4. GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITAL AND HEALTH
CARE FACILITIES (GUIDELINES 2006 EDITION)
5. NFPA 101 (2006)
6, FLORIDA ADMINISTRATIVE CODE 59A -3, (MARCH 2003)
7. NFPA 99 (2005)
8. STATE FIRE PREVENTION CODE 4A60 (2001)
9. AIA GUIDELINES (2006)
10, NFPA 13 (2002)
FIRE PROTECTION SYMBOLS
ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS.
SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.
SYMBOL
DESCRIPTION
EX
EXISTING PIPING TO REMAIN
fd'.
EXISTING PIPING TO BE REMOVED
CONNECT NEW TO EXISTING
F
FIRE PROTECTION (STANDPIPE, SPRINKLER, SERVICE)
DFS —
DRY FIRE STANDPIPE PIPING
SP —
SPRINKLER PIPING (SPRK.)
SDR --
SPRINKLER DRAIN RISER PIPING
pSP—
DRY SPRINKLER PIPING
— PAP
PRE - ACTION SPRINKLER PIPING
-&- -10-
GATE VALVE
GLOBE VALVE
PRESSURE REGULATION VALVE (PRV)
CHECK VALVE WITH AUTOMATIC BALL DRIP
01:* D
VALVE IN VERTICAL
OS & Y VALVE SUPERVISED (HORIZ. POSITION/VERT. POSITION)
INDICATING BUTTERFLY VALVE SUPERVISED (HORIZ. POSITION/VERT. POSITION)
FCA
SPRINKLER SYSTEM FLOOR CONTROL ASSEMBLY
- 911204-
DOUBLE CHECK VALVE ASSEMBLY (D.C.V.A.) WITH OS & Y VALVES SUPERVISED
-
FLOW SWITCH
FIRE HOSE VALVE
amain
FIRE HOSE CABINET (SURFACE MOUNTED)
__==
FIRE HOSE CABINET (RECESSED)
o-q;
-
2 -WAY SIAMESE FIRE DEPARTMENT CONNECTION
DIRECTION OF SLOPE
DIRECTION OF FLOW
CAP OUTLET OR PLUGGED OUTLET
—sin
UNION
•
QUICK RESPONSE CONCEALED SPRINKLER
Q
QUICK RESPONSE RECESSED PENDENT SPRINKLER
O
QUICK RESPONSE UPRIGHT SPRINKLER
►
QUICK RESPONSE SIDEWALL SPRINKLER
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISH GRADE
A/C ABOVE HUNG CEILING
AP ACCESS PANEL OR DOOR
BFF BELOW FINISH FLOOR
B/F BELOW FLOOR
B/G BELOW GRADE
GC GENERAL CONTRACTOR
INV INVERT
I.E. INVERT ELEVATION
MH MANHOLE
PRV PRESSURE REDUCING VALVE
� ^i' s,l> c �� kit �`t OIL
0 I'lo� �a, .1 : N.>
_• t<f1C'tUi� �£� FQFt t�l'1'1 ()VEZI• �U . °rJl�E-
T V\k1'V1�41,171 ki t
co) �J Su �h�rC 1 U > .t.v •
pAU CU 15 IN F1CtE ��04t R(�10ll `
MIN ull 5 CALL.GU
AN Y SYS'CEm
uuJU uuv
V I
vV'vU V V
V V V
V V
vVUJV LVU J
u
V V J V
V U V J
V L V
V V
v vvv a
'J U V V V V V V u V
V V 1V t' V V
V V V L V V
iJ V L J V V v
V VvV
V
V
V V `
Vuv J c�uv
vvvvU 11�1 'vu
v v v
JV U
V U
V V V V V v V v U V
UVV
V
MGEARCHITECTS
160 Alhambra Circle, Suite 700
Coral Gables, Florida 33134
T.305.444.0413 F.305.441A404
www.mgearchitects.com
AA- F000121
in association W&
ail
M
VWILMOT SANZ
A R C H I T E C T U R E
P L A N N I N G
18310 Mmtgwmy Village Avam
Oaillimiburg, 20979
3111 –M-20W (F 301 –= -8150
2121 Ponce; de Leon Blvd., Suite 350
Coral Gables, FL 33134
ord Consulting Engineers phone: 305.569.1692
fax: 305.569.1693
Dallas - Houston . Nashville - Miami . Richmond
Austin . Denver . Phoenix . Washington D.C.
ccrd project number: 411442.000
EB00007658
Baptist Health
South Florida
•. • w
oto.
100% CONSTRUCTION
IOCUMENT SURNTTAL
SEAL_ 9 1 I
0
fd'.
i
�J
A
of
�EyHeI NEE'..'`�'��
DRAWING nn-E 1
aENERAL
DRAWING NO i FO,00