MECHANICAL SYMBOLS
ALL SYMBOLS SHOWN MAY NOT APPEAR IN ALL DRAWINGS.
SYMBOLS ARE SHOWN SCHEMATIC AND MAY NOT BE TO SCALE.
SYMBOL
DESCRIPTION
X
NEW EQUIPMENT DESIGNATION
(TOP - EQUIP. ABBREV., BOTTOM - MARK)
l..A
NEW DIFFUSER DESIGNATION
(TOP - SCHEDULE DESIG., BOTTOM - CFM)
MANUFACTURER/MODEL N0,
EXISTING EQUIPMENT DESIGNATION
(TOP - EXISTING., VAV BOX NUMBER)
y�
NEW SUPPLY VAV DESIGNATION
(TOP - SUPPLY VAV, BOTTOM - BOX NUMBER)
yA
NEW RETURN VAV DESIGNATION
(TOP - RETURN VAV, BOTTOM -- Box NUMBER)
OUTSIDE
AIR CFM
NEW EQUIPMENT
X
EXISTING EQUIPMENT
FIRE STOPPING
NEW DUCT
3575
EXISTING DUCT
- - -,
EXISTING DUCT TO BE REMOVED OR RELOCATED
®
NEW SUPPLY DIFFUSER
®
EXISTING SUPPLY DIFFUSER
EXISTING SUPPLY DIFFUSER TO BE REMOVED OR RELOCATED
NEW R/A OR EXHAUST GRILLE
EXISTING R/A OR EXHAUST GRILLE
r,
It -J
EXISTING R/A OR EXHAUST GRILLE TO BE REMOVED OR RELOCATED
NEW SLOT DIFFUSER
*r
FLEXIBLE DUCT
EXISTING SLOT DIFFUSER
DUCT MOUNTED SMOKE DETECTOR
THERMOSTAT
ST,
EXISTING THERMOSTAT TO BE REMOVED OR RELOCATED
45- PRESSURE TAP W/ VOLUME DAMPER
CONICAL TAP WITH VOLUME DAMPER
t-
CONICAL TAP W/O VOLUME DAMPER
MANUAL VOLUME DAMPER
-----------
FIRE DAMPER
---------- '
SMOKE DAMPER
0
FIRE/SMOKE DAMPER
❑M
MOTORIZED DAMPER
-®
BAROMETRIC DAMPER
- CHS -
CHILLED WATER SUPPLY PIPE
- CHR -
CHILLED WATER RETURN PIPE
- CS -
CONDENSER WATER SUPPLY PIPE
- CR -
CONDENSER WATER RETURN PIPE
- RL -
REFRIGERANT LIQUID PIPE
-� RG -
REFRIGERANT GAS PIPE
- HS -
HEATING WATER SUPPLY
-HR-
HEATING WATER RETURN
-HPS -
HIGH PRESSURE STEAM
-HPR-
HIGH PRESSURE CONDENSATE RETURN
-PCR -
PUMPED CONDENSATE RETURN
r - ---
DOMESTIC COLD WATER
- -- -
DOMESTIC HOT WATER
-- - ®- -
DOMESTIC HOT WATER RETURN
SANITARY WASTE LINE
CD -
CONDENSATE DRAIN
-7=-
DIRECTION OF SLOPE
�---
DIRECTION OF FLOW
EXPANSION LOOP
- ►r�- --
GATE VALVE
_TTY
BUTTERFLY VALVE
BALL VALVE
- i*1- --
GLOBE VALVE
TEMPERATURE AND PRESSURE RELIEF VALVE
AUTOMATIC 2 -WAY CONTROL VALVE
AUTOMATIC 3-WAY CONTROL VALVE
--
PLUG VALVE/BALANCING COCK
SOLENOID VALVE
--
CHECK VALVE
Gl
HYDRAULIC SHOCK ARRESTOR
- --Cg:+
VALVE IN VERTICAL
UNION
VACCUUM BREAKER
DD
P -TRAP
FLOOR DRAIN W/ P -TRAP
CONNECT TO EXISTING
Q
EXISTING TO BE DEMOLISHED
MECHANICAL ABBREVIATIONS
AC ABOVE CEILING EUH ELECTRIC UNIT HEATER
AFF ABOVE FINISHED FLOOR FCU FAN COIL UNIT
AI ANALOG INPUT FPB FAN POWERED BOX
AO ANALOG OUTPUT FPI FINS PER INCH
BF BELOW FLOOR GG GENERAL CONTRACTOR
BFC BELOW FINISHED CEILING MVD MANUAL VOLUME DAMPER
BG BELOW GRADE N NEW
CRU COMPUTER ROOM UNIT OBD OPPOSED BLADE DAMPER
CU CONDENSING UNIT R RELOCATED
DI DIGITAL INPUT RA RETURN AIR
DO DIGITAL OUTPUT SA SUPPLY AIR
DS DISCONNECT SWITCH UH UNIT HEATER
(E) EXISTING WHP WATER - SOURCE HEAT PUMP
EA EXHAUST AIR VAV VARIABLE AIR VALVE
EF EXHAUST FAN WH WATER HEATER
HVAC DESIGN REQUIRES
YES
NO
DUCT SMOKE DETECTOR
X
NEUTRAL
FIRE DAMPER(S)
X
MANUFACTURER/MODEL N0,
SMOKE DAMPER(S)
X
OUTSIDE
AIR CFM
FIRE RATED ENCLOSURE
X
OUTSIDE
AIR CFM
FIRE RATED ROOF/ FLOOR CEILING ASSEMBLY
X
3595
FIRE STOPPING
X
3575
SMOKE CONTROL
X
30%
ME HANI AL'E IFI ATI N
1. GENERAL
A. THE MECHANICAL SYSTEM INSTALLATION SHALL BE IN FULL
COMPLIANCE WITH THE FOLLOWING CODES AND STANDARDS:
1. STATE, COUNTY, AND CITY HEALTH AND BUILDING CODES.
2, NFPA 51B, 1999 EDITION.
3. NFPA 70, 2002 EDITION.
4. NFPA 72, 2002 EDITION.
5. NFPA 90A, 2002 EDITION.
6. NFPA 99: STANDARD FOR HEALTHCARE FACILITIES, 2005 EDITION.
7. NFPA 101, LIFE SAFETY CODE, 2003 EDITION.
8. FLORIDA BUILDING CODE, BUILDING 2007 EDITION.
WITH 2008 AND 2009 REVISIONS.
9. FLORIDA BUILDING CODE, MECHANICAL 2007 EDITION.
WITH 2008 AND 2009 REVISIONS.
10, FLORIDA BUILDING CODE, PLUMBING 2007 EDITION.
WITH 2008 AND 2009 REVISIONS.
11, OTHER NFPA CODES AS REFERENCED BY STANDARD CODES.
12, ANSI A117.1- 1992 - ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES.
13. THE AMERICANS WITH DISABILITIES ACT(ADA), ACCESSIBILITY GUIDELINES
FOR BUILDINGS AND FACILITIES -1991.
14. 2006- AIA GUIDELINES
15. NFPA - 13, 2002 EDDITION
B. THE SCOPE OF THE WORK SHALL INCLUDE THE FURNISHING AND INSTALLATION
OF THE NECESSARY MATERIAL AND LABOR TO ACCOMPLISH THE WORK
INDICATED BY THE DRAWINGS AND HEREIN SPECIFIED. ALL WORK BY THIS
CONTRACTOR SHALL CONFORM TO ALL APPLICABLE FEDERAL, STATE AND
LOCAL BUILDING CODES.
C. CONTRACTOR SHALL BE RESPONSIBLE FOR REVIEWING THE EXISTING
CONDITIONS AT THE JOB SITE BEFORE SUBMITTING PROPOSALS. SUBMISSION
OF PROPOSALS SHALL BE TAKEN AS EVIDENCE THAT SUCH INSPECTION HAS
TAKEN PLACE. THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE
COMPLETE SET OF CONSTRUCTION DOCUMENTS, AND THE LACK OF SPECIFIC
INFORMATION ON THE DRAWINGS SHALL NOT RELIEVE THE CONTRACTOR OF
ANY RESPONSIBILITY.
D. MATERIALS AND EQUIPMENT FURNISHED UNDER THIS CONTRACT SHALL BE NEW
AND SHALL BEAR THE UL LABEL WHERE APPLICABLE, UNLESS NOTED
OTHERWISE, ALL WORK SHALL BE GUARANTEED AGAINST DEFECTIVE MATERIALS
AND WORKMANSHIP FOR A PERIOD OF NOT LESS THAN ONE (1) YEAR AFTER
COMPLETION AND ACCEPTANCE BY THE OWNER.
E CONTRACTOR SHALL INSTALL MECHANICAL SYSTEMS WITHOUT INTERFERENCE
AND IN STRICT COORDINATION WITH OTHER TRADES.
F. MATERIALS AND WORKMANSHIP SHALL COMPLY WITH THE CONTRACT
DOCUMENTS AND APPLICABLE CODES AND STANDARDS. IN CASE OF
DIFFERENCE BETWEEN APPLICABLE CODES AND STANDARDS AND THE
CONTRACT DOCUMENTS, THE CONTRACTOR SHALL PROMPTLY NOTIFY THE
ARCHITECT/ENGINEER AND THE OWNER IN WRITING OF SUCH DIFFERENCE.
SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT COMPLY WITH
THE REQUIREMENTS OF APPLICABLE CODES AND STANDARDS, HE SHALL BEAR
ALL COSTS ARISING IN CORRECTING SUCH DEFECTS. APPLICABLE CODES AND
STANDARDS SHALL INCLUDE ALL ORDINANCES, AND APPLICABLE REQUIREMENTS
OF NATIONALLY ACCEPTED CODES AND STANDARDS, SHOULD THE
CONTRACTOR SUPPLY EQUIPMENT DIFFERING FROM THE SPECIFIED ITEMS IN THE
CONTRACT DOCUMENTS WITHOUT NOTIFICATION TO THE ENGINEER, HE SHALL
BEAR ALL COSTS TO UPGRADE DEFICIENCIES ARISING FROM SUCH.
G, WHERE ONLY ONE MANUFACTURER'S NAME IS LISTED IN THE EQUIPMENT
SPECIFICATION, OTHER MANUFACTURERS OF SIMILAR CHARACTERISTICS AND OF
EQUAL OR BETTER PERFORMANCE CAPACITIES MAY BE CONSIDERED FOR "OR
EQUAL" APPROVAL BY THE ENGINEER. WHERE MORE THAN ONE
MANUFACTURER IS LISTED IN THE NOTES AND EQUIPMENT SPECIFICATIONS,
ONLY THOSE NAMED MANUFACTURERS WILL BE CONSIDERED FOR APPROVAL
H. SHOULD A SUBSTITUTION BE ACCEPTED, AND SHOULD THE SUBSTITUTE
MATERIAL PROVE DEFECTIVE, OR OTHERWISE UNSATISFACTORY FOR THE
SERVICE INTENDED WITHIN THE GUARANTEE PERIOD, THIS MATERIAL OR
EQUIPMENT SHALL BE REPLACED WITH THE MATERIAL OR EQUIPMENT SPECIFIED
AT NO COST TO THE OWNER.
I. DO NOT RUN DUCTWORK, OR LOCATE EQUIPMENT, WITH RESPECT TO
SWITCHBOARDS, PANELBOARDS, POWER PANELS, MOTOR CONTROL CENTERS OR
DRY TYPE TRANSFORMERS, WITHIN 42 INCHES IN FRONT OF EQUIPMENT, OVER
EQUIPMENT, OR WITHIN 36 INCHES HORIZONTALLY OF SAME SPACE.
J. ALL INSULATING MATERIAL SHALL MEET OR BE LESS THAN ASTM STANDARDS FOR SMOKE
DEVELOPED / FLAME SPREAD RATINGS = 50/25
2, MECHANICAL DEMOLITION
A. UNLESS NOTED OTHERWISE, THE MECHANICAL DEMOLITION SHALL BE CARRIED
OUT TO THE EXTENT THAT THE FLOORS ARE RETURNED TO THE ORIGINAL BASE
BUILDING CONDITIONS. CONTRACTOR SHALL VERIFY ALL EXISTING FIELD
CONDITIONS IN ORDER TO ACCURATELY DETERMINE THE EXTENT OF THE WORK
UNDER THIS SECTION.
B. UNLESS NOTED OTHERWISE, REMOVE EXISTING INTERIOR DIFFUSERS, GRILLES,
AND DUCTWORK AS INDICATED PLANS. EXISTING DIFFUSERS AND GRILLES MAY
BE REUSED IF THEY MEET THE SCHEDULED SPECIFICATIONS, EXISTING BASE
BUILDING SLOT DIFFUSERS ARE TO REMAIN EXCEPT WHERE INDICATED ON
PLANS.
C. EXISTING DUCTWORK SHOWN ON PLANS MAY NOT EXACTLY MATCH THE ACTUAL
FIELD CONDITIONS, IT IS NOT NECESSARY TO REWORK THE DUCTWORK IN
ORDER TO MATCH WHAT IS DEPICTED ON THE PLANS. CONTRACTOR SHALL
VERIFY EXISTING DUCTWORK ROUTING AND LOCATIONS AND MAKE ADJUSTMENTS
AS REQUIRED TO AVOID CONFLICTS WITH NEW DUCTWORK, EQUIPMENT, LIGHT
FIXTURES, ETC..
D. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ENGINEERING EXPENSES
REGARDING REVIEW OF SUBSTITUTIONS.
3. MECHANICAL DUCTWORK
A. RECTANGULAR "LOW PRESSURE" SHEET METAL DUCT SHALL BE GAUGE STEEL
SHEETS AND INSTALLED IN ACCORDANCE WITH SMACNA STANDARDS FOR 1.0"
W.C. (DUCTS FOR MEDICAL WORK FABRICATED OF CONTINUOUS HOT DIP MILL
GALVANIZED MINIMUM 26 SHALL NOT BE LINED, BUT WILL BE WRAPPED WITH
INSULATING MATERIAL)
B- "LOW PRESSURE" DUCT FITTINGS SHALL BE FABRICATED OF CONTINUOUS HOT
DIP MILL GALVANIZED MINIMUM 26 GAUGE STEEL SHEETS AND INSTALLED IN
ACCORDANCE WITH SMACNA RECOMMENDATIONS FOR 0.5" W.C.
C. RECTANGULAR SHEET METAL DUCT AND FITINGS SHALL BE FABRICATED OF
FITTINGS SHALL BE FABRICATED OF CONTINUOUS HOT DIP MILL GALVANIZED
MINIMUM 26 GAUGE STEEL SHEETS AND INSTALLED IN ACCORDANCE WITH
SMACNA STANDARDS FOR 3.0" W.C. (DUCTS FOR MEDICAL WORK SHALL NOT
BE LINED, BUT WILL BE WRAPPED), CONSTRUCTION METHODS:
1. RECTANGULAR - DUCTMATE SYSTEM
2. ROUND - SPIRAL DUCT SYSTEM, METAL INNER LINER
D. RECTANGULAR DUCTS SHALL BE INSULATED WITH 3/4 POUND PER CUBIC
FOOT MINIMUM DENSITY, 2" THICK, COMMERCIAL GRADE, OWENS- CORNING
FIBERGLASS FOIL BACKED ALL SERVICE DUCT WRAP, OR EQUAL
E FLEXIBLE DUCTWORK SHALL BE FACTORY FABRICATED WITH A SPRING STEEL WIRE HELIX
BONDED TO A CONTINUOUS LAYER OF CPE INNER SLEEVE, A 1 -INCH THICK GLASS
FIBER BLANKET INSULATION LAYER, AND AN OUTER MOISTURE BARRIER JACKET OF
FOIL- BACKED KRAFT PAPER WITH INTEGRAL ATTACHING GROMMETS, MANUFACTURED BY
FLEXMASTER, THERMAFLEX OR WIREMOLD AND EQUIVALENT TO THERMAREX TYPE MKE.
IT SHALL HAVE A THERMAL CONDUCTANCE OF 0.23 BTU/HR/SQ.FT. /7 AT 757, SHALL
BE UL LISTED AND SHALL COMPLY WITH NFPA STANDARD 90A.
F. CONTRACTOR SHALL BALANCE THE HVAC SYSTEMS FOR DESIGNATED AIR CFM
QUANTITIES AND SHALL BE N.E.B.B. OR A,A.B.C. APPROVED, SUBMIT REPORT
ON NEBB, AABC, OR SMACNA FORMS FOR APPROVAL BY THE ENGINEER.
EXTENT OF BALANCING WORK TO INCLUDE REBALANCING OF EXISTING
SUPPLY RETURN AND EXHAUST SYSTEMS AS REQUIRED TO ACHIEVE DESIGN
CFM ON SUBJECT PROJECT. CONTRACTOR SHALL INSTALL MECHANICAL
SYSTEMS WITOUT INTERFERENCE AND IN STRICT COORDINATION WITH OTHER
TRADES,
G. DUCT ACCESS DOORS: PROVIDE RIGID AND CLOSE FITTING DOORS OF
GALVANIZED STEEL WITH SEALING GASKETS AND QUICK FASTENING LOCKING
DEVICES. FOR INTERNALLY LINED OR INSTALLED DUCTWORK, INSTALL MINIMUM
ONE INCH THICK INSULATION WITH SHEET METAL COVER. INSTALL AT EACH
FIRE DAMPER.DOORS TO BE EQUAL TO FLEXMASTER "THE INSPECTOR
SERIES."
H. DUCT PENETRATIONS THROUGH FIRE /SMOKE RATED PARTITIONS /WALLS SHALL
BE SEALED WITH FIRE RATED SEALANT WHICH SHALL MAINTAIN THE RATED
INTEGRITY OF THE WALL
L WHERE DUCTS PENETRATE FIRE WALLS OR PARTITIONS, FIRE DAMPERS SHALL
BE INSTALLED IN THE CONSTRUCTION IN A MANNER DIRECTED BY THE
MANUFACTURER OF THE DAMPERS, WHERE DUCTS ARE NOT RATED AS FIRE
WALLS, INSTALL 1 -1/2 x 1 -1/2 ANGLE COMPLETELY FRAMING THE OPENING
ON FOUR SIDES,
J. PENETRATION OF STRUCTURAL, LOAD BEARING WALLS SHALL BE DONE WITH
THE APPROVAL OF A STRUCTURAL ENGINEER. ALL PENETRATIONS
SHALL BE FRAMED WITH STRUCTURAL LINTELS. OPENINGS IN EXTERIOR WALLS
SHALL BE SEALED WATER TIGHT.
K. DUCT SUPPORTS:
SUPPORT HORIZONTAL DUCTWORK ON HANGERS AT INTERVALS OF NOT MORE
THAN 8' APART. ATTACH HANGERS TO OVERHEAD STRUCTURE WITH THE USE
OF APPROVED STRUCTURAL INSERTS AND SUPPORT HARDWARE. SUPPORT
HARDWARE SHALL COMPLY WITH MSS SP -69 SPECIFICATIONS.
C- CLAMPS SHALL NOT BE ALLOWED. DUCT HANGER STRAPS AND SUPPORT
RODS SHALLCOMPLY WITH SMACNA STANDARDS.
L. ALL SUPPLY AND RETURN DUCTWORK SHALL BE EXTERNALLY WRAPPED.
M. ALL HOOD EXHAUST DUCTWORK TO BE 304 STAINLESS STEEL WITH WELDED
SEAMS AND JOINTS.
4. ERODUCTS, EQUIPMENT AND EXECUTION
A. INSULATION SHALL BE PROTECTED AT HANGERS BY A SECTION OF CALCIUM
SILICATE PIPE INSULATION AND A 12" LONG HALF -ROUND SHEET METAL
SHIELD ON THE OUTSIDE OF THE INSULATION. EXTEND PIPING INSULATION
FULL THICKNESS WITHOUT INTERRUPTION THROUGH WALLS, FLOORS AND
SIMILAR PENETRATIONS.
B. PROVIDE AND INSTALL UNIONS AT PROPER POINTS TO PERMIT REMOVAL OF
A PIPE; EQUIPMENT, ETC., WITHOUT INJURY TO OTHER PARTS OF THE
SYSTEM AND TO PREVENT CORROSION DUE TO ELECTROLYSIS. ALL
EQUIPMENT SHALL BE INSTALLED IN A MANNER TO PERMIT ACCESS FOR
SERVICE WITHOUT DISASSEMBLY. UNIONS SHALL BE DIELECTRIC WHERE
DISSIMILAR MATERIALS OCCUR. PRESSURE RATINGS SAME AS FITTINGS.
C. PROVIDE INSULATION PRODUCTS MANUFACTURED BY JOHNS- MANVILLE,
OWENS- CORNING, ARMSTRONG AND CERTAINTEED. FIBERGLASS PIPE
INSULATION SHALL BE ASTM C547 -77, CLASS 1. PROVIDE BANDS, WIRES,
AND CEMENT AS RECOMMENDED BY INSULATION MANUFACTURER FOR THE
APPLICATIONS INDICATED, FLEXIBLE FIBERGLASS DUCTWORK INSULATION
SHALL BE ASTM 0553 -70, TYPE I, CLASS 83.
D. PROVIDE COMPOSITE INSULATION (INSULATION JACKETS, COVERINGS,
SEALERS, MASTICS AND ADHESIVE) WITH FLAME- SPREAD RATINGS OF 25
OR LESS AND A SMOKE- DEVELOPED RATING OF 50 OR LESS, AS TESTED
BY ASTM K04 (HFFA 255) METHOD.
E MAINTAIN INTEGRITY OF VAPOR BARRIER JACKETS ON PIPE AND DUCTWORK
INSULATION, AND PROTECT TO PREVENT PUNCTURE OR OTHER DAMAGE.
SEAL OPEN ENDS OF INSULATION WITH MASTIC. SECTIONALLY SEAL ALL BUTT
ENDS OF CHILLED WATER INSULATION OF FITTINGS WITH WHITE VAPOR
BARRIER COATING. EXTEND PIPING INSULATION WITHOUT INTERRUPTION
THROUGH WALLS, FLOORS AND SIMILAR PIPING PENETRATIONS, EXCEPT WHERE
OTHERWISE INDICATED. INSTALL PROTECTIVE METAL SHIELDS AND FOAM
GLASS INSERTS WHERE PIPE HANGERS BEAR ON OUTSIDE OF INSULATION,
F. FURNISH AND INSTALL SMOKE, FIRE AND /OR FIRE /SMOKE DAMPERS WHERE
SHOWN ON THE DRAWINGS, AND REQUIRED BY THE GOVERNING AUTHORITY.
DAMPERS SHALL BE INSTALLED AS RECOMMENDED BY SMACNA AND COMPLY
WITH U.L AND LOCAL ORDINANCES AS REQUIRED BY THE GOVERNING
AUTHORITY.
5. TEST AND BALANCE
A. TEST AND BALANCE TO BE BY OWNER.
B. TESTING AND BALANCING SHALL BE PERFORMED IN ACCORDANCE WITH
THESE SPECIFICATIONS AND IN ACCORDANCE WITH THE ASSOCIATED AIR
BALANCE COUNCIL NATIONAL STANDARDS FOR FIELD MEASUREMENT AND
INSTRUMENTATION, SECOND EDITION, 1974, OR NATIONAL ENVIRONMENTAL
BALANCING BUREAU STANDARDS.
C. READINGS AND TEST OF DIFFUSERS, GRILLES AND REGISTERS SHALL INCLUDE
DESIGN, INITIAL TEST, AND FINAL ADJUSTED FPM VELOCITY AND CFM. ALL
DIFFUSERS, GRILLES AND REGISTERS SHALL BE BALANCED BY A HOOD THAT
HAS BEEN CALIBRATED, INCLUDING A MANOMETER, AND PILOT TUBE
READINGS SHALL BE TAKEN TO ESTABLISH TOTAL CFM FLOW IN ALL MAIN
DUCTS.
6. TEMPERATURE CONTROLS:
A. ALL TEMPERATURE CONTROLS NECESSARY FOR THE RENOVATION AND
FINISH -OUT OF THE SPACE SHALL COMPLY TO THE BASE BUILDING SYSTEM
AND CONTROL SPECIFICATIONS. BUILDING STANDARD CONTROL SYSTEM
COMPONENTS SHALL BE UTILIZED.
B. NEW THERMOSTATS OR SENSORS IF REQUIRED SHALL MATCH THE EXISTING
THERMOSTATS OR SENSORS.
C. ALL CONTROL WIRING AND POWER WIRING FOR CONTROLS SHALL BE BY THE
CONTROLS SUB - CONTRACTOR.
D. AT THE COMPLETION OF CONSTRUCTION, ALL NEW AND EXISTING
THERMOSTATS AND SENSORS SHALL BE CALIBRATED.
7. RECORDS OF OWNER
A. CONTRACTOR SHALL KEEP A CLEAN SET OF DRAWINGS ON THE JOB, NOTING
DAILY ALL CHANGES MADE IN THESE DRAWINGS IN CONNECTION WITH THE
FINAL INSTALLATION INCLUDING EXACT DIMENSIONED LOCATIONS OF ALL NEW
AND UNCOVERED EXISTING UTILITIES AND SHALL, WITH HIS REQUEST FOR FINAL
PAYMENT, TURN OVER A CLEAN, NEATLY MARKED SET OF 2 MIL
REPRODUCIBLE MYLARS SHOWING "AS INSTALLED" WORK TO THE ARCHITECT
FOR SUBSEQUENT REVIEW AND TRANSMITTAL TO THE OWNER.
CONTRACTOR SHALL NOTE ALL CONSTRUCTION CHANGES, DATE EACH SHEET
AND LABEL "AS- BUILTS" IN THE REVISION BLOCK ON THE DRAWINGS.
CONTRACTOR SHALL ALSO FURNISH ONE (1) SET OF BLUELINE PRINTS FROM
THE "AS- BUILTS" MYLARS.
B. IN ADDITION TO THE ABOVE, CONTRACTOR SHALL ACCUMULATE DURING THE
JOB'S PROGRESS, THE FOLLOWING DATA, IN TRIPLICATE, PREPARED IN A NEAT
BROCHURE OR PACKET FOLDER AND TURNED OVER TO THE ARCHITECT FOR
REVIEW AND SUBSEQUENT DELIVERY TO THE OWNER,
1. ALL WARRANTIES AND GUARANTEES AND MANUFACTURER'S
DIRECTIONS ON EQUIPMENT AND MATERIAL COVERED BY THE
CONTRACT INCLUDING THE NAMES, ADDRESSES AND TELEPHONE
NUMBERS OF THE MANUFACTURER'S REPRESENTATIVEDING 10' -0" O,C
2. APPROVED FIXTURE BROCHURES, WIRING DIAGRAMS AND
CONTROL DIAGRAMS (ORIGINAL DATA, NO COPIES).
3. COPIES OF APPROVED SHOP DRAWINGS.
4. TEST AND BALANCE REPORTS REQUIRED BY THESE
SPECIFICATIONS.
5. ANY AND ALL OTHER DATA AND /OR DRAWINGS REQUIRED
DURING CONSTRUCTION,
6. REPAIR PARTS LISTS OF ALL MAJOR ITEMS AND EQUIPMENT
INCLUDING NAME, ADDRESS AND TELEPHONE NUMBERS OF LOCAL
SUPPLIER OR AGENT.
C. ALL OF THE ABOVE DATA SHALL BE SUBMITTED TO THE ENGINEER FOR HIS
REVIEW AT SUCH TIME AS THE CONTRACTOR SUBMITS HIS LAST ESTIMATE
PRIOR TO HIS FINAL PAYMENT, BUT IN NO CASE, LESS THAN TWO WEEKS
BEFORE FINAL INSPECTION.
8. RECORDS OF OWNER
A. COMPLETE LIST OF MATERIALS TO BE FURNISHED UNDER EACH PRODUCT
SPECIFIED.
B. MANUFACTURERS' SPECIFICATIONS AND OTHER DATA REQUIRED TO ASSURE
SPECIFICATION COMPLIANCE.
C. ALL SHOP DRAWING CUT SHEETS SHALL CLEARLY IDENTIFY THE SPECIFIC
PRODUCT TO BE REVIEWED, INCLUDING MANUFACTURER. GENERIC CUT
SHEETS, INCOMPLETE CUT SHEETS AND CUT SHEETS SUBMITTED WITHOUT
IDENTIFYING THE SPECIFIC PRODUCT PROVIDED, WILL BE AUTOMATICALLY
REJECTED.
DIRECTION OF RETURN/EXHAUST AIR FLOW
BRANCH DUCT
r- MANUAL VOLUME DAMPER
0-
45 DEG.
- MAIN DUCT
TYPICAL TAP
LOW PRESSURE DUCT DETAIL
03 NO SCALE
:ADED ROD
PER SMACNA (TYP)
EET METAL DUCT
®UUT 5UIJVUK a ut I AIL
NC? SCALE
I�
SHEET METAL PLENUM
FULL SIZE OF GRILLE
NECK & MINIMUM OF
6" TALL PAINT INSIDE
OF PLENUM BLACK.
LAY -IN
CEILING
mrwm
RETURN AIR DUCT
SEE PLAN FOR SIZE
T -BAR
BY OTHERS
01 DIFFUSER /GRILLE CONNECTION
NO SCALE
GENERAL MECHANICAL NOTES
1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AND EQUIPMENT FOR THE
COMPLETION OF ALL MECHANICAL WORK SHOWN ON THE DRAWINGS AND /OR SPECIFIED. THIS
SHALL INCLUDE ANY INCIDENTAL ACCESSORIES NECESSARY TO MAKE THE WORK COMPLETE IN
ALL RESPECTS AND READY FOR OPERATION.
2. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, THE
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), AND THE LOCAL AUTHORITIES HAVING
JURISDICTION. ALL EQUIPMENT, MATERIALS, CONTROLS, ETC. SHALL BE NEW UNLESS NOTED
OTHERWISE AND SHALL MATCH ALL FACILITY STANDARDS OR IF APPROVED BY THE OWNER,
BE OF THE SAME QUALITY AS REPRESENTED BY THE SCHEDULED ITEM,
3. COORDINATE ALL WORK WITH ALL TRADES. WORK SHOWN IS INTENDED TO PROVIDE THE
OVER -ALL ENGINEERING DESIGN CONCEPT AND DOES NOT PROVIDE FOR RELOCATIONS,
OFFSETS, ETC., THAT ARE REQUIRED. COORDINATION OF TRADES SHALL BE PROVIDED BY THE
CONTRACTOR AT NO ADDITIONAL COST TO THE CONTRACT.
4. THE ROUTING OF ALL DUCTWORK AND PIPING AS SHOWN ON THE DRAWINGS ARE
DIAGRAMMATIC ONLY, INTENDING TO SHOW GENERAL RUNS AND LOCATIONS OF EQUIPMENT,
DUCTWORK, PIPING AND SPECIALTIES, THE CONTRACTOR WILL BE RESPONSIBLE FOR THE
EXACT LOCATION AND COORDINATION OF ALL ITEMS.
5. PROVIDE FINAL CONNECTION TO ALL EQUIPMENT FURNISHED BY OWNER AND /OR OTHERS.
6. ALL DUCTWORK AND PIPING SHOWN ON THE PLANS OR INDICATED BY NOTES SHALL BE
CONCEALED ABOVE THE CEILING OR IN THE WALLS UNLESS NOTED OTHERWISE,
7. DEMONSTRATE TO OWNER'S REPRESENTATIVE THAT ALL INSTALLED CONTROLS ARE WORKING
PROPERLY WITHOUT ERRORS PRIOR TO RELEASING SYSTEM TO OWNER,
8. LOCATIONS AND SIZES OF EXISTING SYSTEMS ARE APPROXIMATE. EXACT SIZES AND
LOCATIONS OF ALL EXISTING PIPING, DUCTS, ETC. SHALL BE VERIFIED ON THE JOB BY THE
CONTRACTOR.
9. CONTRACTOR SHALL INSTALL MECHANICAL SYSTEMS WITHOUT INTERFERENCE AND IN STRICT
COORDINATION WITH ALL OTHER TRADES. HOLD DUCTWORK TIGHT AGAINST UNDERSIDE OF
STRUCTURE ABOVE.
10. TAPE AND SEAL ALL ROUND DUCT CONNECTIONS TO BE PERMANENTLY AIR TIGHT.
11. EQUIPMENT CAPACITIES AND CHARACTERISTICS SHALL BE AS SCHEDULED ON THE DRAWINGS.
12. NEW CEILING DIFFUSERS TO BE TITUS OR AN ACCEPTABLE EQUIVALENT AND SUIT THE
SPECIFIED SERVICE AND CEILING TYPE UNLESS NOTED OTHERWISE ON PLANS, COORDINATE
WITH ARCHITECTURAL PLANS.
13. CEILING RETURN AIR GRILLES SHALL BE TITUS, OR AN ACCEPTABLE EQUIVALENT,
14. EXHAUST REGISTERS SHALL BE TITUS, OR AN ACCEPTABLE EQUIVALENT,
15. ALL NEW FLOOR PENETRATIONS AND PENETRATIONS THROUGH RATED WALLS SHALL BE FIRE
SAFETY RATED,
16. CONTRACTOR SHALL PREPARE AND SUBMIT FOR APPROVAL BY THE ENGINEER ALL MAJOR
ITEMS OF MATERIALS AND EQUIPMENT.
17. ALL HVAC SHUTDOWNS REQUIRED FOR THIS PROJECT, WORK REQUIRED ASSOCIATED WITH
SHUTDOWNS, AND ALL WORK IN CORRIDORS SHALL OCCUR AFTER NORMAL BUSINESS HOURS
AND SHALL BE COORDINATED WITH THE OWNER.
EXISTING AHU SCHEDULE
BALANIM
W
POSITIVE
(0)
NEUTRAL
( -)
NEGATIVE
EXISTING AHU SCHEDULE
DESIG.
SERVICE
PRE T &B CFM
NEW DESIGN CFM
NECK SIZE
PRE
FlLT.
FINAL
FlLT.
MANUFACTURER/MODEL N0,
TOTAL
CFM
RETURN
CFM
OUTSIDE
AIR CFM
TOTAL
CFM
RETURN
CFM
OUTSIDE
AIR CFM
AHU -1 -2
GENERAL ADMIN
3595
2920
675
3575
2900
675
30%
-
EXISTING
AIR DEVICE SCHEDULE
DESIG.
FRAME SIZE
I OBD
I FINISH
I THROW
NECK SIZE
100 -200
CFM
1O"O
201 -350
CFM
12 "0
S1
R1
24x24
24x24
YES
YES
WHITE
WHITE
4 -WAY U.N.O
N/A
NOTE 1
NOTE 2
NOTES: L
NECK*
AIRFLOW
6 "0
0 -99
CFM
8 "4I
100 -200
CFM
1O"O
201 -350
CFM
12 "0
351 -560
CFM
14wO
561 -850
CFM
*AND /OR DUCT RUNDUT
P1I
NECK*
AIRFLOW
6x6
0 -100
CFM
8x8
101 -230
CFM
10x10
231 -360
CFM
12x12
361 -450
CFM
16x16
451 -800
CFM
22x22
801 -1200 CFM
*AND/OR DUCT RUNDUT
MANUF./MODEL NO.
REMARKS/NOTES
TITUS / TDC -AA ALUMINUM LOUVERED SUPPLY DIFFUSER /3,4,5,6,7,8
TITUS / 350FL ALUMINUM RETURN GRILLE /3,4,5,6,7,8,9
3, DIFFUSER RUNOUT SIZE SHALL BE DIFFUSER NECK SIZE, UNLESS OTHERWISE
NOTED ON PLANS
4. PROVIDE SURFACE MOUNT HARDWARE IN ALL INACCESSABLE CEILING SYSTEMS
5. PROVIDE LAY -IN MOUNT HARDWARE IN ALL SUSPENDED CEILING SYSTEMS
6. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR LOC. OF DIFFUSERS
7. PROVIDE SELECTION BASED ON A MAXIMUM RADIATED NOISE OF NC -25
8• PROVIDE DIFFUSERS, GRILLES, AND REGISTERS MANUFACTURED FROM ALUMINUM
UNLESS NOTED OTHERWISED.
9. 35 DEGREE BLADES, 31e SPACING.
U4 4 4 4 U U U V y U U J u
V U u u V U U 4
rUUy U U 4 V :! y
U U V V U J U V V V
y U u V J U
V v
U
uuo
JJJJy�
u u
J V U
U
4
U v V
U V U L y
U U U u
U 4
0 y V 4
U v
U U U
U r) Lu0 V J
MGEARCHITECI-5
150 Alhambra Circle, Suite 700
Coral Gablea, Florida 3 3184
T.305.444.0413 F.306.441.8404
www.m8earchitecte -ccm
AA- F000121
In azacd&O with
WI I_M OT SAN Z
A R C H I T E C T U R E
P L A N N I N G
18310 Man
�,-- �
34 -500-111150
2121 Ponce de Leon Blvd„ Suite 350
Coral Gables, FL 33134
JonalConsultingEngineers phone: 305.569.1692
fax: 305.569.1693
Dallas . Houston , Nashville . Miami . Richmond
Austin . Denver . Phoenix . Washington D,C.
ccrd project number: 411442.000
EB00007658