12-365-004-7- S CL3N2-5' cc LC 7 E G EXISTING 0' 1' 2' 4' 8' EXISTING 200A DISCONNECT -- FOR PANEL CLIN PANEL- CL3N (SEC 3) PANEL- CL3N (SEC 2) N nq 1Vq- lorlh-1 XFMR 4 PANEL CL3N2 PANEL ABOVE NH3N EOL3N XFMR EOL3N KEYED NOTES: RELOCATE EXISTING LIGHT SWITCH FOR 2X4 OVERBED LIGHT TOWARDS THE FOOTWALL TO MAKE ROOM FOR NEW EXAM LIGHT CONTROL STATION. CUT AND PATCH EXISTING J WALL AS NECESSARY AND RESTORE TO ORIGINAL FINISH. BID ADD ALTERNATE: M INCLUDE ADD ALTERNATE LINE ITEM IN BID TO REMOVE THE EXISTING DOWNLIGHT FIXTURE AND TURN OVER TO OWNER. SCOPE SHALL ALSO INCLUDE REMOVAL OF LIGHT SWITCH AT HEADWALL AND PROVIDING A BLANK COVER PLATE FOR BOX. CONTRACTOR SHALL REMOVE WIRING BACK TO SOURCE. PROVIDE UNISTRUT FRAMING TO SUPPORT PANEL ABOVE TRANSFORMER SUCH THAT PANEL FRONT IS ALIGNED WITH FRONT OF TRANSFORMER. ENSURE NEC REQUIRED WORKING CLEARANCES FOR ALL OTHER EXISTING PANELS IS MAINTAINED. NEW TRANSFORMER CQN2 TO BE INSTALLED ABOVE TRANSFORMER EOL3N. REFER TO DETAIL ON SHEET EO.I FOR STACKING TRANSFORMERS. PROVIDE UNI-STRUT FRAMING TO SUPPORT MOUNTING OF NEW XMFR PRIMARY 5 DISCONNECT ADJACENT TO XFMR CL3N2. COORDINATE EXACT PLACEMENT IN FIELD TO ENSURE REQUIRED CLEARANCES ARE MAINTAINED PRIOR TO INSTALLATION. Smith Seckman Reid, Inc. _600 Wiest Hillsboro, Suite 300 'Dee;-fiel(I Beach, FL 33441 (9-1�4) 421-1260 FAX: (954) 421-1466 www.ssr-inc.com Firm Certification - EB-0000857 Dennis Davis PE - 65701 John E. Moulder PE - a3200 Michael A. Steward PE - 33200 SSR JOB # 1132078.0