EXISTING
0' 1' 2' 4' 8'
EXISTING 200A
DISCONNECT --
FOR PANEL CLIN
PANEL-
CL3N
(SEC 3)
PANEL-
CL3N
(SEC 2)
N
nq
1Vq- lorlh-1
XFMR
4 PANEL
CL3N2
PANEL ABOVE NH3N
EOL3N XFMR
EOL3N
KEYED NOTES:
RELOCATE EXISTING LIGHT SWITCH FOR 2X4 OVERBED LIGHT TOWARDS THE FOOTWALL
TO MAKE ROOM FOR NEW EXAM LIGHT CONTROL STATION. CUT AND PATCH EXISTING
J WALL AS NECESSARY AND RESTORE TO ORIGINAL FINISH.
BID ADD ALTERNATE:
M
INCLUDE ADD ALTERNATE LINE ITEM IN BID TO REMOVE THE EXISTING DOWNLIGHT
FIXTURE AND TURN OVER TO OWNER. SCOPE SHALL ALSO INCLUDE REMOVAL OF
LIGHT SWITCH AT HEADWALL AND PROVIDING A BLANK COVER PLATE FOR BOX.
CONTRACTOR SHALL REMOVE WIRING BACK TO SOURCE.
PROVIDE UNISTRUT FRAMING TO SUPPORT PANEL ABOVE TRANSFORMER SUCH THAT
PANEL FRONT IS ALIGNED WITH FRONT OF TRANSFORMER. ENSURE NEC REQUIRED
WORKING CLEARANCES FOR ALL OTHER EXISTING PANELS IS MAINTAINED.
NEW TRANSFORMER CQN2 TO BE INSTALLED ABOVE TRANSFORMER EOL3N.
REFER TO DETAIL ON SHEET EO.I FOR STACKING TRANSFORMERS.
PROVIDE UNI-STRUT FRAMING TO SUPPORT MOUNTING OF NEW XMFR PRIMARY
5 DISCONNECT ADJACENT TO XFMR CL3N2. COORDINATE EXACT PLACEMENT IN
FIELD TO ENSURE REQUIRED CLEARANCES ARE MAINTAINED PRIOR TO INSTALLATION.