12-354-006Miami -Dade Fire Rescue
Fire Alarm Pre - Submittal Checklist
Based On NFPA 72 2002 edition & NFPA 1 and 1012006 edition
Designed by: / Z 41a l Phone #: �S% �iGZ'S1� `.t3
Signature: Created by: MDFR 11 / 2009
THIS IS A REQ DOCUMENT ON ALL FIRE ALARM PLAN SUBMITTALS
YES
NO
NIA
LOCATION I COMMENTS
The FACP or remote annunciator is located at the main entrancellobby In single
40
tenant buildings, or in a common building ar=ea for multi - tenant.
The FACP and all sub panels in unoccupied rooms are protected with a smoke
41
detector.
y
If a complete automatically activated system,.there Is at least 1 manual pull station
42
provided on each floor level of the bulldin (rictuding mezzanines.
If a manually activated system, the travel distance to reach a pull station Is less
43-
than 20(' feet and within 5' feet of all required floor and for building exits.
All automatic initiating devices are shown and are located in accordance with NFPA
44
77 the manufacturers specifications, and accepted en ineerino practices.
All visual notification appliances are placed per the tables In NFPA 72 and each
X
48
strobe has its candela ratio listed on the floor Ian and riser.
All corridor spaced strobes -are placed a maximum of 100' apart and within 15' from
46
ends of the corridor.
x
47
All spaces meet the audible characteristics of NFPA 72 and NFPA 101.
Bell used for water flow indication is shown on the floor plan and riser. Bell shall be
located so as to be visible and heard from roadway or parking area adjacent to Fire
48
Dent. Connection (FDC).
Sequence of operation in regards to flow bell Indicates the following In like or
similar verbiage: A) Flow bell shall activate upon water flow only. B) Flow bell shall
continue to sound as long as water Is flowing. C) Flow bell shall not be stlenceable
49
from FACP
Walls, partition, racks, shelves and equipment which may block devices are shown
50
with their height Indicated.
Duct detectors or relays for duct detectors are shown on the floor plan and riser for
all systems over 2000 cfm. These devices are powered by the FRCP, not the AIC or
AiH units. Duct detector must receive 24 vdc source from the FACP to satisfy NFPA
51
72 4A.T
A complete system riser diagram Is provided showing each floor and building with
52
all zones and circuits labeled.
The wire size, type, and number of conductors are provided for each circuit on
53
riser.
X
The fire pump is monitored for A) Pump or Motor Running, B) Loss of Phase, C)
Phase Reversal, and, If applicable, D) Controller connected to alternate source; and
are Indicated at _ a continuously manned location, or _ the supervised fire
54
alarms stem.
All relays for automatic extinguishing systems are shown on the floor plan and
55
riser. Hood, sprinkler, FM200 etc Clarify use of all relays on riser.
The ampacity of each power supply and circuits is specified for each FACP & NAC
!
56
panel. Also Individual device current is specified on riser.
✓1
The total footage to the last device including voltage drop calculations are provided
57
for each notification appliance circuit for each power supply.
58
The wattage tap is Indicated for all speakers.
59
The wattage capacltX and load Is provided for each amplifier.
All load values for stand -by and alarm used in calculations are high- lighted on the
manufacturer's specification and 1 or installation sheets. Also, ampacity of
°t
60
equipment I components and circuits are highlighted as well.
This system Includes Emergency Voice Evacuation and is provided with 15 minutes
of secondary alarm power. Required in all high rises and assembly occupancies
�[
61
with an occupant load greater than 300.
'\
Th is system Is being provided back up power by an emergency generator, In lieu of
batteries, and will be provided 4 hours of standby power plus the appropriate
3(
62
secondary alarm eower by the generator.
`
Battery calculations, detailed In chart form, showing all information required per
63
NFPA 72 4.4.1.5.3.1 are provided for each back-up power supply,
The location of Backflow Preventer (BFP), Post Indicating Valve (PIV) and Fire DepL
64
Connection are Indicated on the plans for sorinklered buildings.
165
Area smoke detectors, If used, shall provide coverage throughout the entire smoke
compartment
Designed by: / Z 41a l Phone #: �S% �iGZ'S1� `.t3
Signature: Created by: MDFR 11 / 2009
THIS IS A REQ DOCUMENT ON ALL FIRE ALARM PLAN SUBMITTALS